Fonksiyon elemanı, kontaktör, SmartWire-DT, DIL/MSC, manuel/otomatik Fonksiyon elemanı, SmartWire-DT'ye bağlantı: evet, Şunlarla kullanım için: DILM(C)7… - DILM(C)32…, DILM38…, DILA…, DILMP20…, DILMP32…, DILMP45…, MSC-D(E) -...(24VDC)
Fonksiyon elemanı, kontaktör, SmartWire-DT, DIL/MSC, manuel/otomatik
Fonksiyon elemanı, SmartWire-DT'ye bağlantı: evet, Şunlarla kullanım için: DILM(C)7… - DILM(C)32…, DILM38…, DILA…, DILMP20…, DILMP32…, DILMP45…, MSC-D(E) -...(24VDC)
Product range | SmartWire-DT slave |
Accessories | SWD contactor modules |
Function | For connecting the contactors to SmartWire-DT |
Description | Per contactor 1 module necessary. 1 electrical interlock for the surface mounting of reversing starters Two self-supply digital inputs for potential-free contacts 1-0-A switch for manual or automatic operation. |
Messages | Contactor switching position, status of the digital inputs 1 and 2, 1-0-A switch position |
Commands | Contactor actuation |
Connection to SmartWire-DT | yes |
For use with | DILM(C)7… - DILM(C)32… DILM38… DILA… DILMP20… DILMP32… DILMP45… MSC-D(E)-...(24VDC) |
Setting | viaRotary switch |
Notes | For current consumption of the contactor coils > 3 A (UL: 2 A) use additional power feed module. A2 connections must not be bridged. Wiring sets DILM 12-XRL and PKZM0-XRM12 cannot be used. Connection terminals for electrical interlocking are not suitable for safety technology. |
Standards | IEC/EN 61131-2 EN 50178 IEC/EN 60947 |
Dimensions (W x H x D) | 45 x 38 x 76 mm |
Weight | 0.04 kg |
Mounting | on DILM7…DILM38 |
Mounting position | as DILM7 to DILM38 |
Protection type (IEC/EN 60529, EN50178, VBG 4) | IP20 |
Vibrations (IEC/EN 61131-2:2008) >Constant amplitude 3,5 mm |
5 - 8.4 Hz |
Vibrations (IEC/EN 61131-2:2008) >Constant acceleration 1 g |
8.4 - 150 Hz |
Mechanical shock resistance (IEC/EN 60068-2-27) semi-sinusoidal 15 g/11 ms | 9 Impacts |
Drop to IEC/EN 60068-2-31 [Drop height] | 50 mm |
Free fall, packaged (IEC/EN 60068-2-32) | 0.3 m |
Overvoltage category | II |
Pollution degree | 2 |
Electrostatic discharge (IEC/EN 61131-2:2008) >Air discharge (Level 3) |
8 kV |
Electrostatic discharge (IEC/EN 61131-2:2008) >Contact discharge (Level 2) |
4 kV |
Electromagnetic fields (IEC/EN 61131-2:2008) >80 - 1000 MHz |
10 V/m |
Electromagnetic fields (IEC/EN 61131-2:2008) >1.4 - 2 GHz |
3 V/m |
Electromagnetic fields (IEC/EN 61131-2:2008) >2 - 2.7 GHz |
1 V/m |
Radio interference suppression (SmartWire-DT) | EN 55011 Class A |
Burst (IEC/EN 61131-2:2008, Level 3) >CAN/DP bus cable |
1 kV |
Burst (IEC/EN 61131-2:2008, Level 3) >SmartWire-DT cables |
1 kV |
Radiated RFI (IEC/EN 61131-2:2008, Level 3) | 10 V |
Operating ambient temperature (IEC 60068-2) | - 25 - +60 °C |
Condensation | Take appropriate measures to prevent condensation |
Storage | - 30 - 70 °C |
Relative humidity, non-condensing (IEC/EN 60068-2-30) | 5 - 95 % |
Station type | SmartWire-DT slave |
Address allocation | automatic |
SmartWire-DT status LED | green/orange LED |
Connections | Plug, 8-pole |
Plug connectors | External device plug SWD4-8SF2-5 |
Current consumption | 40 mA |
Pick-up power >for DILM 7-9 |
3 W |
Pick-up power >for DILM 12-15 |
4.5 W |
Pick-up power >for DILM 17-38 |
12 W |
Pick-up current >for DILM 7-9 |
125 mA |
Pick-up current >for DILM 12-15 |
188 mA |
Pick-up current >for DILM 17-38 |
500 mA |
Holding power >for DILM 7-9 |
3 W |
Holding power >for DILM 12-15 |
4.5 W |
Holding power >for DILM 17-38 |
0.5 W |
Holding current >for DILM 17-38 |
21 mA |
Holding current >for DILM 12-15 |
188 mA |
Holding current >for DILM 7-9 |
125 mA |
Manual/automatic mode | yes |
Setting | viaRotary switch |
Number | 2 |
Rated voltage [Ue ] | 15 V DC |
Input current at 1 signal, typical | 3 mA |
Potential isolation | No |
Cable length | ≦ 2.8 m |
