Product range |
Main switch maintenance switch Repair switch |
Part group reference |
P3 |
Stop Function |
STOP function |
Information about equipment supplied |
with black rotary handle and lock ring (K series) |
Notes |
auxiliary contact fitted by user. |
Number of poles |
With metal shaft for a control panel depth of 400 mm |
Locking facility |
3 pole + N |
Degree of Protection |
0 N/O |
Design |
0 N/C |
Contact sequence |
Lockable in the 0 (Off) position |
Front plate no. |
Front IP65 |
400 V [P] |
rear mounting |
Rated uninterrupted current [Iu] |
|
Note on rated uninterrupted current !u |
|
Standards |
|
Climatic proofing |
55 kW |
Ambient temperature >Open |
100 A |
Ambient temperature >Enclosed |
Rated uninterrupted current Iu is specified for max. cross-section. |
Overvoltage category/pollution degree |
IEC/EN 60947, VDE 0660, IEC/EN 60204 Switch-disconnector according to IEC/EN 60947-3 |
Rated impulse withstand voltage [Uimp] |
Damp heat, constant, to IEC 60068-2-78 Damp heat, cyclic, to IEC 60068-2-30 |
Mechanical shock resistance |
-25 - +50 °C |
Mounting position |
-25 - +40 °C |
Mechanical variables >Number of poles |
III/3 |
Mechanical variables >Auxiliary contacts0 N/O
Mechanical variables >Auxiliary contacts 0 N/C
Electrical characteristics >Rated operational voltage [Ue] |
6000 V AC |
Electrical characteristics >Rated uninterrupted current [Iu] |
15 g |
Electrical characteristics >Note on rated uninterrupted current !u |
As required |
Load rating with intermittent operation, class 12 >AB 25 % DF |
3 pole + N |
Load rating with intermittent operation, class 12 >AB 40 % DF |
0 N/O |
Load rating with intermittent operation, class 12 >AB 60 % DF |
0 N/C |
Short-circuit rating >Fuse |
690 V AC |
Rated short-time withstand current (1 s current) [Icw
] |
100 A |
Note on rated short-time withstand current lcw |
Rated uninterrupted current Iu is specified for max. cross-section. |
Rated conditional short-circuit current [Iq] |
2 x Ie |
cos ϕ rated making capacity as per IEC 60947-3 |
1.6 x Ie |
Rated breaking capacity cos ϕ to IEC 60947-3 >230 V |
1.3 x Ie |
Rated breaking capacity cos ϕ to IEC 60947-3 >400/415 V |
100 A gG/gL |
Rated breaking capacity cos ϕ to IEC 60947-3 >500 V |
2000 Arms |
Rated breaking capacity cos ϕ to IEC 60947-3 >690 V |
Current for a time of 1 second |
Safe isolation to EN 61140 >between the contacts |
4 kA |
Safe isolation to EN 61140 >Current heat loss per contact at Ie |
950 A |
Lifespan, mechanical [Operations] |
760 A |
Maximum operating frequency [Operations/h] |
740 A |
AC >AC-3 >Rating, motor load switch [P] >220 V 230 V [P] |
880 A |
AC >AC-3 >Rating, motor load switch [P] >400 V 415 V [P] |
520 A |
AC >AC-3 >Rating, motor load switch [P] >500 V [P] |
440 V AC |
AC >AC-3 >Rating, motor load switch [P] >690 V [P] |
7.5 W |
AC >AC-3 >Rated operational current motor load switch >230 V [Ie] |
> 0.1 x 106 |
AC >AC-3 >Rated operational current motor load switch >400V 415 V [Ie] |
1200 |
AC >AC-3 >Rated operational current motor load switch >500 V [Ie
] |
22 kW |
AC >AC-3 >Rated operational current motor load switch >690 V [Ie] |
37 kW |
AC >AC-21A >Rated operational current switch >440 V [Ie] |
45 kW |
AC >AC-23A >Motor rating AC-23A, 50 - 60 Hz [P] >230 V [P] |
37 kW |
AC >AC-23A >Motor rating AC-23A, 50 - 60 Hz [P] >400 V 415 V [P] |
71 A |
AC >AC-23A >Motor rating AC-23A, 50 - 60 Hz [P] >500 V [P] |
71 A |
AC >AC-23A >Motor rating AC-23A, 50 - 60 Hz [P] >690 V [P] |
65 A |
AC >AC-23A >Rated operational current motor load switch >230 V [Ie] |
23.8 A |
AC >AC-23A >Rated operational current motor load switch >400 V 415 V [Ie] |
100 A |
AC >AC-23A >Rated operational current motor load switch >500 V [Ie] |
30 kW |
AC >AC-23A >Rated operational current motor load switch >690 V [Ie] |
55 kW |
DC >DC-1, Load-break switches L/R = 1 ms >Rated operational current [Ie] |
55 kW |
DC >DC-1, Load-break switches L/R = 1 ms >Voltage per contact pair in series |
55 kW |
DC >DC-23A, motor load switch
L/R = 15 ms >24 V >Rated operational current [Ie] |
100 A |
DC >DC-23A, motor load switch
L/R = 15 ms >24 V >Contacts |
100 A |
DC >DC-23A, motor load switch
L/R = 15 ms >48 V >Rated operational current [Ie] |
96 A |
DC >DC-23A, motor load switch
L/R = 15 ms >48 V >Contacts |
68 A |
DC >DC-23A, motor load switch
L/R = 15 ms >60 V >Rated operational current [Ie] |
100 A |
DC >DC-23A, motor load switch
L/R = 15 ms >60 V >Contacts |
60 V |
DC >DC-23A, motor load switch
L/R = 15 ms >120 V >Rated operational current [Ie] |
50 A |
DC >DC-23A, motor load switch
L/R = 15 ms >120 V >Contacts |
1 Quantity |
Control circuit reliability at 24 V DC, 10 mA [Fault probability] |
