Product range |
Electronic motor starter |
Product range |
SmartWire-DT slave |
Subrange |
SmartWire-DT electronic motor starters |
Basic function |
DOL starters (complete devices) |
Function |
For connecting to SmartWire-DT for expanded diagnostics. |
Description |
DOL starting Motor protection Circuit design: safety output stage with bypass, three-phase disconnect. Motor current additionally adjustable via SmartWire-DT. |
Messages |
Operational readiness Operating direction feedback Motor current in % Motor current in A Thermal motor image in % Overload prewarning Trip indications (overload, phase failure, etc.) Set short-circuit release value Device Type |
Commands |
Operating the motor starter Manual reset Automatic reset |
Max. rating for three-phase motors, 50 - 60 Hz >AC-53a >380 V 400 V 415 V [P] |
0.06 - 0.75 kW |
Setting range of overload releases [Ir] |
0,18 - 2,4 A_x |
Actuating voltage |
24 V DC |
Connection technique |
Push in terminals |
Connection to SmartWire-DT |
yes |
Standards |
IEC/EN 60947-4-2 |
Dimensions >Width |
30 mm |
Dimensions >Height |
157 mm |
Dimensions >Depth |
124 mm |
Weight |
0.3 kg |
Mounting |
Top-hat rail IEC/EN 60715, 35 mm |
Protection type (IEC/EN 60529, EN50178, VBG 4) |
IP20 |
Mounting position |
Vertical |
Lifespan, electrical [Operations] |
3 x 107 |
Max. switching frequency |
7200 (pulse pause time 50:50) Operations/h |
Terminal capacity >Solid |
1 x (0.2 - 2.5) 1 x AWG20 - 14 mm2 |
Terminal capacity >flexible, with ferrule |
2 x (0,2 - 2,5) 1 x AWG24 - 14 mm2
|
Terminal capacity >Notes |
Minimum length 10 mm. |
Terminal capacity >flexible, with twin ferrule |
2 x (0,2 - 1,5) 2 x AWG24 - 16 mm2
|
Terminal capacity >Notes |
Minimum length 10 mm. |
Operating ambient temperature |
-5 - +60, in accordance with IEC 60068-2-1 °C |
Storage [ϑ] |
-40 - +80 °C |
Rated impulse withstand voltage [Uimp] |
6000 V AC |
Overvoltage category/pollution degree |
III/2 |
Rated operational voltage [Ue
] |
42 - 550 V |
Rated operational current >AC-51 [Ie] |
0.15 - 2.40 A |
Rated operational current >AC-53a [Ie] |
0.15 - 2.4 A |
Heat dissipation [PV] |
0.1 - 2 W |
Static heat dissipation, non-current-dependent [Pvs] |
1 W |
Basic insulation to IEC/EN60947-1 >between feedback signal output and switch voltage |
500 V AC |
Current measurement >Setting range of overload releases [Ir] |
0,18 - 2,4 A_x |
Current measurement >Release class |
10 CLASS |
Current measurement >Recovery time [tW] |
2 (manual startup) 20 (automatic restart) min. |
Current measurement >Balance monitoring >Magnitude Imax > Irated ((Imax - Imin)/Imax) |
If ≧ 33, pick-up time of 120 s If ≧ 67, pick-up time of 1.8 s % |
Current measurement >Balance monitoring >Magnitude Imax < Irated ((Imax - Imin)/Irated) |
If ≧ 33, pick-up time of 120 s If ≧ 67, pick-up time of 1.8 s % |
Stall protection >Pick-up time I (L1) or I (L3) |
33 A |
Stall protection >Pick-up time |
0.5 S |
Short-circuit rating >Type “1” coordination >Short-circuit protective device |
50 kA, 500 V AC: Fuse 16 A gG/gL 50 kA, 500 V AC: fuse 30 A CCMR 50 kA, 415 V AC: PKM0-4 15 kA, 415 V AC: PKM0-6,3 2.5 kA, 400 V AC: FAZ-B16/3 |
Input data >Supply voltage [UAUX] |
24 (-15 - +20 %) V DC |
Input data >Residual ripple on the input voltage |
≦ 5 % |
Input data >Input current |
70 mA |
Input data >Current draw inrush |
120 mA |
Input data >Current draw (operation) [UAUX] |
50 mA |
Electrostatic discharge (ESD) >applied standard |
IEC EN 61000-4-2, Level 3 |
Electrostatic discharge (ESD) >Air discharge |
8 kV |
Electrostatic discharge (ESD) >Contact discharge |
6 kV |
Electromagnetic fields (RFI) >applied standard |
IEC/EN 61000-4-3 |
Electromagnetic fields (RFI) |
800 - 1000 MHz: 10 1.4 - 2 GHz: 10 2.0 - 2.7 GHz: 3 V/m |
Radio interference suppression |
EN 55011, Class A (emitted interference, line-conducted) EN 61000-6-3, Class A (emitted interference, radiated) |
Note on use |
This product is designed for operation in industrial environments (environment 2). The use in residential environments (environment 1) could cause electrical interference so that addition suppression must be planned. |
Burst |
2 IEC/EN 61000-4-4, level 3 kV |
power pulses (Surge) |
1 kV (symmetrical) 2 kV (asymmetrical) according to IEC/EN 61000-4-5 |
Immunity to line-conducted interference to (IEC/EN 61000-4-6) |
10 V |
Rated operational current for specified heat dissipation [In] |
2.4 A |
Heat dissipation per pole, current-dependent [Pvid] |
0.7 W |
Equipment heat dissipation, current-dependent [Pvid] |
2.1 W |
Static heat dissipation, non-current-dependent [Pvs] |
1 W |
Heat dissipation capacity [Pdiss] |
0 W |
Operating ambient temperature min. |
-5 °C |
Operating ambient temperature max. |
+60 °C |
10.2 Strength of materials and parts >10.2.2 Corrosion resistance |
Meets the product standard´s requirements. |
10.2 Strength of materials and parts >10.2.3.1 Verification of thermal stability of enclosures |
Meets the product standard´s requirements. |
10.2 Strength of materials and parts >10.2.3.2 Verification of resistance of insulating materials to normal heat |