Connection type | Push in terminals |
Solid | 0.2 - 1.5 (AWG 24 - 16) mm2 |
Flexible with ferrule | 0.25 - 1.5 mm2 |
Notes | own supply Minimum length 8 mm. |
Rated operational current for specified heat dissipation [In] | 0 A |
Heat dissipation per pole, current-dependent [Pvid] | 0 W |
Equipment heat dissipation, current-dependent [Pvid] | 0 W |
Static heat dissipation, non-current-dependent [Pvs] | 0.8 W |
Heat dissipation capacity [Pdiss] | 0 W |
Operating ambient temperature min. | -25 °C |
Operating ambient temperature max. | +60 °C |
10.2 Strength of materials and parts >10.2.2 Corrosion resistance |
Meets the product standard´s requirements. |
10.2 Strength of materials and parts >10.2.3.1 Verification of thermal stability of enclosures |
Meets the product standard´s requirements. |
10.2 Strength of materials and parts >10.2.3.2 Verification of resistance of insulating materials to normal heat |
Meets the product standard´s requirements. |
10.2 Strength of materials and parts >10.2.3.3 Verification of resistance of insulating materials to abnormal heat and fire due to internal electric effects |
Meets the product standard´s requirements. |
10.2 Strength of materials and parts >10.2.4 Resistance to ultra-violet (UV) radiation |
Meets the product standard´s requirements. |
10.2 Strength of materials and parts >10.2.5 Lifting |
Does not apply, since the entire switchgear needs to be evaluated. |
10.2 Strength of materials and parts >10.2.6 Mechanical impact |
Does not apply, since the entire switchgear needs to be evaluated. |
10.2 Strength of materials and parts >10.2.7 Inscriptions |
Meets the product standard´s requirements. |
10.3 Degree of protection of ASSEMBLIES | Does not apply, since the entire switchgear needs to be evaluated. |
10.4 Clearances and creepage distances | Meets the product standard´s requirements. |
10.5 Protection against electric shock | Does not apply, since the entire switchgear needs to be evaluated. |
10.6 Incorporation of switching devices and components | Does not apply, since the entire switchgear needs to be evaluated. |
10.7 Internal electrical circuits and connections | Is the panel builder´s responsibility. |
10.8 Connections for external conductors | Is the panel builder´s responsibility. |
10.9 Insulation properties >10.9.2 Power-frequency electric strength |
Is the panel builder´s responsibility. |
10.9 Insulation properties >10.9.3 Impulse withstand voltage |
Is the panel builder´s responsibility. |
10.9 Insulation properties >10.9.4 Testing of enclosures made of insulating material |
Is the panel builder´s responsibility. |
10.10 Temperature rise | The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices. |
10.11 Short-circuit rating | Is the panel builder´s responsibility. The specifications for the switchgear must be observed. |
10.12 Electromagnetic compatibility | Is the panel builder´s responsibility. The specifications for the switchgear must be observed. |
10.13 Mechanical function | The device meets the requirements, provided the information in the instruction leaflet (IL) is observed. |
Supply voltage AC 50 Hz | 0 - 0 V |
Supply voltage AC 60 Hz | 0 - 0 V |
Supply voltage DC | 15 - 15 V |
Voltage type of supply voltage | DC |
Number of digital inputs | 2 |
Number of digital outputs | 1 |
Digital inputs configurable | No |
Digital outputs configurable | No |
Input current at signal 1 | 3 mA |
Permitted voltage at input | 15 - 15 V |
Type of voltage (input voltage) | DC |
Type of digital output | Other |
Output current | 0.5 A |
Permitted voltage at output | 20.4 - 28.8 V |
Type of output voltage | DC |
Short-circuit protection, outputs available | No |
Number of HW-interfaces industrial Ethernet | 0 |
Number of interfaces PROFINET | 0 |
