Product range |
Switch-disconnectors |
Protective function |
Disconnectors/main switches Photovoltaic applications |
Product range |
DC switch-disconnectors |
Application field |
Utility buildings Open areas |
Part no. |
N...DC |
Standard/Approval |
IEC |
Rated operational voltage |
1000 |
Installation type |
Fixed |
Construction size |
N2 |
Description |
IEC/EN 60947-3 CCC China Compulsory Certificate Main switch characteristics including positive drive to IEC/EN 60204 and VDE 0113. Isolating characteristics to IEC/EN 60947-3 and VDE 0660. N switch-disconnectors can, in addition, be combined with NZM...-XU, NZM...-XA shunt releases and auxiliary contacts as well as with NZM...-XR... remote operator. For DC switching, all 4 contacts must be connected in series. Refer to the information on jumper kit accessories. Supplied as standard: Screw connection; box terminal optional. When working with ungrounded systems (e.g., IT), the installation must ensure that a double ground fault will be impossible. Switch can not be combined with plug-in/withdrawable units and/or connection on rear. N4-4-...-S15-DC feeder unit and outgoer from the bottom only. |
Connection options |
|
Number of poles |
4-pole basic device, usable in a 1-pole or 2-pole configuration depending on the type of connection |
Standard equipment |
Screw connection |
Switch positions |
I, +, 0 |
Rated current = rated uninterrupted current [In = Iu] |
200 A |
Short-circuit protective device max. fuse gR-characteristic |
200 A gR |
Remotely control / trip |
Remote operation with shunt releases / remote operator |
Rated operating frequency |
DC |
Rated operational voltage, max. [Ue] |
1000 V DC |
Rated uninterrupted current with terminal jumpers >at 40° |
200 |
Rated uninterrupted current with terminal jumpers >at 65° |
200 |
Rated uninterrupted current with terminal jumpers |
Values for rated uninterrupted current at 65 °C include jumpers. |
Utilization category |
DC-22A |
Rated operational current [Ie
] >DC 22-A [Ie] |
200 A |
Overvoltage category/pollution degree |
III/3 |
Rated insulation voltage [Ui
] |
1250 V |
Ambient temperature >Ambient temperature, storage |
- 40 - + 70 °C |
Ambient temperature >Operation |
-25 - +70 °C |
t = 1 s [Icw
] |
3.6 kA |
1000 V |
15 kA |
With back-up fuse |
200 A gR |
Max. operating frequency |
120 Ops/h |
Lifespan, mechanical [Operations] |
20000 |
Standard equipment |
Lifespan, mechanical: of which max. 50 % trip by shunt/undervoltage release |
Round copper conductor >Box terminal >Solid |
Screw connection |
Round copper conductor >Box terminal >Stranded |
1 x (4 - 16) 2 x (4 - 16) mm2 |
Round copper conductor >Tunnel terminal >Solid |
1 x (25 - 185) 2 x (25 - 70) mm2
|
Round copper conductor >Tunnel terminal >Stranded >Stranded |
1 x 16 mm2 |
Round copper conductor >Bolt terminals >Direct on the switch >Solid |
1 x (25 - 185) mm2
|
Round copper conductor >Bolt terminals >Direct on the switch >Stranded |
1 x (10 - 16) 2 x (4 - 16) mm2
|
Al conductors, Cu cable >Tunnel terminal >Solid |
1 x (25 - 185) 2 x (25 - 70) mm2
|
Al conductors, Cu cable >Tunnel terminal >Stranded >Stranded |
1 x 16 mm2
|
Al conductors, Cu cable >Bolt terminal and rear-side connection >Flat copper strip, with holes [min.] |
1 x (25 - 185) mm2
|
Al conductors, Cu cable >Bolt terminal and rear-side connection >Flat copper strip, with holes [max.] |
2 x 16 x 0.8 mm |
Cu strip (number of segments x width x segment thickness) >Box terminal [min.] |
10 x 24 x 0.8 mm |
Cu strip (number of segments x width x segment thickness) >Box terminal [max.] |
2 x 9 x 0,8 mm |
Cu strip (number of segments x width x segment thickness) >Bolt terminal and rear-side connection >Flat copper strip, with holes [min.] |
10 x 16 x 0,8 (2x) 8 x 15,5 x 0,8 mm |
Cu strip (number of segments x width x segment thickness) >Bolt terminal and rear-side connection >Flat copper strip, with holes [max.] |
2 x 16 x 0.8 mm |
Copper busbar (width x thickness) [mm] >Bolt terminal and rear-side connection >Screw connection |
10 x 24 x 0.8 mm |
Copper busbar (width x thickness) [mm] >Bolt terminal and rear-side connection >Direct on the switch [min.] |
M8 |
Copper busbar (width x thickness) [mm] >Bolt terminal and rear-side connection >Direct on the switch [max.] |
