NZMH4-AEF1000-NA
271118 NZMH4-AEF1000-NA
271118

Devre kesici, 3p, 1000A Devre kesici NZM4, 3 kutuplu, Anahtarlama kapasitesi SCCR 480Y/277 V 60 Hz( Icu ): 85 kA, Anahtarlama kapasitesi SCCR 600Y/347 V 60 Hz( Icu): 50 kA, Anahtarlama kapasitesi SCCR 480 V 60 Hz( Icu ) : 85 kA, Nominal akım = nominal kesintisiz akım (In = Iu): 1000 A, Kurulum tipi: Sabit, Vidalı bağlantı, Standart/Onay: UL/CSA, IEC, Koruma fonksiyonu: Sistem ve kablo koruması

Devre kesici, 3p, 1000A
Devre kesici NZM4, 3 kutuplu, Anahtarlama kapasitesi SCCR 480Y/277 V 60 Hz( Icu ): 85 kA, Anahtarlama kapasitesi SCCR 600Y/347 V 60 Hz( Icu): 50 kA, Anahtarlama kapasitesi SCCR 480 V 60 Hz( Icu ) : 85 kA, Nominal akım = nominal kesintisiz akım (In = Iu): 1000 A, Kurulum tipi: Sabit, Vidalı bağlantı, Standart/Onay: UL/CSA, IEC, Koruma fonksiyonu: Sistem ve kablo koruması

Product range Circuit-breaker
Protective function System and cable protection
Standard/Approval UL/CSA, IEC
Release system Electronic release
Installation type Fixed
Description Switches conform to UL/CSA as well as the IEC regulations. IEC switching performance values are contained on the rating plate.
Fixed overload releases Ir
R.m.s. value measurement and “thermal memory”
Frame size NZM4
Number of poles 3 pole
Standard equipment Screw connection
SCCR 480Y/277 V 60 Hz [Icu]
SCCR 480 V 60 Hz [Icu] 85 kA
SCCR 600Y/347 V 60 Hz [Icu] 85 kA
SCCR 600 V 60 Hz [Icu] 50 kA
Rated current = rated uninterrupted current [In = Iu] 50 kA
Overload trip [Ir ]Overload release, min. [Ir]
Short-circuit releases [Irm ]
>Non-delayed [Ii = In x …]
1000 A
Standards
Protection against direct contact 1000 A
Climatic proofing 2 - 12
Ambient temperature
>Ambient temperature, storage
Ambient temperature
>Operation
IEC/EN 60947
Mechanical shock resistance (10 ms half-sinusoidal shock) according to IEC 60068-2-27 Finger and back of hand proof to VDE 0106 Part 100
Safe isolation to EN 61140
>Between auxiliary contacts and main contacts
Damp heat, constant, to IEC 60068-2-78
Damp heat, cyclic, to IEC 60068-2-30
Safe isolation to EN 61140
>between the auxiliary contacts
- 40 - + 70 °C
Weight -25 - +70 °C
Mounting position
>Mounting position
20 (half-sinusoidal shock 20 ms) g
Direction of incoming supply 500 V AC
Degree of protection
>Device
300 V AC
Degree of protection
>Enclosures
21 kg
Degree of protection
>Terminations
Vertical and 90° in all directions
  With XFI earth-fault release:
- NZM1, N1, NZM2, N2: vertical and 90° in all directions
with plug-in unit
- NZM1, N1, NZM2, N2: vertical, 90° right/left
with withdrawable unit:
- NZM3, N3: vertical, 90° right/left
- NZM4, N4: vertical
with remote operator:
- NZM2, N(S)2, NZM3, N(S)3, NZM4, N(S)4: vertical and 90° in all directions