50 A |
Solid or stranded |
2 Quantity |
Flexible with ferrules to DIN 46228 |
50 A |
Tightening torque for terminal screw |
2 Quantity |
Notes |
25 A |
Rated operational current for specified heat dissipation [In] |
3 Quantity |
Heat dissipation per pole, current-dependent [Pvid] |
< 10 -5, < 1 fault in 100000 operations HF
|
Equipment heat dissipation, current-dependent [Pvid] |
1 x (2,5 - 35) 2 x (2,5 - 10) mm2
|
Static heat dissipation, non-current-dependent [Pvs] |
1 x (1.5 - 25) 2 x (1.5 - 6) mm2 |
Heat dissipation capacity [Pdiss] |
3 Nm |
Operating ambient temperature min. |
B10d values as per EN ISO 13849-1, table C1 |
Operating ambient temperature max. |
100 A |
10.2 Strength of materials and parts >10.2.2 Corrosion resistance |
7.5 W |
10.2 Strength of materials and parts >10.2.3.1 Verification of thermal stability of enclosures |
0 W |
10.2 Strength of materials and parts >10.2.3.2 Verification of resistance of insulating materials to normal heat |
0 W |
10.2 Strength of materials and parts >10.2.3.3 Verification of resistance of insulating materials to abnormal heat and fire due to internal electric effects |
0 W |
10.2 Strength of materials and parts >10.2.4 Resistance to ultra-violet (UV) radiation |
-25 °C |
10.2 Strength of materials and parts >10.2.5 Lifting |
+50 °C |
10.2 Strength of materials and parts >10.2.6 Mechanical impact |
Meets the product standard´s requirements. |
10.2 Strength of materials and parts >10.2.7 Inscriptions |
Meets the product standard´s requirements. |
10.3 Degree of protection of ASSEMBLIES |
Meets the product standard´s requirements. |
10.4 Clearances and creepage distances |
Meets the product standard´s requirements. |
10.5 Protection against electric shock |
UV resistance only in connection with protective shield. |
10.6 Incorporation of switching devices and components |
Does not apply, since the entire switchgear needs to be evaluated. |
10.7 Internal electrical circuits and connections |
Does not apply, since the entire switchgear needs to be evaluated. |
10.8 Connections for external conductors |
Meets the product standard´s requirements. |
10.9 Insulation properties >10.9.2 Power-frequency electric strength |
Does not apply, since the entire switchgear needs to be evaluated. |
10.9 Insulation properties >10.9.3 Impulse withstand voltage |
Meets the product standard´s requirements. |
10.9 Insulation properties >10.9.4 Testing of enclosures made of insulating material |
Does not apply, since the entire switchgear needs to be evaluated. |
10.10 Temperature rise |
Does not apply, since the entire switchgear needs to be evaluated. |
10.11 Short-circuit rating |
Is the panel builder´s responsibility. |
10.12 Electromagnetic compatibility |
Is the panel builder´s responsibility. |
10.13 Mechanical function |
Is the panel builder´s responsibility. |
Version as main switch |
Is the panel builder´s responsibility. |
Version as maintenance-/service switch |
Is the panel builder´s responsibility. |
Version as safety switch |
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices. |
Version as emergency stop installation |
Is the panel builder´s responsibility. The specifications for the switchgear must be observed. |
Version as reversing switch |
Is the panel builder´s responsibility. The specifications for the switchgear must be observed. |
Number of switches |
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed. |
Max. rated operation voltage Ue AC |
Yes |
Rated operating voltage |
Yes |
Rated permanent current Iu |
No |
Rated permanent current at AC-23, 400 V |
No |
Rated permanent current at AC-21, 400 V |
No |
Rated operation power at AC-3, 400 V |
1 |
Rated short-time withstand current lcw |
690 V |
Rated operation power at AC-23, 400 V |
690 - 690 V |
Switching power at 400 V |
100 A |
Conditioned rated short-circuit current Iq |
100 A |
Number of poles |
100 A |
Number of auxiliary contacts as normally closed contact |
37 kW |
Number of auxiliary contacts as normally open contact |
2 kA |
Number of auxiliary contacts as change-over contact |
55 kW |
Motor drive optional |
55 kW |
Motor drive integrated |
4 kA |
Voltage release optional |
4 |
Device construction |
0 |
Suitable for ground mounting |
0 |
Suitable for front mounting 4-hole |
0 |
Suitable for front mounting centre |
No |
Suitable for distribution board installation |
No |
Suitable for intermediate mounting |
No |
Colour control element |
Built-in device fixed built-in technique |
Type of control element |
Yes |
Interlockable |
No |
Type of electrical connection of main circuit |
No |
Degree of protection (IP), front side |
No |
Degree of protection (NEMA) |
Yes |