NZMS3-ME350-AVE
113555 NZMS3-ME350-AVE
113555

Devre kesici, 350 A, 3 kutuplu, motor koruması için elektronik serbest bırakmalı, çekmeceli Devre kesici NZM3, 3 kutuplu, Nominal akım = nominal kesintisiz akım ( In = Iu ): 350 A, Montaj tipi: Çekmeceli, Vidalı bağlantı, Standart/Onay: IEC, Koruma fonksiyonu: Motor koruma

Devre kesici, 350 A, 3 kutuplu, motor koruması için elektronik serbest bırakmalı, çekmeceli
Devre kesici NZM3, 3 kutuplu, Nominal akım = nominal kesintisiz akım ( In = Iu ): 350 A, Montaj tipi: Çekmeceli, Vidalı bağlantı, Standart/Onay: IEC, Koruma fonksiyonu: Motor koruma

Product range Circuit-breaker
Protective function Motor protection
Standard/Approval 0000SPC-571
Installation type IEC
Release system Withdrawable
Construction size Electronic release
Description NZM3
Number of poles IEC/EN 60947-4-1, IEC/EN 60947-2

The circuit-breaker fulfills all requirements for AC-3 switching category.


R.m.s. value measurement and “thermal memory”
Adjustable time delay setting to overcome current peaks tr at 6 x Ir also infinity (without overload releases)
All AC-3 rating data applies to direct switching by the circuit-breaker under normal operating conditions. If, for example, a contactor takes over AC-3 switching under normal operating conditions, the full rated uninterrupted current applies to the circuit-breaker, In = Iu.
Standard equipment 3 pole
400/415 V 50 Hz [Icu ] Screw connection
Rated current = rated uninterrupted current [In = Iu] 70 kA
Overload trip [Ir ]
175 - 350 A
Short-circuit releases [Irm ]
>Non-delayed [Ii = In x …]
350 A
Standards 175 - 350 A
Protection against direct contact 2 - 14
Climatic proofing IEC/EN 60947
Ambient temperature
>Ambient temperature, storage
Finger and back of hand proof to VDE 0106 Part 100
Ambient temperature
>Operation
Damp heat, constant, to IEC 60068-2-78
Damp heat, cyclic, to IEC 60068-2-30
Mechanical shock resistance (10 ms half-sinusoidal shock) according to IEC 60068-2-27 - 40 - + 70 °C
Safe isolation to EN 61140
>Between auxiliary contacts and main contacts
-25 - +70 °C
Safe isolation to EN 61140
>between the auxiliary contacts
20 (half-sinusoidal shock 20 ms) g
Mounting position 500 V AC
Direction of incoming supply 300 V AC
Degree of protection
>Device
Vertical and 90° in all directions
  With XFI earth-fault release:
- NZM1, N1, NZM2, N2: vertical and 90° in all directions
with plug-in unit
- NZM1, N1, NZM2, N2: vertical, 90° right/left
with withdrawable unit:
- NZM3, N3: vertical, 90° right/left
- NZM4, N4: vertical
with remote operator:
- NZM2, N(S)2, NZM3, N(S)3, NZM4, N(S)4: vertical and 90° in all directions