Other technical data (sheet catalogue) as required
Rated surge voltage invariability [Uimp ]
>Main contacts
In the operating controls area: IP20 (basic degree of protection)
Rated surge voltage invariability [Uimp ]
>Auxiliary contacts
With insulating surround: IP40
With door coupling rotary handle: IP66
Rated operational voltage [Ue] Tunnel terminal: IP10
Phase isolator and strip terminal: IP00
Overvoltage category/pollution degree Weight
Temperature dependency, Derating
Effective power loss
Rated insulation voltage [Ui ]
Use in unearthed supply systems 8000 V
Rated short-circuit making capacity [Icm ]
>240 V [Icm ]
6000 V
Rated short-circuit making capacity [Icm ]
>400/415 V [Icm ]
690 V AC
Rated short-circuit making capacity [Icm ]
>440 V 50/60 Hz [Icm ]
III/3
Rated short-circuit making capacity [Icm ]
>525 V 50/60 Hz [Icm ]
1000 V
Rated short-circuit making capacity [Icm ]
>690 V 50/60 H [Ic]
≦ 690 V
Rated short-circuit breaking capacity Icn [Icn ]
>Icu to IEC/EN 60947 test cycle O-t-CO [Icu]
>240 V 50/60 Hz [Icu ]
Rated short-circuit breaking capacity Icn [Icn ]
>Icu to IEC/EN 60947 test cycle O-t-CO [Icu]
>400/415 V 50/60 Hz [Icu ]
275 kA
Rated short-circuit breaking capacity Icn [Icn ]
>Icu to IEC/EN 60947 test cycle O-t-CO [Icu]
>440 V 50/60 Hz [Icu ]
187 kA
Rated short-circuit breaking capacity Icn [Icn ]
>Icu to IEC/EN 60947 test cycle O-t-CO [Icu]
>525 V 50/60 Hz [Icu ]
187 kA
Rated short-circuit breaking capacity Icn [Icn ]
>Icu to IEC/EN 60947 test cycle O-t-CO [Icu]
>690 V 50/60 Hz [Icu ]
143 kA
Rated short-circuit breaking capacity Icn [Icn ]
>Ics to IEC/EN 60947 test cycle O-t-CO-t-CO [Ics]
>240 V 50/60 Hz [Ics ]
100 kA
Rated short-circuit breaking capacity Icn [Icn ]
>Ics to IEC/EN 60947 test cycle O-t-CO-t-CO [Ics]
>400/415 V 50/60 Hz [Ics ]
125 kA
Rated short-circuit breaking capacity Icn [Icn ]
>Ics to IEC/EN 60947 test cycle O-t-CO-t-CO [Ics]
>440 V 50/60 Hz [Ics ]
85 kA
Rated short-circuit breaking capacity Icn [Icn ]
>Ics to IEC/EN 60947 test cycle O-t-CO-t-CO [Ics]
>525 V 50/60 Hz [Ics ]
85 kA
Rated short-circuit breaking capacity Icn [Icn ]
>Ics to IEC/EN 60947 test cycle O-t-CO-t-CO [Ics]
>690 V 50/60 Hz [Ics]
65 kA
Rated short-circuit breaking capacity Icn [Icn ]
>Maximum low-voltage h.b.c. fuse
50 kA
Rated short-circuit breaking capacity Icn [Icn ] 63 kA
Technical data that diverge from products for the IEC market

Switching capacity of NA switches (UL489, CSA 22.2 No. 5.1)

Short-circuit current rating SCCR
>SCCR 240 V 60 Hz [Icu]
50 kA
Technical data that diverge from products for the IEC market

Switching capacity of NA switches (UL489, CSA 22.2 No. 5.1)

Short-circuit current rating SCCR
>SCCR 480Y/277 V 60 Hz [Icu]
50 kA
Technical data that diverge from products for the IEC market

Switching capacity of NA switches (UL489, CSA 22.2 No. 5.1)

Short-circuit current rating SCCR
>SCCR 480 V 60 Hz [Icu]
50 kA
Technical data that diverge from products for the IEC market

Switching capacity of NA switches (UL489, CSA 22.2 No. 5.1)

Short-circuit current rating SCCR
>SCCR 600Y/347 V 60 Hz [Icu]
37 kA
Technical data that diverge from products for the IEC market

Switching capacity of NA switches (UL489, CSA 22.2 No. 5.1)

