Kaçak akım devre kesici (RCCB), 100A, 4 p, 300mA, tip S/A Kaçak akım devre kesici PF7, 4 kutuplu, Nominal akım In: 100 A, Nominal kısa devre gücü Icn: 10 kA, Nominal arıza akımı IΔN: 0,3 A, Tip S/A, Darbe akımına duyarlı, aşırı gerilime dayanıklı 5 kA , Konut ve ticari uygulamalara yönelik şalt cihazları
Kaçak akım devre kesici (RCCB), 100A, 4 p, 300mA, tip S/A
Kaçak akım devre kesici PF7, 4 kutuplu, Nominal akım In: 100 A, Nominal kısa devre gücü Icn: 10 kA, Nominal arıza akımı IΔN: 0,3 A, Tip S/A, Darbe akımına duyarlı, aşırı gerilime dayanıklı 5 kA , Konut ve ticari uygulamalara yönelik şalt cihazları
Basic function | Residual current circuit-breakers |
Number of poles | 4 pole |
Application | Residual current circuit-breaker for residential and commercial applications |
Rated current [In] | 100 A |
Rated short-circuit strength [Icn] | 10 kA |
Rated fault current [IΔN] | 0.3 A |
Type | Type S/A |
Tripping | selective switch off s… |
Product range | PF7 |
Sensitivity | Pulse-current sensitive |
Impulse withstand current | surge-proof 5 kA |
Standards | IEC/EN 61008 |
Rated operational voltage [Ue] [Ue]Rated operating voltage [Ue] | 230/400 V AC |
Rated frequency [f] | 50 Hz |
Limit values of the operating voltage >Test circuit |
184 - 440 V AC |
Sensitivity | Pulse-current sensitive |
Rated insulation voltage [Ui ] | 440 V |
Rated impulse withstand voltage [Uimp] | 4 kV |
Rated short-circuit strength [Icn] | 10 kA |
Rated making and breaking capacity / Rated residual making and breaking capacity [Im / IΔm] | 1000 A |
lifespan >Electrical [Operations] |
≧ 4000 |
lifespan >Mechanical [Operations] |
≧ 20000 |
Auxiliary switch for subsequent installation | Z-HK 248432 |
Tripping signal contact for subsequent installation | Z-NHK 248434 |
Remote control and automatic switching device | Z-FW/LP 248296 |
Compact enclosure | KLV-TC-4 276241 |
Switching interlock | IS/SPE-1TE 101911 |
Sealing cover set | Z-RC/AK-4TE 101062 |
Standard front dimension | 45 mm |
Device height | 80 mm |
Built-in width | 70 (4TE) mm |
Mounting | Quick attachment with 2 latch positions for DIN-rail IEC/EN 60715 |
Degree of Protection | IP40, IP54 (with moisture-proof enclosure) |
Terminals top and bottom | Open mouthed/lift terminals |
Terminal protection | BGV A3, ÖVE-EN 6 |
Terminal cross-section >Solid |
1.5 - 35 mm2 |
Terminal cross-section >Stranded |
2 x 16 mm2 |
Thickness of busbar material | 0.8 - 2 mm |
Permissible storage and transport temperatures | -35 - +60 °C |
Climatic proofing | 25-55°C/90-95% relative humidity according to IEC 60068-2 |
Thickness of busbar material >Material thickness |
0.8 - 2 mm |
Rated operational current for specified heat dissipation [In] | 100 A |
Heat dissipation per pole, current-dependent [Pvid] | 0 W |
Equipment heat dissipation, current-dependent [Pvid] | 18.8 W |
Static heat dissipation, non-current-dependent [Pvs] | 0 W |
Heat dissipation capacity [Pdiss] | 0 W |
Operating ambient temperature min. | -25 °C |
Operating ambient temperature max. | +60 °C |
10.2 Strength of materials and parts >10.2.2 Corrosion resistance |
Starting at 40 °C, the max. permissible continuous current decreases by 1.2% for every 1 °C |
10.2 Strength of materials and parts >10.2.3.1 Verification of thermal stability of enclosures |
Meets the product standard´s requirements. |
10.2 Strength of materials and parts >10.2.3.2 Verification of resistance of insulating materials to normal heat |
Meets the product standard´s requirements. |
10.2 Strength of materials and parts >10.2.3.3 Verification of resistance of insulating materials to abnormal heat and fire due to internal electric effects |
Meets the product standard´s requirements. |
10.2 Strength of materials and parts >10.2.4 Resistance to ultra-violet (UV) radiation |
Meets the product standard´s requirements. |
10.2 Strength of materials and parts >10.2.5 Lifting |
Meets the product standard´s requirements. |
