Minyatür devre kesici (MCB), 3A, 3p, C-Char, AC Minyatür devre kesici (MCB) FAZ, 3 kutuplu, Açma karakteristiği: C, Nominal akım In: 3 A, Endüstriyel ve gelişmiş ticari uygulamalar için şalt cihazı

Minyatür devre kesici (MCB), 3A, 3p, C-Char, AC
Minyatür devre kesici (MCB) FAZ, 3 kutuplu, Açma karakteristiği: C, Nominal akım In: 3 A, Endüstriyel ve gelişmiş ticari uygulamalar için şalt cihazı

Basic function Miniature circuit-breakers
Number of poles 3 pole
Tripping characteristic C
Application Switchgear for industrial and advanced commercial applications
Rated current [In] 3 A
Rated switching capacity acc. to IEC/EN 60947-2 [Icu] 15 kA
Product range FAZ
Standards IEC/EN 60947-2
IEC/EN 60898
Rated operational voltage [Ue] [Ue] 240/415 V AC
Rated operational voltage [Ue] 60 (per pole) V DC
Rated voltage according to UL [Un] 480Y/277 V AC
Rated switching capacity acc. to IEC/EN 60947-2 [Icu] 15 kA
Breaking capacity according to UL 10 (UL1077) kA
Max operational voltage according to IEC/EN 60947-2 440 V AC
Rated switching capacity according to IEC/EN 60947-2 (max operational voltage) [Icu] 10 kA
Rated service short-circuit breaking capacity according to IEC/EN 60947-2 (max operational voltage) [Ics] 7,5 kA
Rated voltage according to IEC/EN 60898-1 [Un] 415 V AC
Rated switching capacity according to IEC/EN 60898-1 [Icn] 10 kA
Rated service short-circuit breaking capacity according to IEC/EN 60898-1 [Ics] 7,5 kA
Operational switching capacity 7.5 kA
Characteristic B, C, D, K, S, Z
Max. back-up fuse 125 A gL/gG
Selectivity Class 3
lifespan
>Lifespan [Operations]
> 10000
Direction of incoming supply as required
Standard front dimension 45 mm
Enclosure height 80 mm
Mounting width per pole 17.5 mm
Mounting IEC/EN 60715 top-hat rail
Degree of Protection IP20, IP40 (when fitted)
Terminals top and bottom Twin-purpose terminals
Terminal protection Finger and back-of-hand proof to BGV A2
Terminal capacities 1 x 25 mm2
Terminal capacities 2 x 10 mm2
Thickness of busbar material 0.8 … 2 mm
Mounting position As required
Rated operational current for specified heat dissipation [In] 3 A
Heat dissipation per pole, current-dependent [Pvid] 0 W
Equipment heat dissipation, current-dependent [Pvid] 3.6 W
Static heat dissipation, non-current-dependent [Pvs] 0 W
Heat dissipation capacity [Pdiss] 0 W
Operating ambient temperature min. -40 °C
Operating ambient temperature max. +75 °C
10.2 Strength of materials and parts
>10.2.2 Corrosion resistance
linear, per +1 °C, results in a 0.5% reduction of current carrying capacity
10.2 Strength of materials and parts
>10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard´s requirements.
10.2 Strength of materials and parts
>10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard´s requirements.
10.2 Strength of materials and parts
>10.2.3.3 Verification of resistance of insulating materials to abnormal heat and fire due to internal electric effects
Meets the product standard´s requirements.
10.2 Strength of materials and parts
>10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard´s requirements.
10.2 Strength of materials and parts
>10.2.5 Lifting
Meets the product standard´s requirements.
10.2 Strength of materials and parts
>10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2 Strength of materials and parts
>10.2.7 Inscriptions
Does not apply, since the entire switchgear needs to be evaluated.
10.3 Degree of protection of ASSEMBLIES Meets the product standard´s requirements.
10.4 Clearances and creepage distances Does not apply, since the entire switchgear needs to be evaluated.
10.5 Protection against electric shock Meets the product standard´s requirements.
10.6 Incorporation of switching devices and components Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections Does not apply, since the entire switchgear needs to be evaluated.
10.8 Connections for external conductors Is the panel builder´s responsibility.
10.9 Insulation properties
>10.9.2 Power-frequency electric strength
Is the panel builder´s responsibility.
10.9 Insulation properties
>10.9.3 Impulse withstand voltage
Is the panel builder´s responsibility.
10.9 Insulation properties
>10.9.4 Testing of enclosures made of insulating material
Is the panel builder´s responsibility.
10.10 Temperature rise Is the panel builder´s responsibility.
10.11 Short-circuit rating The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.12 Electromagnetic compatibility Is the panel builder´s responsibility. The specifications for the switchgear must be observed.
10.13 Mechanical function Is the panel builder´s responsibility. The specifications for the switchgear must be observed.
Release characteristic The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
Number of poles (total) C
Number of protected poles 3
Rated current 3
Rated voltage 3 A
Rated insulation voltage Ui 400 V
Rated impulse withstand voltage Uimp 440 V
Rated short-circuit breaking capacity Icn EN 60898 at 230 V 4 kV
Rated short-circuit breaking capacity Icn EN 60898 at 400 V 10 kA
Rated short-circuit breaking capacity Icu IEC 60947-2 at 230 V 10 kA
Rated short-circuit breaking capacity Icu IEC 60947-2 at 400 V 15 kA
Voltage type 15 kA
Frequency AC
Current limiting class 50 - 60 Hz
Suitable for flush-mounted installation 3
Concurrently switching N-neutral No
Over voltage category No
Pollution degree 3
Additional equipment possible 2
Width in number of modular spacings Yes
Built-in depth 3
Degree of protection (IP) 70.5 mm
Ambient temperature during operating IP20
Connectable conductor cross section multi-wired -25 - 75 °C
Connectable conductor cross section solid-core 1 - 25 mm²
Product Standards 1 - 25 mm²
UL File No. IEC/EN 60947-2; IEC/EN 60898; UL 1077; CSA-C22.2 No. 235; CE marking
UL Category Control No. E177451
CSA File No. QVNU2, QVNU8
CSA Class No. 204453
North America Certification 3215-30
Conditions of Acceptability UL recognized, CSA certified
Suitable for Supplementary Protector only
Current Limiting Circuit-Breaker Branch Circuits; not as BCPD
Max. Voltage Rating No
Degree of Protection 480Y/277 VAC
Characteristic curve IEC: IP20; UL/CSA Type: -
Characteristic curve 122U025
Characteristic curve Let-through energy I2t
According to IEC/EN 60898
Characteristic curve 122U026