Degree of protection
>Enclosures
as required
Degree of protection
>Terminations
In the operating controls area: IP20 (basic degree of protection)
Other technical data (sheet catalogue) With insulating surround: IP40
With door coupling rotary handle: IP66
Rated current = rated uninterrupted current [In = Iu] Tunnel terminal: IP10
Phase isolator and strip terminal: IP00
Rated surge voltage invariability [Uimp ]
>Main contacts
Temperature dependency, Derating
Rated surge voltage invariability [Uimp ]
>Auxiliary contacts
350 A
Rated operational voltage [Ue] 8000 V
Overvoltage category/pollution degree 6000 V
Rated insulation voltage [Ui ] 690 V AC
Use in unearthed supply systems III/3
Rated short-circuit making capacity [Icm ]
>240 V [Icm ]
1000 V
Rated short-circuit making capacity [Icm ]
>400/415 V [Icm ]
≦ 690 V
Rated short-circuit making capacity [Icm ]
>440 V 50/60 Hz [Icm ]
220 kA
Rated short-circuit making capacity [Icm ]
>525 V 50/60 Hz [Icm ]
154 kA
Rated short-circuit making capacity [Icm ]
>690 V 50/60 H [Ic]
143 kA
Rated short-circuit breaking capacity Icn [Icn ]
>Icu to IEC/EN 60947 test cycle O-t-CO [Icu]
>240 V 50/60 Hz [Icu ]
80 kA
Rated short-circuit breaking capacity Icn [Icn ]
>Icu to IEC/EN 60947 test cycle O-t-CO [Icu]
>400/415 V 50/60 Hz [Icu ]
50 kA
Rated short-circuit breaking capacity Icn [Icn ]
>Icu to IEC/EN 60947 test cycle O-t-CO [Icu]
>440 V 50/60 Hz [Icu ]
100 kA
Rated short-circuit breaking capacity Icn [Icn ]
>Icu to IEC/EN 60947 test cycle O-t-CO [Icu]
>525 V 50/60 Hz [Icu ]
70 kA
Rated short-circuit breaking capacity Icn [Icn ]
>Icu to IEC/EN 60947 test cycle O-t-CO [Icu]
>690 V 50/60 Hz [Icu ]
65 kA
Rated short-circuit breaking capacity Icn [Icn ]
>Ics to IEC/EN 60947 test cycle O-t-CO-t-CO [Ics]
>240 V 50/60 Hz [Ics ]
36 kA
Rated short-circuit breaking capacity Icn [Icn ]
>Ics to IEC/EN 60947 test cycle O-t-CO-t-CO [Ics]
>400/415 V 50/60 Hz [Ics ]
25 kA
Rated short-circuit breaking capacity Icn [Icn ]
>Ics to IEC/EN 60947 test cycle O-t-CO-t-CO [Ics]
>440 V 50/60 Hz [Ics ]
100 kA
Rated short-circuit breaking capacity Icn [Icn ]
>Ics to IEC/EN 60947 test cycle O-t-CO-t-CO [Ics]
>525 V 50/60 Hz [Ics ]
70 kA
Rated short-circuit breaking capacity Icn [Icn ]
>Ics to IEC/EN 60947 test cycle O-t-CO-t-CO [Ics]
>690 V 50/60 Hz [Ics]
65 kA
Rated short-circuit breaking capacity Icn [Icn ] 18 kA
Rated short-time withstand current
>t = 0.3 s [Icw ]
6 kA
Rated short-time withstand current
>t = 1 s [Icw ]
Maximum back-up fuse, if the expected short-circuit currents at the installation location exceed the switching capacity of the circuit-breaker.
Utilization category to IEC/EN 60947-2 3.3 kA
Lifespan, mechanical(of which max. 50 % trip by shunt/undervoltage release) [Operations] 3.3 kA
Lifespan, electrical
>AC-1
>400 V 50/60 Hz [Operations]
A
Lifespan, electrical
>AC-1
>415 V 50/60 Hz [Operations]
15000
Lifespan, electrical
>AC-1
>690 V 50/60 Hz [Operations]
5000
Lifespan, electrical
>AC--3
>400 V 50/60 Hz [Operations]
5000
Lifespan, electrical
>AC--3
>415 V 50/60 Hz [Operations]
3000
Lifespan, electrical
>AC--3
>690 V 50/60 Hz [Operations]
2000
Lifespan, electrical
>Max. operating frequency
2000
Total break time at short-circuit 2000
Standard equipment 60 Ops/h
Accessories required < 10 ms
Optional accessories Screw connection
Round copper conductor
>Box terminal
>Solid
NZM3-XAVS
Round copper conductor
>Box terminal
>Stranded
Box terminal
Tunnel terminal
connection on rear
Round copper conductor
>Tunnel terminal
>Solid
2 x 16 mm2
Round copper conductor
>Tunnel terminal
>Stranded
>1-hole
1 x (35 - 240)
2 x (25-120) mm2
Round copper conductor
>Bolt terminal and rear-side connection
>Direct on the switch
>Solid
1 x 16 mm2
Round copper conductor
>Bolt terminal and rear-side connection
>Direct on the switch
>Stranded
1 x (16 - 185) mm2
Round copper conductor
>Bolt terminal and rear-side connection
>Connection width extension
>Connection width extension
1 x 16
2 x 16 mm2
Al circular conductor
>Tunnel terminal
>Solid
1 x (25 - 240)
2 x (25 - 240) mm2
Al circular conductor
>Tunnel terminal
>Stranded
>Stranded
2 x 300 mm2
Al circular conductor
>Tunnel terminal
>Stranded
>Double hole
1 x 16 mm2
Al circular conductor
>Tunnel terminal
>Stranded
1 x (25 - 185) 2) mm2
Cu strip (number of segments x width x segment thickness)
>Box terminal [min.]
1 x (50 - 240)
2 x (50 - 240) mm2
Cu strip (number of segments x width x segment thickness)
>Box terminal [max.]
2) Up to 240 mm² can be connected depending on the cable manufacturer.