10.2 Strength of materials and parts >10.2.6 Mechanical impact |
Does not apply, since the entire switchgear needs to be evaluated. |
10.2 Strength of materials and parts >10.2.7 Inscriptions |
Does not apply, since the entire switchgear needs to be evaluated. |
10.3 Degree of protection of ASSEMBLIES | Meets the product standard´s requirements. |
10.4 Clearances and creepage distances | Does not apply, since the entire switchgear needs to be evaluated. |
10.5 Protection against electric shock | Meets the product standard´s requirements. |
10.6 Incorporation of switching devices and components | Does not apply, since the entire switchgear needs to be evaluated. |
10.7 Internal electrical circuits and connections | Does not apply, since the entire switchgear needs to be evaluated. |
10.8 Connections for external conductors | Is the panel builder´s responsibility. |
10.9 Insulation properties >10.9.2 Power-frequency electric strength |
Is the panel builder´s responsibility. |
10.9 Insulation properties >10.9.3 Impulse withstand voltage |
Is the panel builder´s responsibility. |
10.9 Insulation properties >10.9.4 Testing of enclosures made of insulating material |
Is the panel builder´s responsibility. |
10.10 Temperature rise | Is the panel builder´s responsibility. |
10.11 Short-circuit rating | The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices. |
10.12 Electromagnetic compatibility | Is the panel builder´s responsibility. The specifications for the switchgear must be observed. |
10.13 Mechanical function | Is the panel builder´s responsibility. The specifications for the switchgear must be observed. |
Number of poles | The device meets the requirements, provided the information in the instruction leaflet (IL) is observed. |
Rated voltage | 4 |
Rated current | 400 V |
Rated fault current | 100 A |
Rated insulation voltage Ui | 300 mA |
Rated impulse withstand voltage Uimp | 440 V |
Mounting method | 4 kV |
Leakage current type | DIN rail |
Selective protection | A |
Short-time delayed tripping | Yes |
Short-circuit breaking capacity (Icw) | No |
Surge current capacity | 10 kA |
Frequency | 0.25 kA |
Additional equipment possible | 50 Hz |
With interlocking device | Yes |
Degree of protection (IP) | Yes |
Width in number of modular spacings | IP20 |
Built-in depth | 4 |
Ambient temperature during operating | 69.5 mm |
Pollution degree | -25 - 40 °C |
Connectable conductor cross section multi-wired | 2 |
Connectable conductor cross section solid-core | 1.5 - 16 mm² |
Mnelko olarak, endüstriyel otomasyon çözümlerinde güvenilir bir iş ortağı olarak, geniş ürün yelpazesi ile işletmenizin tüm ihtiyaçlarını karşılamaya yönelik kaliteli ve yenilikçi ürünler sunmaktayız. Ürün portföyümüz, modern endüstriyel süreçleri desteklemek amacıyla yüksek performans, dayanıklılık ve verimlilik ilkeleri doğrultusunda tasarlanmış çözümlerden oluşur.
Tüm ürünlerimiz, zorlu çalışma koşullarında dahi maksimum güvenilirlik sunar ve işletmenizin operasyonlarını sorunsuz şekilde sürdürmesine yardımcı olur. Endüstriyel otomasyon, enerji yönetimi, kablolama çözümleri ve daha birçok alanda sunduğumuz ürünler, farklı sektörlerdeki ihtiyaçlara esneklikle uyum sağlar.
Ayrıca, ürünlerimiz sadece kaliteli malzemelerle üretilmiş olup, uluslararası standartlara uygunluk göstermektedir. Müşterilerimize sunduğumuz çözümlerle, operasyonel verimliliklerini artırmalarına ve maliyetlerini optimize etmelerine olanak tanıyoruz. Teknolojik gelişmeleri yakından takip eden firmamız, sürekli olarak yenilikçi ürünler sunarak, müşterilerimizin rekabet avantajı elde etmesine destek vermektedir.
Her bir ürün sayfamızda, teknik detaylar, kullanım alanları ve ürün özelliklerine dair kapsamlı bilgilere ulaşabilirsiniz. Endüstriyel süreçlerinizi güçlendirmek için ihtiyacınız olan tüm ürünleri sitemizden keşfedebilir, sorunsuz bir satın alma deneyimi yaşayabilirsiniz.