Basic function |
Residual current circuit-breakers
, digital |
Number of poles |
4 pole |
Rated current [In] |
25 A |
Rated short-circuit strength [Icn] |
10 kA |
Rated fault current [IΔN] |
0.03 A |
Type |
Type G/B (ÖVE E 8601) |
Product range |
FRCdM |
Sensitivity |
All current sensitive |
Current test marks |
As per inscription |
Rated voltage according to IEC/EN 60947-2
[Un] |
240/415 V AC |
Rated frequency [f] |
60 Hz |
Limit values of the operating voltage >electronic |
50 - 456 V AC |
Limit values of the operating voltage >Test circuit |
184 - 440 V AC |
Rated fault current [IΔn] |
30 mA |
Sensitivity |
All current sensitive |
Rated insulation voltage [Ui
] |
440 V |
Rated impulse withstand voltage [Uimp] |
4 kV |
Rated short-circuit strength [Icn] |
10 kA |
Max. admissible back-up fuse >Short-circuit [gG/gL] |
63 A |
Max. admissible back-up fuse >Overload [gG/gL] |
63 A |
Rated making and breaking capacity / Rated residual making and breaking capacity [Im / IΔm] |
500 A |
lifespan >Electrical [Operations] |
≧ 4000 |
lifespan >Mechanical [Operations] |
≧ 20000 |
Rated switching capacity >30 VDC (resistive load) |
2 A |
Rated switching capacity >240 VAC (resistive load) |
0.25 A |
Max. switching duty (resistive load) |
60 W |
Max. switching voltage AC |
240 V |
Max. switching voltage DC |
220 V |
Maximum switching current |
2 A |
Min. switching capacity (reference value) |
10 μA, 10 mV DC |
lifespan >Electrical (at 20 switching operations per minute) 2 A 30 VDC resistive load |
>105 Operations |
lifespan >Electrical (at 20 switching operations per minute) 1 A 30 VDC resistive load |
>5 x 105 Operations |
Terminal capacity |
0.25 - 1.5 mm² |
Standard front dimension |
45 mm |
Device height |
80 mm |
Built-in width |
70 (4TE) mm |
Mounting |
Quick attachment with 2 latch positions for DIN-rail IEC/EN 60715 |
Degree of Protection |
IP40, IP54 (with moisture-proof enclosure) |
Terminals top and bottom |
Twin-purpose terminals |
Terminal protection |
finger and hand touch safe, DGUV VS3, EN 50274 |
Terminal cross-section >Solid |
1.5 - 35 mm2 |
Terminal cross-section >Stranded |
2 x 16 mm2
|
Terminal cross-section |
M5 (with cross-recessed screw as defined in EN ISO 4757-Z2, Pozidriv PZ2) |
Tightening torque of fixing screws |
2 - 2.4 N/m |
Thickness of busbar material |
0.8 - 2 mm |
Admissible ambient temperature range |
-25 - +60 °C |
Permissible storage and transport temperatures |
-35 - +60 °C |
Climatic proofing |
25-55°C/90-95% relative humidity according to IEC 60068-2 |
Mounting position |
As required |
Contact position indicator |
red / green |
Trip indication |
white / blue |
Rated operational current for specified heat dissipation [In] |
25 A |
Heat dissipation per pole, current-dependent [Pvid] |
0 W |
Equipment heat dissipation, current-dependent [Pvid] |
4.6 W |
Static heat dissipation, non-current-dependent [Pvs] |
0 W |
Heat dissipation capacity [Pdiss] |
0 W |
Operating ambient temperature min. |
-25 °C |
Operating ambient temperature max. |
+60 °C |
10.2 Strength of materials and parts >10.2.2 Corrosion resistance |
Maximum operating temperature is 60 °C in accordance with the de-rating table |
10.2 Strength of materials and parts >10.2.3.1 Verification of thermal stability of enclosures |
Meets the product standard´s requirements. |
10.2 Strength of materials and parts >10.2.3.2 Verification of resistance of insulating materials to normal heat |
Meets the product standard´s requirements. |
10.2 Strength of materials and parts >10.2.3.3 Verification of resistance of insulating materials to abnormal heat and fire due to internal electric effects |
Meets the product standard´s requirements. |
10.2 Strength of materials and parts >10.2.4 Resistance to ultra-violet (UV) radiation |
Meets the product standard´s requirements. |
10.2 Strength of materials and parts >10.2.5 Lifting |
Meets the product standard´s requirements. |
10.2 Strength of materials and parts >10.2.6 Mechanical impact |
Does not apply, since the entire switchgear needs to be evaluated. |
10.2 Strength of materials and parts >10.2.7 Inscriptions |
Does not apply, since the entire switchgear needs to be evaluated. |
10.3 Degree of protection of ASSEMBLIES |
Meets the product standard´s requirements. |
10.4 Clearances and creepage distances |
Does not apply, since the entire switchgear needs to be evaluated. |
10.5 Protection against electric shock |
Meets the product standard´s requirements. |
10.6 Incorporation of switching devices and components |
Does not apply, since the entire switchgear needs to be evaluated. |
10.7 Internal electrical circuits and connections |
Does not apply, since the entire switchgear needs to be evaluated. |
10.8 Connections for external conductors |
Is the panel builder´s responsibility. |
10.9 Insulation properties >10.9.2 Power-frequency electric strength |
Is the panel builder´s responsibility. |
10.9 Insulation properties >10.9.3 Impulse withstand voltage |
Is the panel builder´s responsibility. |
10.9 Insulation properties >10.9.4 Testing of enclosures made of insulating material |
Is the panel builder´s responsibility. |
10.10 Temperature rise |
Is the panel builder´s responsibility. |
10.11 Short-circuit rating |
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices. |
10.12 Electromagnetic compatibility |
Is the panel builder´s responsibility. The specifications for the switchgear must be observed. |
10.13 Mechanical function |
Is the panel builder´s responsibility. The specifications for the switchgear must be observed. |
Number of poles |
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed. |
Rated voltage |
4 |
Rated current |
415 V |
Rated fault current |
25 A |
Rated insulation voltage Ui |
30 mA |
Rated impulse withstand voltage Uimp |
440 V |
Mounting method |
4 kV |
Leakage current type |
DIN rail |
Selective protection |
B |
Short-time delayed tripping |
No |
Short-circuit breaking capacity (Icw) |
Yes |
Surge current capacity |
10 kA |
Frequency |
3 kA |
Additional equipment possible |
60 Hz |
With interlocking device |
Yes |
Degree of protection (IP) |
Yes |
Width in number of modular spacings |
IP20 |
Built-in depth |
4 |
Ambient temperature during operating |
70.5 mm |
Pollution degree |
-25 - 60 °C |
Connectable conductor cross section multi-wired |
2 |
Connectable conductor cross section solid-core |
1.5 - 16 mm² |
Characteristic curve |
1.5 - 35 mm² |
Characteristic curve |
|