Short-circuit current rating SCCR
>SCCR 600 V 60 Hz [Icu]
2 x 630 A gG/gL
Rated short-time withstand current
>t = 0.3 s [Icw ]
Maximum back-up fuse, if the expected short-circuit currents at the installation location exceed the switching capacity of the circuit-breaker.
Rated short-time withstand current
>t = 1 s [Icw ]
125 kA
Utilization category to IEC/EN 60947-2 85 kA
Lifespan, mechanical(of which max. 50 % trip by shunt/undervoltage release) [Operations] 85 kA
Lifespan, electrical
>AC-1
>400 V 50/60 Hz [Operations]
50 kA
Lifespan, electrical
>AC-1
>690 V 50/60 Hz [Operations]
50 kA
Lifespan, electrical
>AC--3
>400 V 50/60 Hz [Operations]
19.2 kA
Lifespan, electrical
>AC--3
>415 V 50/60 Hz [Operations]
19.2 kA
Lifespan, electrical
>AC--3
>690 V 50/60 Hz [Operations]
A
Lifespan, electrical
>Max. operating frequency
10000
Total break time at short-circuit 3000
Standard equipment 2000
Round copper conductor
>Tunnel terminal
>Stranded
>4-hole
2000
Round copper conductor
>Bolt terminal and rear-side connection
>Direct on the switch
>Stranded
2000
Round copper conductor
>Bolt terminal and rear-side connection
>Module plate
>Single hole [min.]
1000
Round copper conductor
>Bolt terminal and rear-side connection
>Module plate
>Single hole [max.]
60 Ops/h
Round copper conductor
>Bolt terminal and rear-side connection
>Module plate
>Double hole [min.]
< 25 ≦ 415 V; < 35 > 415 V ms
Round copper conductor
>Bolt terminal and rear-side connection
>Module plate
>Double hole [max.]
Round copper conductor
>Bolt terminal and rear-side connection
>Connection width extension
>Connection width extension
Screw connection
Al conductors, Cu cable
>Tunnel terminal
>Stranded
>4-hole
4 x (1/0 - 500) mm2
Al conductors, Cu cable
>Bolt terminal and rear-side connection
>Flat copper strip, with holes [min.]
1 x (250 … 350)
4 x (0 … 350) mm2
Al conductors, Cu cable
>Bolt terminal and rear-side connection
>Flat copper strip, with holes [max.]
1 x (250 - 600) mm2
Al conductors, Cu cable
>Bolt terminal and rear-side connection
>Connection width extension
2 x (3/0 - 600) mm2
Cu strip (number of segments x width x segment thickness)
>Flat conductor terminal [min.]
2 x (3/0 - 350) mm2
Cu strip (number of segments x width x segment thickness)
>Flat conductor terminal [max.]
4 x (2 - 350) mm2
Cu strip (number of segments x width x segment thickness)
>Module plate
>Single hole
4 x 600
6 x (3/0 - 500) mm2
Cu strip (number of segments x width x segment thickness)
>Bolt terminal and rear-side connection
>Flat copper strip, with holes [min.]
4 x (50 - 240) mm2
Cu strip (number of segments x width x segment thickness)
>Bolt terminal and rear-side connection
>Flat copper strip, with holes [max.]
(2 x) 10 x 50 x 1.0 mm
Cu strip (number of segments x width x segment thickness)
>Bolt terminal and rear-side connection
>Connection width extension
(2 x) 10 x 50 x 1.0 mm
Copper busbar (width x thickness) [mm]
>Bolt terminal and rear-side connection
>Screw connection
(2 x) 10 x 80 x 1.0 mm
Copper busbar (width x thickness) [mm]
>Bolt terminal and rear-side connection
>Direct on the switch [min.]
6 x 16 x 0.8 mm
Copper busbar (width x thickness) [mm]
>Bolt terminal and rear-side connection
>Direct on the switch [max.]
(2 x) 10 x 32 x 1.0 mm
Copper busbar (width x thickness) [mm]
>Bolt terminal and rear-side connection
>Module plate
>Single hole [min.]
(2 x) 10 x 50 x 1.0 mm
Copper busbar (width x thickness) [mm]
>Bolt terminal and rear-side connection
>Module plate
>Single hole [max.]
(2 x) 10 x 50 x 1.0 mm
Copper busbar (width x thickness) [mm]
>Bolt terminal and rear-side connection
>Module plate
>Double hole
(2 x) 10 x 50 x 1.0 mm
Copper busbar (width x thickness) [mm]
>Bolt terminal and rear-side connection
>Connection width extension
>Connection width extension [min.]
(2 x) 10 x 80 x 1.0 mm
Copper busbar (width x thickness) [mm]
>Bolt terminal and rear-side connection
>Connection width extension
>Connection width extension [max.]
M10
Control cables 25 x 5 mm
Rated operational current for specified heat dissipation [In] 2 x (50 x 10)
2 x (80 x 10) mm
Equipment heat dissipation, current-dependent [Pvid] 25 x 5 mm
Operating ambient temperature min. 2 x (50 x 10)
mm
Operating ambient temperature max. 2 x (50 x 10) mm
10.2 Strength of materials and parts
>10.2.2 Corrosion resistance
60 x 10 mm
10.2 Strength of materials and parts
>10.2.3.1 Verification of thermal stability of enclosures
2 x (80 x 10) mm
10.2 Strength of materials and parts
>10.2.3.2 Verification of resistance of insulating materials to normal heat
1 x (18 … 14)
2 x (18 … 16) mm2
10.2 Strength of materials and parts
>10.2.3.3 Verification of resistance of insulating materials to abnormal heat and fire due to internal electric effects
10.2 Strength of materials and parts
>10.2.4 Resistance to ultra-violet (UV) radiation
1000 A
10.2 Strength of materials and parts
>10.2.5 Lifting
123 W
10.2 Strength of materials and parts
>10.2.6 Mechanical impact
-25 °C
10.2 Strength of materials and parts
>10.2.7 Inscriptions
+70 °C
10.3 Degree of protection of ASSEMBLIES
10.4 Clearances and creepage distances Meets the product standard´s requirements.
10.5 Protection against electric shock Meets the product standard´s requirements.
10.6 Incorporation of switching devices and components Meets the product standard´s requirements.
10.7 Internal electrical circuits and connections Meets the product standard´s requirements.
10.8 Connections for external conductors Meets the product standard´s requirements.
10.9 Insulation properties
>10.9.2 Power-frequency electric strength
Does not apply, since the entire switchgear needs to be evaluated.
10.9 Insulation properties
>10.9.3 Impulse withstand voltage
Does not apply, since the entire switchgear needs to be evaluated.
10.9 Insulation properties
>10.9.4 Testing of enclosures made of insulating material
Meets the product standard´s requirements.
10.10 Temperature rise Does not apply, since the entire switchgear needs to be evaluated.
10.11 Short-circuit rating Meets the product standard´s requirements.
10.12 Electromagnetic compatibility Does not apply, since the entire switchgear needs to be evaluated.
10.13 Mechanical function Does not apply, since the entire switchgear needs to be evaluated.
Rated permanent current Iu Is the panel builder´s responsibility.
Rated voltage Is the panel builder´s responsibility.
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz Is the panel builder´s responsibility.
Overload release current setting Is the panel builder´s responsibility.
Adjustment range short-term delayed short-circuit release Is the panel builder´s responsibility.
Adjustment range undelayed short-circuit release The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
Integrated earth fault protection Is the panel builder´s responsibility. The specifications for the switchgear must be observed.
Type of electrical connection of main circuit Is the panel builder´s responsibility. The specifications for the switchgear must be observed.
Device construction The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
Suitable for DIN rail (top hat rail) mounting
DIN rail (top hat rail) mounting optional
Number of auxiliary contacts as normally closed contact 1000 A
Number of auxiliary contacts as normally open contact 690 - 690 V
Number of auxiliary contacts as change-over contact 85 kA
With switched-off indicator 1000 - 1000 A
With under voltage release 0 - 0 A
Number of poles 2000 - 12000 A
Position of connection for main current circuit No
Type of control element Screw connection
Complete device with protection unit Built-in device fixed built-in technique
Motor drive integrated No
Motor drive optional No
Degree of protection (IP) 0
Product Standards 0
UL File No. 0
UL Category Control No. No
CSA File No. No
CSA Class No. 3
North America Certification Front side
Specially designed for North America Rocker lever
Suitable for Yes
Current Limiting Circuit-Breaker No
Max. Voltage Rating Yes
Degree of Protection IP20
Characteristic curve UL 489; CSA-C22.2 No. 5-09; IEC 60947-2; CE marking

