Product range |
Contactors |
Application |
Contactors for Semiconductor Industries acc. to SEMI F47 |
Subrange |
Contactors up to 150 A with electronic actuation |
Utilization category |
AC-1: Non-inductive or slightly inductive loads, resistance furnaces NAC-3: Normal AC induction motors: starting, switch off during running AC-4: Normal AC induction motors: starting, plugging, reversing, inching |
Notes |
|
Connection technique |
Also suitable for motors with efficiency class IE3. IE3-ready devices are identified by the logo on their packaging. |
AC-3 >380 V 400 V [Ie] |
Screw terminals |
AC-1 >Conventional free air thermal current, 3 pole, 50 - 60 Hz >Open >at 40 °C [Ith =Ie] |
|
AC-1 >Conventional free air thermal current, 3 pole, 50 - 60 Hz >enclosed [Ith
] |
9 A |
AC-1 >Conventional free air thermal current, 1 pole >open [Ith
] |
22 A |
AC-1 >Conventional free air thermal current, 1 pole >enclosed [Ith
] |
18 A |
AC-3 >220 V 230 V [P] |
50 A |
AC-3 >380 V 400 V [P] |
45 A |
AC-3 >660 V 690 V [P] |
|
AC-4 >220 V 230 V [P] |
2.5 kW |
AC-4 >380 V 400 V [P] |
4 kW |
AC-4 >660 V 690 V [P] |
4.5 kW |
N/O = Normally open |
1.5 kW |
Contact sequence |
2.5 kW |
Actuating voltage |
3.6 kW |
Instructions |
|
Mounting position |
1 N/O |
Altitude |
|
AC-1 >Rated operational current >Conventional free air thermal current, 3 pole, 50 - 60 Hz >Open >at 40 °C [Ith =Ie] |
RAC 120: 100 - 120 V 50/60 Hz |
AC-1 >Rated operational current >Conventional free air thermal current, 3 pole, 50 - 60 Hz >Open >at 50 °C [Ith =Ie] |
Contacts to EN 50 012. built-in suppressor circuit´ integrated suppressor circuit in actuating electronics |
AC-1 >Rated operational current >Conventional free air thermal current, 3 pole, 50 - 60 Hz >Open >at 60 °C [Ith =Ie] |
|
AC-1 >Rated operational current >Conventional free air thermal current, 3 pole, 50 - 60 Hz >enclosed [Ith
] |
|
AC-1 >Rated operational current >Conventional free air thermal current, 1 pole >open [Ith
] |
Max. 2000 m |
AC-1 >Rated operational current >Conventional free air thermal current, 1 pole >enclosed [Ith
] |
|
AC-3 >Rated operational current >Open, 3-pole: 50 – 60 Hz >Notes |
22 A |
AC-3 >Rated operational current >Open, 3-pole: 50 – 60 Hz >220 V 230 V [Ie] |
21 A |
AC-3 >Rated operational current >Open, 3-pole: 50 – 60 Hz >240 V [Ie] |
20 A |
AC-3 >Rated operational current >Open, 3-pole: 50 – 60 Hz >380 V 400 V [Ie] |
18 A |
AC-3 >Rated operational current >Open, 3-pole: 50 – 60 Hz >415 V [Ie] |
50 A |
AC-3 >Rated operational current >Open, 3-pole: 50 – 60 Hz >440V [Ie] |
45 A |
AC-3 >Rated operational current >Open, 3-pole: 50 – 60 Hz >500 V [Ie] |
At maximum permissible ambient temperature (open.) |
AC-3 >Rated operational current >Open, 3-pole: 50 – 60 Hz >660 V 690 V [Ie] |
9 A |
AC-3 >Motor rating [P] >220 V 230 V [P] |
9 A |
AC-3 >Motor rating [P] >240V [P] |
9 A |
AC-3 >Motor rating [P] >380 V 400 V [P] |
9 A |
AC-3 >Motor rating [P] >415 V [P] |
9 A |
AC-3 >Motor rating [P] >440 V [P] |
7 A |
AC-3 >Motor rating [P] >500 V [P] |
5 A |
AC-3 >Motor rating [P] >660 V 690 V [P] |
2.5 kW |
AC-4 >Open, 3-pole: 50 – 60 Hz >220 V 230 V [Ie
] |
3 kW |
AC-4 >Open, 3-pole: 50 – 60 Hz >240 V [Ie
] |
4 kW |
AC-4 >Open, 3-pole: 50 – 60 Hz >380 V 400 V [Ie
] |
5.5 kW |
AC-4 >Open, 3-pole: 50 – 60 Hz >415 V [Ie
] |
5.5 kW |
AC-4 >Open, 3-pole: 50 – 60 Hz >440 V [Ie
] |
4.5 kW |
AC-4 >Open, 3-pole: 50 – 60 Hz >500 V [Ie
] |
4.5 kW |
AC-4 >Open, 3-pole: 50 – 60 Hz >660 V 690 V [Ie
] |
6 A |
AC-4 >Motor rating [P] >220 V 230 V [P] |
6 A |
AC-4 >Motor rating [P] >240 V [P] |
6 A |
AC-4 >Motor rating [P] >380 V 400 V [P] |
6 A |
AC-4 >Motor rating [P] >415 V [P] |
6 A |
AC-4 >Motor rating [P] >440 V [P] |
5 A |
AC-4 >Motor rating [P] >500 V [P] |
4.5 A |
AC-4 >Motor rating [P] >660 V 690 V [P] |
1.5 kW |
3 pole, at Ith (60°) |
1.6 kW |
Current heat loss at Ie to AC-3/400 V |
2.5 kW |
Voltage tolerance >AC operated [Pick-up] |
2.8 kW |
