007595 AT0-02-1-IA/H

Position switch, 2 N/C, wide, IP65_x, actuating rod
Position switch, Degree of Protection: IP65, Contacts N/C = Normally closed: 2 NC, Notes: = safety function, by positive opening to IEC/EN 60947-5-1, Housing: Wide version, Standards: IEC/EN 60947

Ürün Açıklaması

Position switch, 2 N/C, wide, IP65_x, actuating rod
Position switch, Degree of Protection: IP65, Contacts N/C = Normally closed: 2 NC, Notes: = safety function, by positive opening to IEC/EN 60947-5-1, Housing: Wide version, Standards: IEC/EN 60947
Degree of Protection IP65
N/C = Normally closed 2 NC
Notes = safety function, by positive opening to IEC/EN 60947-5-1
Contact sequence 131S004
Contact travel■ = Contact closed□ = Contact open 131U020
Housing Wide version
Standards IEC/EN 60947
Climatic proofing Damp heat, constant, to IEC 60068-2-78; damp heat, cyclical, to IEC 60068-2-30
Mounting position As required
Degree of Protection IP65
Terminal capacities
>Solid
1 x (0.75 - 2.5)
2 x (0.75 - 1.5) mm2
Terminal capacities
>Flexible with ferrule
1 x (0.5 - 1.5)
2 x (0.5 - 1.5) mm2
Repetition accuracy 0.02 mm
Rated impulse withstand voltage [Uimp] 6000 V AC
Rated insulation voltage [Ui ] 500 V
Rated operational current [Ie ]
>AC-15
>24 V [Ie ]
10 A
Rated operational current [Ie ]
>AC-15
>220 V 230 V 240 V [Ie]
6 A
Rated operational current [Ie ]
>AC-15
>380 V 400 V 415 V [Ie]
4 A
Rated operational current [Ie ]
>DC-13
>24 V [Ie ]
10 A
Rated operational current [Ie ]
>DC-13
>110 V [Ie ]
1 A
Rated operational current [Ie ]
>DC-13
>220 V [Ie ]
0.5 A
Supply frequency max. 400 Hz
Short-circuit rating to IEC/EN 60947-5-1
>max. fuse
6 A gG/gL
Contact temperature of roller head ≦ 100 °C
Mechanical shock resistance (half-sinusoidal shock, 20 ms)
>Standard-action contact
25 g
Mechanical shock resistance (half-sinusoidal shock, 20 ms)
>Snap-action contact
2 g
Operating frequency [Operations/h] ≦ 6000
Mechanical
>Actuating torque of rotary drives
0.2 Nm
Mechanical
>Max. operating speed with DIN cam
1.5 m/s
Mechanical
>Notes
L = 130 mm
Rated operational current for specified heat dissipation [In] 6 A
Heat dissipation per pole, current-dependent [Pvid] 0.13 W
Equipment heat dissipation, current-dependent [Pvid] 0 W
Static heat dissipation, non-current-dependent [Pvs] 0 W
Heat dissipation capacity [Pdiss] 0 W
Operating ambient temperature min. -25 °C
Operating ambient temperature max. +70 °C
10.2 Strength of materials and parts
>10.2.2 Corrosion resistance
Meets the product standard´s requirements.
10.2 Strength of materials and parts
>10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard´s requirements.
10.2 Strength of materials and parts
>10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard´s requirements.
10.2 Strength of materials and parts
>10.2.3.3 Verification of resistance of insulating materials to abnormal heat and fire due to internal electric effects
Meets the product standard´s requirements.
10.2 Strength of materials and parts
>10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard´s requirements.
10.2 Strength of materials and parts
>10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
10.2 Strength of materials and parts
>10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2 Strength of materials and parts
>10.2.7 Inscriptions
Meets the product standard´s requirements.
10.3 Degree of protection of ASSEMBLIES Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances Meets the product standard´s requirements.
10.5 Protection against electric shock Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections Is the panel builder´s responsibility.
10.8 Connections for external conductors Is the panel builder´s responsibility.
10.9 Insulation properties
>10.9.2 Power-frequency electric strength
Is the panel builder´s responsibility.
10.9 Insulation properties
>10.9.3 Impulse withstand voltage
Is the panel builder´s responsibility.
10.9 Insulation properties
>10.9.4 Testing of enclosures made of insulating material
Is the panel builder´s responsibility.
10.10 Temperature rise The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating Is the panel builder´s responsibility. The specifications for the switchgear must be observed.
10.12 Electromagnetic compatibility Is the panel builder´s responsibility. The specifications for the switchgear must be observed.
10.13 Mechanical function The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
Width sensor 51 mm
Diameter sensor 0 mm
Height of sensor 51 mm
Length of sensor 0 mm
Rated operation current Ie at AC-15, 24 V 10 A
Rated operation current Ie at AC-15, 125 V 0 A
Rated operation current Ie at AC-15, 230 V 6 A
Rated operation current Ie at DC-13, 24 V 10 A
Rated operation current Ie at DC-13, 125 V 1 A
Rated operation current Ie at DC-13, 230 V 0.5 A
Switching function Slow-action switch
Switching function latching No
Output electronic No
Forced opening No
Number of safety auxiliary contacts 0
Number of contacts as normally closed contact 2
Number of contacts as normally open contact 0
Number of contacts as change-over contact 0
Type of interface None
Type of interface for safety communication None
Construction type housing Cuboid
Material housing Plastic
Coating housing Other
Type of control element Actuating rod
Alignment of the control element Other
Type of electric connection Other
With status indication No
Suitable for safety functions Yes
Explosion safety category for gas None
Explosion safety category for dust None
Ambient temperature during operating 25 - 70 °C
Degree of protection (IP) IP65
Degree of protection (NEMA) Other