Mnelko olarak, endüstriyel otomasyon çözümlerinde güvenilir bir iş ortağı olarak, geniş ürün yelpazesi ile işletmenizin tüm ihtiyaçlarını karşılamaya yönelik kaliteli ve yenilikçi ürünler sunmaktayız. Ürün portföyümüz, modern endüstriyel süreçleri desteklemek amacıyla yüksek performans, dayanıklılık ve verimlilik ilkeleri doğrultusunda tasarlanmış çözümlerden oluşur.
Tüm ürünlerimiz, zorlu çalışma koşullarında dahi maksimum güvenilirlik sunar ve işletmenizin operasyonlarını sorunsuz şekilde sürdürmesine yardımcı olur. Endüstriyel otomasyon, enerji yönetimi, kablolama çözümleri ve daha birçok alanda sunduğumuz ürünler, farklı sektörlerdeki ihtiyaçlara esneklikle uyum sağlar.
Ayrıca, ürünlerimiz sadece kaliteli malzemelerle üretilmiş olup, uluslararası standartlara uygunluk göstermektedir. Müşterilerimize sunduğumuz çözümlerle, operasyonel verimliliklerini artırmalarına ve maliyetlerini optimize etmelerine olanak tanıyoruz. Teknolojik gelişmeleri yakından takip eden firmamız, sürekli olarak yenilikçi ürünler sunarak, müşterilerimizin rekabet avantajı elde etmesine destek vermektedir.
Her bir ürün sayfamızda, teknik detaylar, kullanım alanları ve ürün özelliklerine dair kapsamlı bilgilere ulaşabilirsiniz. Endüstriyel süreçlerinizi güçlendirmek için ihtiyacınız olan tüm ürünleri sitemizden keşfedebilir, sorunsuz bir satın alma deneyimi yaşayabilirsiniz.

Benzer Ürünler

NZMH2-4-VX250/VAR
Eaton
NZMH2-VX250-SVE
Eaton
NZMS2-4-VX250/VAR
Eaton
NZMS2-4-VX160
Eaton
NZMS2-MX220-SVE
Eaton
NZMS2-VX250-SVE
Eaton
NZMN2-4-VX160/VAR
Eaton
NZMN2-VX100-BT
Eaton