Voltage tolerance >Drop-out voltage AC operated [Drop-out] |
3 kW |
Power consumption of the coil in a cold state and 1.0 x US >Electronic actuation [Pick-up] |
2.8 kW |
Power consumption of the coil in a cold state and 1.0 x US >Electronic actuation [Sealing] |
3.6 kW |
Power consumption of the coil in a cold state and 1.0 x US >Electronic actuation [Sealing] |
|
Duty factor |
2.4 W |
Operating times >Closing delay |
0.6 W |
Operating times >Opening delay |
|
-suitable according to |
0.8 - 1.15 x Uc |
Emitted interference |
0.2 - 0.5 x Uc
|
Interference immunity |
14 VA |
like the contactar [DIL] |
0.7 VA |
Switching capacity >Maximum motor rating >Three-phase >200 V 208 V |
0.8 W |
Switching capacity >Maximum motor rating >Three-phase >230 V 240 V |
100 % DF |
Switching capacity >Maximum motor rating >Three-phase >460 V 480 V |
40 ms |
Switching capacity >Maximum motor rating >Three-phase >575 V 600 V |
45 ms |
Switching capacity >Maximum motor rating >Single-phase >115 V 120 V |
SEMI F47 |
Switching capacity >Maximum motor rating >Single-phase >230 V 240 V |
|
Switching capacity >General use |
according to EN 60947-1 |
Auxiliary contacts >Pilot Duty >AC operated |
according to EN 60947-1 |
Auxiliary contacts >Pilot Duty >DC operated |
|
Auxiliary contacts >General Use >AC |
M9 |
Auxiliary contacts >General Use >AC |
|
Auxiliary contacts >General Use >DC |
5 HP |
Auxiliary contacts >General Use >DC |
5 HP |
Short Circuit Current Rating >Basic Rating >SCCR |
10 HP |
Short Circuit Current Rating >Basic Rating >max. Fuse |
15 HP |
Short Circuit Current Rating >Basic Rating >max. CB |
2 HP |
Short Circuit Current Rating >480 V High Fault >SCCR (fuse) |
3 HP |
Short Circuit Current Rating >480 V High Fault >max. Fuse |
40 A |
Short Circuit Current Rating >480 V High Fault >SCCR (CB) |
A600 |
Short Circuit Current Rating >480 V High Fault >max. CB |
P300 |
Short Circuit Current Rating >600 V High Fault >SCCR (fuse) |
600 V |
Short Circuit Current Rating >600 V High Fault >max. Fuse |
10 A |
Short Circuit Current Rating >600 V High Fault >SCCR (CB) |
250 V |
Short Circuit Current Rating >600 V High Fault >max. CB |
1 A |
Special Purpose Ratings >Electrical Discharge Lamps (Ballast) >480V 60Hz 3phase, 277V 60Hz 1phase |
5 kA |
Special Purpose Ratings >Electrical Discharge Lamps (Ballast) >600V 60Hz 3phase, 347V 60Hz 1phase |
125 A |
Special Purpose Ratings >Incandescent Lamps (Tungsten) >480V 60Hz 3phase, 277V 60Hz 1phase |
125 A |
Special Purpose Ratings >Incandescent Lamps (Tungsten) >600V 60Hz 3phase, 347V 60Hz 1phase |
10/100 kA |
Special Purpose Ratings >Resistance Air Heating >480V 60Hz 3phase, 277V 60Hz 1phase |
125/70 Class J A |
Special Purpose Ratings >Resistance Air Heating >600V 60Hz 3phase, 347V 60Hz 1phase |
10/65 kA |
Special Purpose Ratings >Refrigeration Control (CSA only) >LRA 480V 60Hz 3phase |
50/32 A |
Special Purpose Ratings >Refrigeration Control (CSA only) >FLA 480V 60Hz 3phase |
10/100 kA |
Special Purpose Ratings >Refrigeration Control (CSA only) >LRA 600V 60Hz 3phase |
125/70 Class J A |
Special Purpose Ratings >Refrigeration Control (CSA only) >FLA 600V 60Hz 3phase |
10/22 kA |
Special Purpose Ratings >Definite Purpose Ratings (100,000 cycles acc. to UL 1995) >LRA 480V 60Hz 3phase |
50/32 A |
Special Purpose Ratings >Definite Purpose Ratings (100,000 cycles acc. to UL 1995) >FLA 480V 60Hz 3phase |
40 A |
Special Purpose Ratings >Elevator Control >200V 60Hz 3phase |
40 A |
Special Purpose Ratings >Elevator Control >200V 60Hz 3phase |
40 A |
Special Purpose Ratings >Elevator Control >240V 60Hz 3phase |
40 A |
Special Purpose Ratings >Elevator Control >240V 60Hz 3phase |
40 A |
Special Purpose Ratings >Elevator Control >480V 60Hz 3phase |
40 A |
Special Purpose Ratings >Elevator Control >480V 60Hz 3phase |
240 A |
Special Purpose Ratings >Elevator Control >600V 60Hz 3phase |
40 A |
Special Purpose Ratings >Elevator Control >600V 60Hz 3phase |
180 A |