Mnelko olarak, endüstriyel otomasyon çözümlerinde güvenilir bir iş ortağı olarak, geniş ürün yelpazesi ile işletmenizin tüm ihtiyaçlarını karşılamaya yönelik kaliteli ve yenilikçi ürünler sunmaktayız. Ürün portföyümüz, modern endüstriyel süreçleri desteklemek amacıyla yüksek performans, dayanıklılık ve verimlilik ilkeleri doğrultusunda tasarlanmış çözümlerden oluşur.
Tüm ürünlerimiz, zorlu çalışma koşullarında dahi maksimum güvenilirlik sunar ve işletmenizin operasyonlarını sorunsuz şekilde sürdürmesine yardımcı olur. Endüstriyel otomasyon, enerji yönetimi, kablolama çözümleri ve daha birçok alanda sunduğumuz ürünler, farklı sektörlerdeki ihtiyaçlara esneklikle uyum sağlar.
Ayrıca, ürünlerimiz sadece kaliteli malzemelerle üretilmiş olup, uluslararası standartlara uygunluk göstermektedir. Müşterilerimize sunduğumuz çözümlerle, operasyonel verimliliklerini artırmalarına ve maliyetlerini optimize etmelerine olanak tanıyoruz. Teknolojik gelişmeleri yakından takip eden firmamız, sürekli olarak yenilikçi ürünler sunarak, müşterilerimizin rekabet avantajı elde etmesine destek vermektedir.
Her bir ürün sayfamızda, teknik detaylar, kullanım alanları ve ürün özelliklerine dair kapsamlı bilgilere ulaşabilirsiniz. Endüstriyel süreçlerinizi güçlendirmek için ihtiyacınız olan tüm ürünleri sitemizden keşfedebilir, sorunsuz bir satın alma deneyimi yaşayabilirsiniz.

Benzer Ürünler

PKNM-32/1N/C/003-F-MW
Eaton
HNB-C20/1N/003-A-HX
Eaton
HNB-C6/1N/003-A-HX
Eaton
HNB-C6/1N/003-HX
Eaton
HNB-B16/1N/003-A
Eaton