Cu strip (number of segments x width x segment thickness)
>Bolt terminal and rear-side connection
>Flat copper strip, with holes [min.]
6 x 16 x 0.8 mm
Cu strip (number of segments x width x segment thickness)
>Bolt terminal and rear-side connection
>Flat copper strip, with holes [max.]
10 x 24 x 1.0
+ 5 x 24 x 1.0
(2 x) 8 x 24 x 1.0 mm
Cu strip (number of segments x width x segment thickness)
>Bolt terminal and rear-side connection
>Connection width extension
6 x 16 x 0.8 mm
Copper busbar (width x thickness) [mm]
>Bolt terminal and rear-side connection
>Screw connection
10 x 32 x 1.0 + 5 x 32 x 1.0 mm
Copper busbar (width x thickness) [mm]
>Bolt terminal and rear-side connection
>Direct on the switch [min.]
(2 x) 10 x 50 x 1.0 mm
Copper busbar (width x thickness) [mm]
>Bolt terminal and rear-side connection
>Direct on the switch [max.]
M10
Copper busbar (width x thickness) [mm]
>Bolt terminal and rear-side connection
>Connection width extension
>Connection width extension [max.]
20 x 5 mm
Control cables 30 x 10
+ 30 x 5 mm
Rated operational current for specified heat dissipation [In] 2 x (10 x 50) mm
Equipment heat dissipation, current-dependent [Pvid] 1 x (0.75 - 2.5)
2 x (0.75 - 1.5) mm2
Operating ambient temperature min. 350 A
Operating ambient temperature max. 36.75 W
10.2 Strength of materials and parts
>10.2.2 Corrosion resistance
-25 °C
10.2 Strength of materials and parts
>10.2.3.1 Verification of thermal stability of enclosures
+70 °C
10.2 Strength of materials and parts
>10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard´s requirements.
10.2 Strength of materials and parts
>10.2.3.3 Verification of resistance of insulating materials to abnormal heat and fire due to internal electric effects
Meets the product standard´s requirements.
10.2 Strength of materials and parts
>10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard´s requirements.
10.2 Strength of materials and parts
>10.2.5 Lifting
Meets the product standard´s requirements.
10.2 Strength of materials and parts
>10.2.6 Mechanical impact
Meets the product standard´s requirements.
10.2 Strength of materials and parts
>10.2.7 Inscriptions
Does not apply, since the entire switchgear needs to be evaluated.
10.3 Degree of protection of ASSEMBLIES Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances Meets the product standard´s requirements.
10.5 Protection against electric shock Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components Meets the product standard´s requirements.
10.7 Internal electrical circuits and connections Does not apply, since the entire switchgear needs to be evaluated.
10.8 Connections for external conductors Does not apply, since the entire switchgear needs to be evaluated.
10.9 Insulation properties
>10.9.2 Power-frequency electric strength
Is the panel builder´s responsibility.
10.9 Insulation properties
>10.9.3 Impulse withstand voltage
Is the panel builder´s responsibility.
10.9 Insulation properties
>10.9.4 Testing of enclosures made of insulating material
Is the panel builder´s responsibility.
10.10 Temperature rise Is the panel builder´s responsibility.
10.11 Short-circuit rating Is the panel builder´s responsibility.
10.12 Electromagnetic compatibility The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.13 Mechanical function Is the panel builder´s responsibility. The specifications for the switchgear must be observed.
Rated permanent current Iu Is the panel builder´s responsibility. The specifications for the switchgear must be observed.
Rated voltage The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz 350 A
Overload release current setting 690 - 690 V
Adjustment range short-term delayed short-circuit release 150 kA
Adjustment range undelayed short-circuit release 175 - 350 A
Integrated earth fault protection 0 - 0 A
Type of electrical connection of main circuit 700 - 4900 A
Device construction No
Suitable for DIN rail (top hat rail) mounting Screw connection
DIN rail (top hat rail) mounting optional Built-in device slide-in technique (withdrawable)
Number of auxiliary contacts as normally closed contact No
Number of auxiliary contacts as normally open contact No
Number of auxiliary contacts as change-over contact 0
Switched-off indicator available 0
With under voltage release 0
Number of poles No
Position of connection for main current circuit No
Type of control element 3
Complete device with protection unit Back side
Motor drive integrated Rocker lever
Motor drive optional Yes
Degree of protection (IP) No
Characteristic curve Yes