Rated operational current for specified heat dissipation [In] |
30 A |
Heat dissipation per pole, current-dependent [Pvid] |
108 A |
Equipment heat dissipation, current-dependent [Pvid] |
18 A |
Static heat dissipation, non-current-dependent [Pvs] |
3 HP |
Heat dissipation capacity [Pdiss] |
11 A |
Operating ambient temperature min. |
3 HP |
Operating ambient temperature max. |
9.6 A |
10.2 Strength of materials and parts >10.2.2 Corrosion resistance |
7.5 HP |
10.2 Strength of materials and parts >10.2.3.1 Verification of thermal stability of enclosures |
11 A |
10.2 Strength of materials and parts >10.2.3.2 Verification of resistance of insulating materials to normal heat |
10 HP |
10.2 Strength of materials and parts >10.2.3.3 Verification of resistance of insulating materials to abnormal heat and fire due to internal electric effects |
11 A |
10.2 Strength of materials and parts >10.2.4 Resistance to ultra-violet (UV) radiation |
|
10.2 Strength of materials and parts >10.2.5 Lifting |
9 A |
10.2 Strength of materials and parts >10.2.6 Mechanical impact |
0.2 W |
10.2 Strength of materials and parts >10.2.7 Inscriptions |
0.6 W |
10.3 Degree of protection of ASSEMBLIES |
0.8 W |
10.4 Clearances and creepage distances |
0 W |
10.5 Protection against electric shock |
-25 °C |
10.6 Incorporation of switching devices and components |
+60 °C |
10.7 Internal electrical circuits and connections |
|
10.8 Connections for external conductors |
Meets the product standard´s requirements. |
10.9 Insulation properties >10.9.2 Power-frequency electric strength |
Meets the product standard´s requirements. |
10.9 Insulation properties >10.9.3 Impulse withstand voltage |
Meets the product standard´s requirements. |
10.9 Insulation properties >10.9.4 Testing of enclosures made of insulating material |
Meets the product standard´s requirements. |
10.10 Temperature rise |
Meets the product standard´s requirements. |
10.11 Short-circuit rating |
Does not apply, since the entire switchgear needs to be evaluated. |
10.12 Electromagnetic compatibility |
Does not apply, since the entire switchgear needs to be evaluated. |
10.13 Mechanical function |
Meets the product standard´s requirements. |
Rated control supply voltage Us at AC 50HZ |
Does not apply, since the entire switchgear needs to be evaluated. |
Rated control supply voltage Us at AC 60HZ |
Meets the product standard´s requirements. |
Rated control supply voltage Us at DC |
Does not apply, since the entire switchgear needs to be evaluated. |
Voltage type for actuating |
Does not apply, since the entire switchgear needs to be evaluated. |
Rated operation current Ie at AC-1, 400 V |
Is the panel builder´s responsibility. |
Rated operation current Ie at AC-3, 400 V |
Is the panel builder´s responsibility. |
Rated operation power at AC-3, 400 V |
Is the panel builder´s responsibility. |
Rated operation current Ie at AC-4, 400 V |
Is the panel builder´s responsibility. |
Rated operation power at AC-4, 400 V |
Is the panel builder´s responsibility. |
Rated operation power NEMA |
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices. |
Modular version |
Is the panel builder´s responsibility. The specifications for the switchgear must be observed. |
Number of auxiliary contacts as normally open contact |
Is the panel builder´s responsibility. The specifications for the switchgear must be observed. |
Number of auxiliary contacts as normally closed contact |
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed. |
Type of electrical connection of main circuit |
|
Number of normally closed contacts as main contact |
|
Number of main contacts as normally open contact |
100 - 120 V |
Product Standards |
100 - 120 V |
UL File No. |
0 - 0 V |
UL Category Control No. |
AC |
CSA File No. |
20 A |
CSA Class No. |
9 A |
North America Certification |
4 kW |
Specially designed for North America |
7 A |
Accessories |
3 kW |
Characteristic curve |
7.4 kW |
Characteristic curve |
No |