Product range |
Main switch maintenance switch Repair switch |
Part group reference |
T3 |
Stop Function |
STOP function |
Notes |
With black rotary handle and locking ring |
Number of poles |
in steel enclosure |
Locking facility |
8-pole |
Degree of Protection |
Lockable in the 0 (Off) position |
Design |
IP65 |
Contact sequence |
|
Switching angle |
surface mounting |
Design number |
|
Function |
|
400 V [P] |
90 ° |
Rated uninterrupted current [Iu] |
8344 |
Note on rated uninterrupted current !u |
|
Number of contact units |
15 kW |
Standards |
32 A |
Ambient temperature >Enclosed |
Rated uninterrupted current Iu is specified for max. cross-section. |
Overvoltage category/pollution degree |
4 contact unit(s) |
Rated impulse withstand voltage [Uimp] |
IEC/EN 60947, VDE 0660, IEC/EN 60204 Switch disconnector in accordance with IEC/EN 60947-3 |
Mechanical shock resistance |
-25 - +40 °C |
Mounting position |
III/3 |
Mechanical variables >Number of poles |
6000 V AC |
Electrical characteristics >Rated operational voltage [Ue] |
15 g |
Electrical characteristics >Rated uninterrupted current [Iu] |
As required |
Electrical characteristics >Note on rated uninterrupted current !u |
8-pole |
Load rating with intermittent operation, class 12 >AB 25 % DF |
690 V AC |
Load rating with intermittent operation, class 12 >AB 40 % DF |
32 A |
Load rating with intermittent operation, class 12 >AB 60 % DF |
Rated uninterrupted current Iu is specified for max. cross-section. |
Short-circuit rating >Fuse |
2 x Ie |
Rated short-time withstand current (1 s current) [Icw
] |
1.6 x Ie |
Note on rated short-time withstand current lcw |
1.3 x Ie |
Rated conditional short-circuit current [Iq] |
35 A gG/gL |
cos ϕ rated making capacity as per IEC 60947-3 |
650 Arms |
Rated breaking capacity cos ϕ to IEC 60947-3 >230 V |
Current for a time of 1 second |
Rated breaking capacity cos ϕ to IEC 60947-3 >400/415 V |
1 kA |
Rated breaking capacity cos ϕ to IEC 60947-3 >500 V |
320 A |
Rated breaking capacity cos ϕ to IEC 60947-3 >690 V |
260 A |
Safe isolation to EN 61140 >between the contacts |
260 A |
Safe isolation to EN 61140 >Current heat loss per contact at Ie |
240 A |
Safe isolation to EN 61140 >Current heat loss per auxiliary circuit at Ie (AC-15/230 V) |
170 A |
Lifespan, mechanical [Operations] |
440 V AC |
Maximum operating frequency [Operations/h] |
1.1 W |
AC >AC-3 >Rating, motor load switch [P] >220 V 230 V [P] |
1.1 CO |
AC >AC-3 >Rating, motor load switch [P] >230 V Star-delta [P] |
> 0.5 x 106 |
AC >AC-3 >Rating, motor load switch [P] >400 V 415 V [P] |
1200 |
AC >AC-3 >Rating, motor load switch [P] >400 V Star-delta [P] |
5.5 kW |
AC >AC-3 >Rating, motor load switch [P] >500 V [P] |
7.5 kW |
AC >AC-3 >Rating, motor load switch [P] >500 V Star-delta [P] |
11 kW |
AC >AC-3 >Rating, motor load switch [P] >690 V [P] |
15 kW |
AC >AC-3 >Rating, motor load switch [P] >690 V Star-delta [P] |
15 kW |
AC >AC-3 >Rated operational current motor load switch >230 V [Ie] |
18.5 kW |
AC >AC-3 >Rated operational current motor load switch >230 V star-delta [Ie] |
11 kW |
AC >AC-3 >Rated operational current motor load switch >400V 415 V [Ie] |
22 kW |
AC >AC-3 >Rated operational current motor load switch >400 V star-delta [Ie] |
23.7 A |
AC >AC-3 >Rated operational current motor load switch >500 V [Ie
] |
32 A |
AC >AC-3 >Rated operational current motor load switch >500 V star-delta [Ie
] |
23.7 A |
AC >AC-3 >Rated operational current motor load switch >690 V [Ie] |
32 A |
AC >AC-3 >Rated operational current motor load switch >690 V star-delta [Ie] |
23.7 A |
AC >AC-21A >Rated operational current switch >440 V [Ie] |
32 A |
AC >AC-23A >Motor rating AC-23A, 50 - 60 Hz [P] >230 V [P] |