16 x 5 mm |
Rated operational current for specified heat dissipation [In] |
24 x 8 mm |
Equipment heat dissipation, current-dependent [Pvid] |
200 A |
Operating ambient temperature min. |
42 W |
Operating ambient temperature max. |
-25 °C |
10.2 Strength of materials and parts >10.2.2 Corrosion resistance |
+70 °C |
10.2 Strength of materials and parts >10.2.3.1 Verification of thermal stability of enclosures |
Meets the product standard´s requirements. |
10.2 Strength of materials and parts >10.2.3.2 Verification of resistance of insulating materials to normal heat |
Meets the product standard´s requirements. |
10.2 Strength of materials and parts >10.2.3.3 Verification of resistance of insulating materials to abnormal heat and fire due to internal electric effects |
Meets the product standard´s requirements. |
10.2 Strength of materials and parts >10.2.4 Resistance to ultra-violet (UV) radiation |
Meets the product standard´s requirements. |
10.2 Strength of materials and parts >10.2.5 Lifting |
Meets the product standard´s requirements. |
10.2 Strength of materials and parts >10.2.6 Mechanical impact |
Does not apply, since the entire switchgear needs to be evaluated. |
10.2 Strength of materials and parts >10.2.7 Inscriptions |
Does not apply, since the entire switchgear needs to be evaluated. |
10.3 Degree of protection of ASSEMBLIES |
Meets the product standard´s requirements. |
10.4 Clearances and creepage distances |
Does not apply, since the entire switchgear needs to be evaluated. |
10.5 Protection against electric shock |
Meets the product standard´s requirements. |
10.6 Incorporation of switching devices and components |
Does not apply, since the entire switchgear needs to be evaluated. |
10.7 Internal electrical circuits and connections |
Does not apply, since the entire switchgear needs to be evaluated. |
10.8 Connections for external conductors |
Is the panel builder´s responsibility. |
10.9 Insulation properties >10.9.2 Power-frequency electric strength |
Is the panel builder´s responsibility. |
10.9 Insulation properties >10.9.3 Impulse withstand voltage |
Is the panel builder´s responsibility. |
10.9 Insulation properties >10.9.4 Testing of enclosures made of insulating material |
Is the panel builder´s responsibility. |
10.10 Temperature rise |
Is the panel builder´s responsibility. |
10.11 Short-circuit rating |
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices. |
10.12 Electromagnetic compatibility |
Is the panel builder´s responsibility. The specifications for the switchgear must be observed. |
10.13 Mechanical function |
Is the panel builder´s responsibility. The specifications for the switchgear must be observed. |
Version as main switch |
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed. |
Version as maintenance-/service switch |
Yes |
Version as safety switch |
Yes |
Version as emergency stop installation |
No |
Version as reversing switch |
Yes |
Number of switches |
No |
Max. rated operation voltage Ue AC |
1 |
Rated operating voltage |
0 V |
Rated permanent current Iu |
1000 - 1000 V |
Rated permanent current at AC-23, 400 V |
200 A |
Rated permanent current at AC-21, 400 V |
0 A |
Rated operation power at AC-3, 400 V |
0 A |
Rated short-time withstand current lcw |
0 kW |
Rated operation power at AC-23, 400 V |
3.6 kA |
Switching power at 400 V |
0 kW |
Conditioned rated short-circuit current Iq |
0 kW |
Number of poles |
0 kA |
Number of auxiliary contacts as normally closed contact |
4 |
Number of auxiliary contacts as normally open contact |
0 |
Number of auxiliary contacts as change-over contact |
0 |
Motor drive optional |
0 |
Motor drive integrated |
Yes |
Voltage release optional |
No |
Device construction |
Yes |
Suitable for ground mounting |
Built-in device fixed built-in technique |
Suitable for front mounting 4-hole |
Yes |
Suitable for front mounting centre |
No |
Suitable for distribution board installation |
No |
Suitable for intermediate mounting |
Yes |
Colour control element |
Yes |
Type of control element |
Black |
Interlockable |
Rocker lever |
Type of electrical connection of main circuit |
Yes |
Degree of protection (IP), front side |
Screw connection |
Degree of protection (NEMA) |
IP20 |