| Basic function | 
			Miniature circuit-breakers | 
		
		
			| Number of poles | 
			2 pole | 
		
		
			| Tripping characteristic | 
			C | 
		
		
			| Application | 
			Switchgear for export to North America (UL-listed) | 
		
		
			| Rated current [In] | 
			25 A | 
		
		
			| Rated switching capacity acc. to IEC/EN 60947-2 [Icu] | 
			15 kA | 
		
		
			| Product range | 
			FAZ-RT | 
		
		
			| Standards | 
			UL 489, CSA C22.2 No. 5 IEC 60947-2 | 
		
		
			| Rated operational voltage [Ue] [Ue] | 
			240/415 V AC | 
		
		
			| Rated operational voltage [Ue] | 
			60 V DC | 
		
		
			| Rated voltage according to IEC/EN 60947-2
 [Un] | 
			254/440 480Y/277 (UL) V AC | 
		
		
			| Rated switching capacity acc. to IEC/EN 60947-2 [Icu] | 
			15 kA | 
		
		
			| Operational switching capacity | 
			7.5 kA | 
		
		
			| Characteristic | 
			B, C, D | 
		
		
			| Selectivity Class | 
			3 | 
		
		
			lifespan >Lifespan [Operations] | 
			> 20000 | 
		
		
			| Direction of incoming supply | 
			as required | 
		
		
			| Standard front dimension | 
			45 mm | 
		
		
			| Enclosure height | 
			105 mm | 
		
		
			| Mounting width per pole | 
			17.7 mm | 
		
		
			| Mounting | 
			IEC/EN 60715 top-hat rail | 
		
		
			| Degree of Protection | 
			IP20, IP40 (when fitted) | 
		
		
			| Terminals top and bottom | 
			Twin-purpose terminals | 
		
		
			| Terminal protection | 
			Finger and back-of-hand proof to BGV A2 | 
		
		
			| Terminal capacities | 
			1 x 25 mm2
	 | 
		
		
			| Terminal capacities | 
			2 x 10 mm2
	 | 
		
		
			| Tightening torque of fixing screws | 
			max. 2.4 UL: #18-12 AWG: 2.4 Nm (21 lb-in) #10-8 AWG: 2.8 Nm (25 lb-in) #6 AWG: 4 Nm (36 lb-in) N/m | 
		
		
			| Mounting position | 
			As required | 
		
		
			| Rated operational current for specified heat dissipation [In] | 
			25 A | 
		
		
			| Heat dissipation per pole, current-dependent [Pvid] | 
			0 W | 
		
		
			| Static heat dissipation, non-current-dependent [Pvs] | 
			0 W | 
		
		
			| Heat dissipation capacity [Pdiss] | 
			0 W | 
		
		
			| Operating ambient temperature min. | 
			-25 °C | 
		
		
			| Operating ambient temperature max. | 
			+75 °C | 
		
		
			10.2 Strength of materials and parts >10.2.2 Corrosion resistance | 
			linear, per +1 °C, results in a 0.5% reduction of current carrying capacity | 
		
		
			10.2 Strength of materials and parts >10.2.3.1 Verification of thermal stability of enclosures | 
			Meets the product standard´s requirements. | 
		
		
			10.2 Strength of materials and parts >10.2.3.2 Verification of resistance of insulating materials to normal heat | 
			Meets the product standard´s requirements. | 
		
		
			10.2 Strength of materials and parts >10.2.3.3 Verification of resistance of insulating materials to abnormal heat and fire due to internal electric effects | 
			Meets the product standard´s requirements. | 
		
		
			10.2 Strength of materials and parts >10.2.4 Resistance to ultra-violet (UV) radiation | 
			Meets the product standard´s requirements. | 
		
		
			10.2 Strength of materials and parts >10.2.5 Lifting | 
			Meets the product standard´s requirements. | 
		
		
			10.2 Strength of materials and parts >10.2.6 Mechanical impact | 
			Does not apply, since the entire switchgear needs to be evaluated. | 
		
