Product range |
Accessories |
Accessories |
Communications module |
Standard/Approval |
UL/CSA, IEC |
Construction size |
NZM…2(3)(4)-MX(VX)(PX)(PMX)… ; IZMX… |
Description |
For Fieldbus connection to the IZMX and NZM circuit breakers. The module is mounted externally near the circuit breaker. Connection to PROFIBUS-DP Cannot be used with the PXR10 NZM-AX electronic trip. |
For use with |
NZM2(3)(4)(-4)-VX(MX)(PX)(PMX) IZMX... |
Type of the fieldbus interface |
Profibus DP |
Participant type |
Slave |
Kommunikatonsparameter
>NZM connection |
Pre-wired connection |
Kommunikatonsparameter
>Fieldbus connection |
Customer-wired standard Profibus connection |
Rated control voltage [Us
] >DC [Us
] |
24-24 V DC |
Rated control voltage [Us
] >Tolerance |
+/- 20% |
Rated control voltage [Us
] >Power consumption [Pmax.] |
6 W |
Rated control voltage [Us
] >Connection >Connection type |
With bolt connection |
Rated control voltage [Us
] >Connection >Stripping length |
7 mm |
Rated control voltage [Us
] >Connection >Terminal capacity >Solid |
1 x (0.2 - 2.0) mm2 |
Rated control voltage [Us
] >Connection >Terminal capacity >Stranded |
1 x (0.2 - 2.0) mm2
|
Rated control voltage [Us
] >Connection >Terminal capacity |
1 x (24 - 14) AWG |
Rated control voltage [Us
] >Connection >Terminal capacity >with ferrule acc. to DIN46224 / 1
|
1 x (0,2 - 2,0) mm2 |
Rated control voltage [Us
] >Connection >Terminal capacity >with ferrule with plastic collar acc. to DIN46228 / 4
|
1 x (0,2 - 2,0) mm2 |
Digital-Eingänge
>Quantity |
3 |
Digital-Eingänge
>Input current |
5 mA |
Digital-Eingänge
>Power supply |
24 V DC |
Digital-Eingänge
>Input impedance |
5 kΩ |
Digital-Eingänge
>Connection >Connection type |
With bolt connection |
Digital-Eingänge
>Connection >Stripping length |
7 mm |
Digital-Eingänge
>Connection >Terminal capacity >Solid |
1 x (0.2 - 2.0) mm2
|
Digital-Eingänge
>Connection >Terminal capacity >Stranded |
1 x (0.2 - 2.0) mm2
|
Digital-Eingänge
>Connection >Terminal capacity |
1 x (24 - 14) AWG |
Digital-Eingänge
>Connection >Terminal capacity >with ferrule acc. to DIN46224 / 1
|
1 x (0,2 - 2,0) mm2 |
Digital-Eingänge
>Connection >Terminal capacity >with ferrule with plastic collar acc. to DIN46228 / 4
|
1 x (0,2 - 2,0) mm2 |
Relay outputs >Number |
2 |
Relay outputs >Contact sequence |
|
Relay outputs >Rated control voltage [Us
] >AC [Us
] |
24-30 V AC |
Relay outputs >Contacts >Overvoltage category/pollution degree |
II/2 |
Relay outputs >Switching capacity >Rated operational current >AC–1 >220V230V240V [Ie] |
2 A |
Relay outputs >Switching capacity >Rated operational current >DC-1 >24 V [Ie
] |
2 A |
Relay outputs >Connection >Connection type |
With bolt connection |
Relay outputs >Connection >Stripping length |
7 mm |
Relay outputs >Connection >Terminal capacity >Solid |
1 x (0,2 - 2,0) mm2
|
Relay outputs >Connection >Terminal capacity >Stranded |
1 x (0,2 - 2,0) mm2
|
Relay outputs >Connection >Terminal capacity |
1 x (24 - 14) AWG |
Relay outputs >Connection >Terminal capacity >with ferrule acc. to DIN46224 / 1
|
1 x (0,2 - 2,0) mm2 |
Relay outputs >Connection >Terminal capacity >with ferrule with plastic collar acc. to DIN46228 / 4
|
1 x (0,2 - 2,0) mm2 |
Relay outputs >Operating ambient temperature min. |
-20 °C |
Relay outputs >Operating ambient temperature max. |
+70 °C |
Relay outputs >Min. ambient temperature, storage |
- 45 °C |
Relay outputs >Ambient temperature, storage max. |
+ 85 °C |
Operating ambient temperature min. |
-20 °C |
Operating ambient temperature max. |
+70 °C |
10.2 Strength of materials and parts >10.2.2 Corrosion resistance |
Meets the product standard´s requirements. |
10.2 Strength of materials and parts >10.2.3.1 Verification of thermal stability of enclosures |
Meets the product standard´s requirements. |
10.2 Strength of materials and parts >10.2.3.2 Verification of resistance of insulating materials to normal heat |
Meets the product standard´s requirements. |
10.2 Strength of materials and parts >10.2.3.3 Verification of resistance of insulating materials to abnormal heat and fire due to internal electric effects |
Meets the product standard´s requirements. |
10.2 Strength of materials and parts >10.2.4 Resistance to ultra-violet (UV) radiation |
Meets the product standard´s requirements. |
10.2 Strength of materials and parts >10.2.5 Lifting |
Does not apply, since the entire switchgear needs to be evaluated. |
10.2 Strength of materials and parts >10.2.6 Mechanical impact |
Does not apply, since the entire switchgear needs to be evaluated. |
10.2 Strength of materials and parts >10.2.7 Inscriptions |
Meets the product standard´s requirements. |
10.3 Degree of protection of ASSEMBLIES |
Does not apply, since the entire switchgear needs to be evaluated. |
10.4 Clearances and creepage distances |
Meets the product standard´s requirements. |
10.5 Protection against electric shock |
Does not apply, since the entire switchgear needs to be evaluated. |
10.6 Incorporation of switching devices and components |
Does not apply, since the entire switchgear needs to be evaluated. |
10.7 Internal electrical circuits and connections |
Is the panel builder´s responsibility. |
10.8 Connections for external conductors |
Is the panel builder´s responsibility. |
10.9 Insulation properties >10.9.2 Power-frequency electric strength |
Is the panel builder´s responsibility. |
10.9 Insulation properties >10.9.3 Impulse withstand voltage |
Is the panel builder´s responsibility. |
10.9 Insulation properties >10.9.4 Testing of enclosures made of insulating material |
Is the panel builder´s responsibility. |
10.10 Temperature rise |
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices. |
10.11 Short-circuit rating |
Is the panel builder´s responsibility. The specifications for the switchgear must be observed. |
10.12 Electromagnetic compatibility |
Is the panel builder´s responsibility. The specifications for the switchgear must be observed. |
10.13 Mechanical function |
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed. |
Type of accessory |
Communication and measuring function |