14.7 A |
AC >AC-23A >Motor rating AC-23A, 50 - 60 Hz [P] >400 V 415 V [P] |
25.5 A |
AC >AC-23A >Motor rating AC-23A, 50 - 60 Hz [P] >500 V [P] |
32 A |
AC >AC-23A >Motor rating AC-23A, 50 - 60 Hz [P] >690 V [P] |
7.5 kW |
AC >AC-23A >Rated operational current motor load switch >230 V [Ie] |
15 kW |
AC >AC-23A >Rated operational current motor load switch >400 V 415 V [Ie] |
15 kW |
AC >AC-23A >Rated operational current motor load switch >500 V [Ie] |
15 kW |
AC >AC-23A >Rated operational current motor load switch >690 V [Ie] |
32 A |
DC >DC-1, Load-break switches L/R = 1 ms >Rated operational current [Ie] |
32 A |
DC >DC-1, Load-break switches L/R = 1 ms >Voltage per contact pair in series |
26.4 A |
DC >DC-21A [Ie
] >Rated operational current [Ie] |
17 A |
DC >DC-21A [Ie
] >Contacts |
25 A |
DC >DC-23A, motor load switch
L/R = 15 ms >24 V >Rated operational current [Ie] |
60 V |
DC >DC-23A, motor load switch
L/R = 15 ms >24 V >Contacts |
1 A |
DC >DC-23A, motor load switch
L/R = 15 ms >48 V >Rated operational current [Ie] |
1 Quantity |
DC >DC-23A, motor load switch
L/R = 15 ms >48 V >Contacts |
25 A |
DC >DC-23A, motor load switch
L/R = 15 ms >60 V >Rated operational current [Ie] |
1 Quantity |
DC >DC-23A, motor load switch
L/R = 15 ms >60 V >Contacts |
25 A |
DC >DC-23A, motor load switch
L/R = 15 ms >120 V >Rated operational current [Ie] |
2 Quantity |
DC >DC-23A, motor load switch
L/R = 15 ms >120 V >Contacts |
25 A |
DC >DC-23A, motor load switch
L/R = 15 ms >240 V >Rated operational current [Ie] |
3 Quantity |
DC >DC-23A, motor load switch
L/R = 15 ms >240 V >Contacts |
12 A |
DC >DC-13, Control switches L/R = 50 ms >Rated operational current [Ie] |
3 Quantity |
DC >DC-13, Control switches L/R = 50 ms >Voltage per contact pair in series |
5 A |
Control circuit reliability at 24 V DC, 10 mA [Fault probability] |
5 Quantity |
Solid or stranded |
20 A |
Flexible with ferrules to DIN 46228 |
24 V |
Terminal screw |
< 10 -5, < 1 fault in 100000 operations HF
|
Tightening torque for terminal screw |
1 x (1 - 6) 2 x (1 - 6) mm2
|
Notes |
1 x (0.75 - 4) 2 x (0.75 - 4) mm2 |
Terminal capacity >Terminal screw |
M4 |
Terminal capacity >Tightening torque |
1.6 Nm |
Version as main switch |
B10d values as per EN ISO 13849-1, table C1 |
Version as maintenance-/service switch |
M4 |
Version as safety switch |
17.7 lb-in |
Version as emergency stop installation |
No |
Version as reversing switch |
Yes |
Number of switches |
No |
Max. rated operation voltage Ue AC |
No |
Rated operating voltage |
No |
Rated permanent current Iu |
1 |
Rated permanent current at AC-23, 400 V |
690 V |
Rated permanent current at AC-21, 400 V |
690 - 690 V |
Rated operation power at AC-3, 400 V |
32 A |
Rated short-time withstand current lcw |
32 A |
Rated operation power at AC-23, 400 V |
32 A |
Switching power at 400 V |
11 kW |
Conditioned rated short-circuit current Iq |
0.65 kA |
Number of poles |
15 kW |
Number of auxiliary contacts as normally closed contact |
15 kW |
Number of auxiliary contacts as normally open contact |
1 kA |
Number of auxiliary contacts as change-over contact |
8 |
Motor drive optional |
0 |
Motor drive integrated |
0 |
Voltage release optional |
0 |
Device construction |
No |
Suitable for ground mounting |
No |
Suitable for front mounting 4-hole |
No |
Suitable for front mounting centre |
Complete device in housing |
Suitable for distribution board installation |
Yes |
Suitable for intermediate mounting |
No |
Colour control element |
No |
Type of control element |
No |
Interlockable |
No |
Type of electrical connection of main circuit |
Black |
Degree of protection (IP), front side |
Door coupling rotary drive |
Degree of protection (NEMA) |
Yes |