		
			10.2 Strength of materials and parts >10.2.7 Inscriptions | 
			Does not apply, since the entire switchgear needs to be evaluated. | 
		
		
			| 10.3 Degree of protection of ASSEMBLIES | 
			Meets the product standard´s requirements. | 
		
		
			| 10.4 Clearances and creepage distances | 
			Does not apply, since the entire switchgear needs to be evaluated. | 
		
		
			| 10.5 Protection against electric shock | 
			Meets the product standard´s requirements. | 
		
		
			| 10.6 Incorporation of switching devices and components | 
			Does not apply, since the entire switchgear needs to be evaluated. | 
		
		
			| 10.7 Internal electrical circuits and connections | 
			Does not apply, since the entire switchgear needs to be evaluated. | 
		
		
			| 10.8 Connections for external conductors | 
			Is the panel builder´s responsibility. | 
		
		
			10.9 Insulation properties >10.9.2 Power-frequency electric strength | 
			Is the panel builder´s responsibility. | 
		
		
			10.9 Insulation properties >10.9.3 Impulse withstand voltage | 
			Is the panel builder´s responsibility. | 
		
		
			10.9 Insulation properties >10.9.4 Testing of enclosures made of insulating material | 
			Is the panel builder´s responsibility. | 
		
		
			| 10.11 Short-circuit rating | 
			Is the panel builder´s responsibility. | 
		
		
			| 10.12 Electromagnetic compatibility | 
			Is the panel builder´s responsibility. The specifications for the switchgear must be observed. | 
		
		
			| 10.13 Mechanical function | 
			Is the panel builder´s responsibility. The specifications for the switchgear must be observed. | 
		
		
			| Release characteristic | 
			The device meets the requirements, provided the information in the instruction leaflet (IL) is observed. | 
		
		
			| Number of poles (total) | 
			C | 
		
		
			| Number of protected poles | 
			2 | 
		
		
			| Rated current | 
			2 | 
		
		
			| Rated voltage | 
			25 A | 
		
		
			| Rated insulation voltage Ui | 
			240 V | 
		
		
			| Rated impulse withstand voltage Uimp | 
			440 V | 
		
		
			| Rated short-circuit breaking capacity Icn EN 60898 at 230 V | 
			4 kV | 
		
		
			| Rated short-circuit breaking capacity Icn EN 60898 at 400 V | 
			15 kA | 
		
		
			| Rated short-circuit breaking capacity Icu IEC 60947-2 at 230 V | 
			15 kA | 
		
		
			| Rated short-circuit breaking capacity Icu IEC 60947-2 at 400 V | 
			10 kA | 
		
		
			| Voltage type | 
			14 kA | 
		
		
			| Frequency | 
			AC | 
		
		
			| Current limiting class | 
			50 - 50 Hz | 
		
		
			| Suitable for flush-mounted installation | 
			3 | 
		
		
			| Concurrently switching N-neutral | 
			Yes | 
		
		
			| Over voltage category | 
			No | 
		
		
			| Pollution degree | 
			3 | 
		
		
			| Additional equipment possible | 
			2 | 
		
		
			| Width in number of modular spacings | 
			Yes | 
		
		
			| Built-in depth | 
			35.4 | 
		
		
			| Degree of protection (IP) | 
			60 mm | 
		
		
			| Ambient temperature during operating | 
			IP20 | 
		
		
			| Connectable conductor cross section multi-wired | 
			-25 - 75 °C | 
		
		
			| Connectable conductor cross section solid-core | 
			1 - 25 mm² | 
		
		
			| Product Standards  | 
			1 - 25 mm² | 
		
		
			| UL File No.  | 
			IEC/EN 60947-2; UL 489; CSA-C22.2 No. 5-09; CE marking | 
		
		
			| UL Category Control No.  | 
			E235139 | 
		
		
			| CSA File No.  | 
			DIVQ | 
		
		
			| CSA Class No.  | 
			204453 | 
		
		
			| North America Certification  | 
			1432-01 | 
		
		
			| Specially designed for North America  | 
			UL listed, CSA certified | 
		
		
			| Suitable for  | 
			Yes, suitable as BCPD | 
		
		
			| Current Limiting Circuit-Breaker  | 
			Feeder circuits, branch circuits | 
		
		
			| Max. Voltage Rating  | 
			Yes | 
		
		
			| Degree of Protection  | 
			≤ 32 A | 
		
		
			| Characteristic curve | 
			IEC: IP20, UL/CSA Type: - | 
		
		
			| Characteristic curve | 
			  |