Meets the product standard´s requirements. |
10.2 Strength of materials and parts >10.2.3.3 Verification of resistance of insulating materials to abnormal heat and fire due to internal electric effects |
Meets the product standard´s requirements. |
10.2 Strength of materials and parts >10.2.4 Resistance to ultra-violet (UV) radiation |
Meets the product standard´s requirements. |
10.2 Strength of materials and parts >10.2.5 Lifting |
Does not apply, since the entire switchgear needs to be evaluated. |
10.2 Strength of materials and parts >10.2.6 Mechanical impact |
Does not apply, since the entire switchgear needs to be evaluated. |
10.2 Strength of materials and parts >10.2.7 Inscriptions |
Meets the product standard´s requirements. |
10.3 Degree of protection of ASSEMBLIES |
Does not apply, since the entire switchgear needs to be evaluated. |
10.4 Clearances and creepage distances |
Meets the product standard´s requirements. |
10.5 Protection against electric shock |
Does not apply, since the entire switchgear needs to be evaluated. |
10.6 Incorporation of switching devices and components |
Does not apply, since the entire switchgear needs to be evaluated. |
10.7 Internal electrical circuits and connections |
Is the panel builder´s responsibility. |
10.8 Connections for external conductors |
Is the panel builder´s responsibility. |
10.9 Insulation properties >10.9.2 Power-frequency electric strength |
Is the panel builder´s responsibility. |
10.9 Insulation properties >10.9.3 Impulse withstand voltage |
Is the panel builder´s responsibility. |
10.9 Insulation properties >10.9.4 Testing of enclosures made of insulating material |
Is the panel builder´s responsibility. |
10.10 Temperature rise |
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices. |
10.11 Short-circuit rating |
Is the panel builder´s responsibility. The specifications for the switchgear must be observed. |
10.12 Electromagnetic compatibility |
Is the panel builder´s responsibility. The specifications for the switchgear must be observed. |
10.13 Mechanical function |
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed. |
Kind of motor starter |
Direct starter |
With short-circuit release |
No |
Rated control supply voltage Us at AC 50HZ |
0 - 0 V |
Rated control supply voltage Us at AC 60HZ |
0 - 0 V |
Rated control supply voltage Us at DC |
24 - 24 V |
Voltage type for actuating |
DC |
Rated operation power at AC-3, 230 V, 3-phase |
0.37 kW |
Rated operation power at AC-3, 400 V |
0.75 kW |
Rated power, 460 V, 60 Hz, 3-phase |
0.736 kW |
Rated power, 575 V, 60 Hz, 3-phase |
0 kW |
Rated operation current Ie |
2.4 A |
Rated operation current at AC-3, 400 V |
2.4 A |
Overload release current setting |
0.18 - 2.4 A |
Rated conditional short-circuit current, type 1, 480 Y/277 V |
0 A |
Rated conditional short-circuit current, type 1, 600 Y/347 V |
0 A |
Rated conditional short-circuit current, type 2, 230 V |
0 A |
Rated conditional short-circuit current, type 2, 400 V |
0 A |
Number of auxiliary contacts as normally open contact |
0 |
Number of auxiliary contacts as normally closed contact |
0 |
Ambient temperature, upper operating limit |
60 °C |
Temperature compensated overload protection |
Yes |
Release class |
CLASS 10 |
Type of electrical connection of main circuit |
Spring clamp connection |
Type of electrical connection for auxiliary- and control current circuit |
Spring clamp connection |
Rail mounting possible |
Yes |
With transformer |
No |
Number of command positions |
0 |
Suitable for emergency stop |
No |
Coordination class according to IEC 60947-4-3 |
Class 1 |
Number of indicator lights |
4 |
External reset possible |
Yes |
With fuse |
No |
Degree of protection (IP) |
IP20 |
Degree of protection (NEMA) |
Other |
Supporting protocol for TCP/IP |
No |
Supporting protocol for PROFIBUS |
No |
Supporting protocol for CAN |
No |
Supporting protocol for INTERBUS |
No |
Supporting protocol for ASI |
No |
Supporting protocol for MODBUS |
No |
Supporting protocol for Data-Highway |
No |
Supporting protocol for DeviceNet |
No |
Supporting protocol for SUCONET |
No |
Supporting protocol for LON |
No |
Supporting protocol for PROFINET IO |
No |
Supporting protocol for PROFINET CBA |
No |
Supporting protocol for SERCOS |
No |
Supporting protocol for Foundation Fieldbus |
No |
Supporting protocol for EtherNet/IP |
No |
Supporting protocol for AS-Interface Safety at Work |
No |
Supporting protocol for DeviceNet Safety |
No |
Supporting protocol for INTERBUS-Safety |
No |
Supporting protocol for PROFIsafe |
No |
Supporting protocol for SafetyBUS p |
No |
Supporting protocol for other bus systems |
Yes |
Width |
30 mm |
Height |
157 mm |
Depth |
139 mm |
Product Standards |
IEC/EN 60947-5; UL 508; CSA-C22.2 No. 14; CE marking |
UL File No. |
E29096 |
UL Category Control No. |
NLDX, NLDX7 |
CSA File No. |
UL report applies to both US and Canada |
North America Certification |
UL listed, certified by UL for use in Canada |
Specially designed for North America |
No |
Characteristic curve |
|