| Product range | CI-K small enclosures | 
		
			| Basic function | Basic enclosures | 
		
			| Product function | CI-K empty enclosures | 
		
			| Single unit/Complete unit | Single unit | 
		
			| Degree of Protection | Front IP65 IP65, with push-through cable entry
 | 
		
			| Degree of Protection | Front IP65 IP65, with push-through cable entry
 | 
		
			| Material | Glass-fibre reinforced polycarbonate | 
		
			| Colour | Enclosure base RAL 9005, black Operator only RAL 7035, light gray
 | 
		
			| Description | Metric cable entry knockouts top, bottom and in the back plate Control cable entry
 Lamp indicator L‐… can be mounted in base knock-out M20/M25
 | 
		
			| Cable entry | hard knockout version | 
		
			| Width | 100 mm | 
		
			| Height | 160 mm | 
		
			| Depth | 145 mm | 
		
			| Dimensions |  | 
		
			| Legend for the graphic | Dimensions from top: Mounting depth with mounting plate
 Mounting depth for mounting rail 7.5 mm height
 Mounting depth for mounting rail 15 mm height
 | 
		
			| Enclosure depth |  | 
		
			| Mounting depth with mounting plate | 124 mm | 
		
			| Features | with adapter plate for contactors DILE with motor-protective relay ZE | 
		
			| Notes | | M | q |  |   |   |  | Knockouts | Knockouts |  | 2 X M25 or push-through membrane up to max. ⌀ 16 mm | 2 x M25 or push-through membrane up to a max. diameter of 16 mm and 1 push-through membrane up to a max. diameter of 8 mm |  |  |  |  | T |  |  |   |  |  | Back plate:  |  |  | 2 x push-through membrane up to max. ⌀ 11mm |  |  | (not for CI-K2H) |  | 
 | 
		
			| Standards | IEC/EN 60529 DIN EN 62208
 | 
		
			| Climatic proofing | Damp heat, constant, to IEC 60068-2-78 Damp heat, cyclic, to IEC 60068-2-30
 | 
		
			| Ambient temperature | -25 - +70 -25 - +40 (with push-through cable entry) °C
 | 
		
			| Degree of Protection | Front IP65 IP65, with push-through cable entry
 | 
		
			| Power loss >Max. radiated heat dissipation with separate mounting, ambient air temperature +20 °C
 | 18.5 W | 
		
			| Material >Base
 | Glass-fibre reinforced polycarbonate | 
		
			| Material >Cover
 | Glass-fibre reinforced polycarbonate | 
		
			| Surface treatment | Resistant to corrosion | 
		
			| Colour >Base
 | RAL 9005, black (matt) | 
		
			| Colour >Housing body
 | Enclosure cover RAL 7035, light grey (matt) | 
		
			| Electrical >Track resistance
 | CTI 175 (base, to IEC 60112) CTI 175 (cover, to IEC 60112)
 | 
		
			| Electrical >Surface resistance to IEC 60093
 | 1 Ω x 1013 | 
		
			| Electrical >Dielectric strength to IEC 60243-1
 | 30 kV/mm | 
		
			| Thermal >Temperature resistant
 | -40 °C - 120 °C (enclosure) -40 °C - +80 °C (gasket)
 | 
		
			| Mechanical >Impact resistance
 | IK06 according to EN 50102 | 
		
			| Mechanical >max. assembly weights
 >Mounting plate
 | 0.7 kg | 
		
			| Mechanical >max. assembly weights
 >Mounting rail
 | 0.7 kg | 
		
			| Chemical resistance >Chemical resistant
 | Base, Cover Resistant against: Acids < 10 %, mineral oil, alcohol, gasoline, greases, salt solutions
 Partly resistant to: Acids > 10 %, alcohol
 Not resistant to: alkalis, benzene
 Push-through membrane (CI-K1/CI-K2) and sealing material
 Resistant against: Acids < 10 %, alkalis, benzene, salt solutions
 Partly resistant to: Acids > 10 %, greases, benzene
 Not resistant to: Mineral oil, benzene
 | 
		
			| Atmospheric >Saline spray
 | IEC 60068-2-11 | 
		
			| Atmospheric >UV resistance
 | Beneath protective shield | 
		
			| Atmospheric >Water consumption to DIN EN ISO 62
 | 0.29 % | 
		
			| Flammability characteristics >Glow wire test
 >Flammability characteristics
 | 960 °C/1mm thickness (base, cover; glow wire to VDE 0471 Part 2) 650 °C/1mm thick (push-through membrane and seal material) to VDE 0471 Part 2)
 | 
		