Mnelko olarak, endüstriyel otomasyon çözümlerinde güvenilir bir iş ortağı olarak, geniş ürün yelpazesi ile işletmenizin tüm ihtiyaçlarını karşılamaya yönelik kaliteli ve yenilikçi ürünler sunmaktayız. Ürün portföyümüz, modern endüstriyel süreçleri desteklemek amacıyla yüksek performans, dayanıklılık ve verimlilik ilkeleri doğrultusunda tasarlanmış çözümlerden oluşur.
Tüm ürünlerimiz, zorlu çalışma koşullarında dahi maksimum güvenilirlik sunar ve işletmenizin operasyonlarını sorunsuz şekilde sürdürmesine yardımcı olur. Endüstriyel otomasyon, enerji yönetimi, kablolama çözümleri ve daha birçok alanda sunduğumuz ürünler, farklı sektörlerdeki ihtiyaçlara esneklikle uyum sağlar.
Ayrıca, ürünlerimiz sadece kaliteli malzemelerle üretilmiş olup, uluslararası standartlara uygunluk göstermektedir. Müşterilerimize sunduğumuz çözümlerle, operasyonel verimliliklerini artırmalarına ve maliyetlerini optimize etmelerine olanak tanıyoruz. Teknolojik gelişmeleri yakından takip eden firmamız, sürekli olarak yenilikçi ürünler sunarak, müşterilerimizin rekabet avantajı elde etmesine destek vermektedir.
Her bir ürün sayfamızda, teknik detaylar, kullanım alanları ve ürün özelliklerine dair kapsamlı bilgilere ulaşabilirsiniz. Endüstriyel süreçlerinizi güçlendirmek için ihtiyacınız olan tüm ürünleri sitemizden keşfedebilir, sorunsuz bir satın alma deneyimi yaşayabilirsiniz.

Benzer Ürünler

NZMH2-4-VX250/VAR
Eaton
NZMH2-VX250-SVE
Eaton
NZMS2-4-VX250/VAR
Eaton
NZMS2-4-VX160
Eaton
NZMS2-MX220-SVE
Eaton
NZMS2-VX250-SVE
Eaton
NZMN2-4-VX160/VAR
Eaton
NZMN2-VX100-BT
Eaton