Number of HW-interfaces RS-232 | 0 |
Number of HW-interfaces RS-422 | 0 |
Number of HW-interfaces RS-485 | 0 |
Number of HW-interfaces serial TTY | 0 |
Number of HW-interfaces parallel | 0 |
Number of HW-interfaces Wireless | 0 |
Number of HW-interfaces USB | 0 |
Number of HW-interfaces other | 1 |
With optical interface | No |
Supporting protocol for TCP/IP | No |
Supporting protocol for PROFIBUS | No |
Supporting protocol for CAN | No |
Supporting protocol for INTERBUS | No |
Supporting protocol for ASI | No |
Supporting protocol for KNX | No |
Supporting protocol for MODBUS | No |
Supporting protocol for Data-Highway | No |
Supporting protocol for DeviceNet | No |
Supporting protocol for SUCONET | No |
Supporting protocol for LON | No |
Supporting protocol for PROFINET IO | No |
Supporting protocol for PROFINET CBA | No |
Supporting protocol for SERCOS | No |
Supporting protocol for Foundation Fieldbus | No |
Supporting protocol for EtherNet/IP | No |
Supporting protocol for AS-Interface Safety at Work | No |
Supporting protocol for DeviceNet Safety | No |
Supporting protocol for INTERBUS-Safety | No |
Supporting protocol for PROFIsafe | No |
Supporting protocol for SafetyBUS p | No |
Supporting protocol for other bus systems | Yes |
Radio standard Bluetooth | No |
Radio standard WLAN 802.11 | No |
Radio standard GPRS | No |
Radio standard GSM | No |
Radio standard UMTS | No |
IO link master | No |
System accessory | Yes |
Degree of protection (IP) | IP20 |
Type of electric connection | Spring clamp connection |
Time delay at signal exchange | 10 - 84 ms |
Fieldbus connection over separate bus coupler possible | Yes |
Rail mounting possible | No |
Wall mounting/direct mounting | No |
Front build in possible | No |
Rack-assembly possible | No |
Suitable for safety functions | No |
Category according to EN 954-1 | 1 |
SIL according to IEC 61508 | None |
Performance level acc. EN ISO 13849-1 | None |
Appendant operation agent (Ex ia) | No |
Appendant operation agent (Ex ib) | No |
Explosion safety category for gas | None |
Explosion safety category for dust | None |
Width | 45 mm |
Height | 38 mm |
Depth | 81 mm |
Product Standards | IEC/EN 60947-4-1; UL 508; CSA-C22.2 No. 14-05; CE marking |
UL File No. | E29184 |
UL Category Control No. | NKCR |
CSA File No. | 2324643 |
CSA Class No. | 3211-07 |
North America Certification | UL listed, CSA certified |
Specially designed for North America | No |
Mnelko olarak, endüstriyel otomasyon çözümlerinde güvenilir bir iş ortağı olarak, geniş ürün yelpazesi ile işletmenizin tüm ihtiyaçlarını karşılamaya yönelik kaliteli ve yenilikçi ürünler sunmaktayız. Ürün portföyümüz, modern endüstriyel süreçleri desteklemek amacıyla yüksek performans, dayanıklılık ve verimlilik ilkeleri doğrultusunda tasarlanmış çözümlerden oluşur.
Tüm ürünlerimiz, zorlu çalışma koşullarında dahi maksimum güvenilirlik sunar ve işletmenizin operasyonlarını sorunsuz şekilde sürdürmesine yardımcı olur. Endüstriyel otomasyon, enerji yönetimi, kablolama çözümleri ve daha birçok alanda sunduğumuz ürünler, farklı sektörlerdeki ihtiyaçlara esneklikle uyum sağlar.
Ayrıca, ürünlerimiz sadece kaliteli malzemelerle üretilmiş olup, uluslararası standartlara uygunluk göstermektedir. Müşterilerimize sunduğumuz çözümlerle, operasyonel verimliliklerini artırmalarına ve maliyetlerini optimize etmelerine olanak tanıyoruz. Teknolojik gelişmeleri yakından takip eden firmamız, sürekli olarak yenilikçi ürünler sunarak, müşterilerimizin rekabet avantajı elde etmesine destek vermektedir.
Her bir ürün sayfamızda, teknik detaylar, kullanım alanları ve ürün özelliklerine dair kapsamlı bilgilere ulaşabilirsiniz. Endüstriyel süreçlerinizi güçlendirmek için ihtiyacınız olan tüm ürünleri sitemizden keşfedebilir, sorunsuz bir satın alma deneyimi yaşayabilirsiniz.