			| Flammability characteristics >Glow wire test
 >to UL 94
 | VO/1.5 mm thickness | 
		
			| Flammability characteristics >Glow wire test
 >to UL 94
 | HB | 
		
			| Flammability characteristics >Halogen free
 | Yes | 
		
			| Rated operational current for specified heat dissipation [In] | 0 A | 
		
			| Heat dissipation per pole, current-dependent [Pvid] | 0 W | 
		
			| Equipment heat dissipation, current-dependent [Pvid] | 0 W | 
		
			| Static heat dissipation, non-current-dependent [Pvs] | 0 W | 
		
			| Heat dissipation capacity [Pdiss] | 18.5 W | 
		
			| Operating ambient temperature min. | -25 °C | 
		
			| Operating ambient temperature max. | +70 °C | 
		
			| Degree of Protection | Front IP65 IP65, with push-through cable entry
 | 
		
			| Max. radiated heat dissipation with separate mounting, ambient air temperature +20 °C | 18.5 W | 
		
			| Flammability characteristics | 960 °C/1mm thickness (base, cover; glow wire to VDE 0471 Part 2) 650 °C/1mm thick (push-through membrane and seal material) to VDE 0471 Part 2)
 | 
		
			| Track resistance | CTI 175 (base, to IEC 60112) CTI 175 (cover, to IEC 60112)
 | 
		
			| Surface treatment | Resistant to corrosion | 
		
			| Impact resistance | IK06 according to EN 50102 | 
		
			| Temperature resistant | -40 °C - 120 °C (enclosure) -40 °C - +80 °C (gasket)
 | 
		
			| UV resistance | Beneath protective shield | 
		
			| 10.2 Strength of materials and parts >10.2.2 Corrosion resistance
 | Meets the product standard´s requirements. | 
		
			| 10.2 Strength of materials and parts >10.2.3.1 Verification of thermal stability of enclosures
 | Meets the product standard´s requirements. | 
		
			| 10.2 Strength of materials and parts >10.2.3.2 Verification of resistance of insulating materials to normal heat
 | Meets the product standard´s requirements. | 
		
			| 10.2 Strength of materials and parts >10.2.3.3 Verification of resistance of insulating materials to abnormal heat and fire due to internal electric effects
 | Meets the product standard´s requirements. | 
		
			| 10.2 Strength of materials and parts >10.2.4 Resistance to ultra-violet (UV) radiation
 | Please enquire | 
		
			| 10.2 Strength of materials and parts >10.2.5 Lifting
 | Not applicable. | 
		
			| 10.2 Strength of materials and parts >10.2.6 Mechanical impact
 | Meets the product standard´s requirements. | 
		
			| 10.2 Strength of materials and parts >10.2.7 Inscriptions
 | Meets the product standard´s requirements. | 
		
			| 10.3 Degree of protection of ASSEMBLIES | Meets the product standard´s requirements. | 
		
			| 10.4 Clearances and creepage distances | Meets the product standard´s requirements. | 
		
			| 10.5 Protection against electric shock | Is the panel builder´s responsibility. | 
		
			| 10.6 Incorporation of switching devices and components | Is the panel builder´s responsibility. | 
		
			| 10.7 Internal electrical circuits and connections | Is the panel builder´s responsibility. | 
		
			| 10.8 Connections for external conductors | Is the panel builder´s responsibility. | 
		
			| 10.9 Insulation properties >10.9.2 Power-frequency electric strength
 | Is the panel builder´s responsibility. | 
		
			| 10.9 Insulation properties >10.9.3 Impulse withstand voltage
 | Is the panel builder´s responsibility. | 
		
			| 10.9 Insulation properties >10.9.4 Testing of enclosures made of insulating material
 | Meets the product standard´s requirements. | 
		
			| 10.10 Temperature rise | The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices. | 
		
			| 10.11 Short-circuit rating | Is the panel builder´s responsibility. The specifications for the switchgear must be observed. | 
		
			| 10.12 Electromagnetic compatibility | Is the panel builder´s responsibility. The specifications for the switchgear must be observed. | 
		
			| 10.13 Mechanical function | The device meets the requirements, provided the information in the instruction leaflet (IL) is observed. | 
		
			| Material housing | Plastic | 
		
			| Width | 100 mm | 
		
			| Height | 160 mm | 
		
			| Depth | 145 mm | 
		
			| With transparent cover | No | 
		
			| Suitable for emergency stop | Yes | 
		
			| Model | Surface mounting | 
		
			| Degree of protection (IP) | IP65 | 
		
			| Degree of protection (NEMA) | Other |