Product range |
XV150 8.4" |
Product range |
XV-152 |
Subrange |
SmartWire-DT touch display with integrated controller (HMI PLC) |
Function |
SmartWire-DT coordinator |
Description |
XV150 touch display with PLC function for flush mounting plates |
Description |
Coordinator for the SmartWire-DT communications system |
Common features of the model series |
Ethernet interface USB device USB Host Slot for SD card UL508, cUL approvals |
Display - Type |
Color display, TFT |
Touch-technology |
Resistive-Touch |
Number of colours |
64 k Colours |
Resolution |
VGA 640 x 480 Pixel |
Portrait format |
yes |
Screen diagonal |
8.4 Inch |
Model |
Metal enclosure and front plate |
Operating system |
Windows CE 5.0 (licence incl.) |
PLC-licence |
PLC licence inclusive |
License certificates for onboard interfaces |
Not required |
built-in interfaces |
1 x Ethernet 10/100 Mbps 1 x RS485 1 x USB host 2.0 1 x USB device 1 x CANopen®/easyNet 1 x SmartWire-DT |
Front type |
Standard front with standard membrane (fully enclosed) |
Utilization |
Flush mounting |
Slots |
for SD card: 1 |
Memory card automation |
Optionally with SD card -> article no. 139807 |
Pluggable communication cards (optional) |
no |
Touch sensor |
Glass with film |
Heat dissipation |
14.5 W |
Connection to SmartWire-DT |
yes |
Display - Type |
Color display, TFT |
Screen diagonal |
8.4 Inch |
Resolution |
VGA 640 x 480 Pixel |
Visible screen area |
170 x 128 mm |
Number of colours |
64 k Colours |
Contrast ratio (Normally) |
Normally 300:1 |
Brightness |
Normally 250 cd/m2 |
Back-lighting |
LED dimmable via software |
Service life of back-lighting |
Normally 40000 h |
Resistive touch protective screen |
Touch sensor (glass with foil) |
Technology |
Resistive-Touch 4 wire |
Touch sensor |
Glass with film |
Processor |
RISC CPU, 32 Bit, 400 MHz |
Internal memory |
DRAM (OS, Program and data memory): 64 MByte NAND-Flash (can be used for data backup): approx. 64 MByte available NVRAM (Retain data): 125 kByte NOR-Flash: 2 MByte |
External memory |
SD Memory Card Slot: SDA Specification 1.00 |
Cooling |
Fanless CPU and system cooling, natural convection-based passive cooling |
Back-up of real-time clock >Battery (service life) |
non-replaceable, CR2032 soldered in |
Back-up of real-time clock >Backup (time at zero voltage) |
Normally 10 years |
Visualisation software |
GALILEO EPAM XSOFT-CODESYS-2 XSOFT-CODESYS-3 |
PLC-Programming software |
XSOFT-CODESYS-2 XSOFT-CODESYS-3 |
Target and web visualization |
Yes |
PLC-licence |
PLC licence inclusive |
Operating system |
Windows CE 5.0 (licence incl.) |
built-in interfaces |
1 x Ethernet 10/100 Mbps 1 x RS485 1 x USB host 2.0 1 x USB device 1 x CANopen®/easyNet 1 x SmartWire-DT |
USB device |
USB 2.0, not galvanically isolated |
RS-232 |
no |
RS-485 |
Yes |
CAN |
Yes |
Profibus |
no |
Slots |
for SD card: 1 |
SmartWire-DT master |
Yes |
Ethernet |
100Base-TX/10Base-T |
easyNet |
Yes |
MPI |
no |
Nominal voltage |
24 V DC SELV (safety extra low voltage) |
permissible voltage |
Effective: 19.2-30.0 V DC (rated operating voltage -20%/+25%) Absolute with ripple: 18,0-31,2 V DC Battery powered: 18,0-31,2 V DC (rated operating voltage -25%/+30%) 35 V DC for a duration of < 100 ms |
Voltage dips |
≤ 10 ms from rated voltage (24 V DC) 5 ms from undervoltage (19.2 V DC) ms |
Power consumption [Pmax.] |
12 W |
Note on power consumption |
Basic device USB Slave to USB Host: 2.5 Total: 9.5 |
Heat dissipation |
14.5 W |
Note on heat dissipation |
Heat dissipation with power consumption for 24 V 12 W for basic device + 2.5 W for USB module |
Current consumption [I] |
Continuous current = 0.6 (24 V DC) A |
Siemens MPI, (optional) |
yes |
Type of fuse |
Yes (fuse not accessible) |
Potential isolation |
no potential isolation |
Housing material |
Metal, anodized |
Front type |
Standard front with standard membrane (fully enclosed) |
Dimensions (W x H x D) |
275 x 208 x 54 mm |
flush mounted |
Clearance: W x H x D ≥ 30 mm (1.18") Inclination from vertical: ±45° (if using natural convection) |
Weight |
2.1 kg |
Degree of protection (IEC/EN 60529, EN50178, VBG 4) |
IP65 (at front), IP20 (at rear) Enclosure Type 4X (Indoor use only) |
Approvals >Approvals |
cUL (UL508) |
Approvals >Explosion protection (according to ATEX 94/9/EC) |
II 3D Ex II T70°C IP5x: Zone 22, Category 3D |
Approvals >shipping classification |
DNV GL |
Approvals |
|
Applied standards and directives >EMC |
(in relation to CE) EN 61000-6-2 EN 61000-6-4 EN 61131-2 |
Applied standards and directives >Product standards |
EN 50178 EN 61131-2 |
Applied standards and directives >Security |
EN 60950 UL 60950 |
Standards |
Explosion protection (relevant for CE) ATEX 94/9/EG: Zone 22, Category 3D (II 3D Ex tc IIIC T70°C IP6x): IEC/EN 60079-0 IEC/EN 61241-0 IEC/EN 61241-1 Security: IEC/EN 60950 UL 508 Product standards: EN 50178 IEC/EN 61131-2 EMC /relevant for CE): IEC/EN 61000-6-2 IEC/EN 61000-6-4 IEC/EN 61131-2 IEC/EN 61000-6-3 |
Mechanical shock resistance |
according to IEC 60068-2-27 g |
Vibration |
according to IEC/EN 60068-2-6 |
RoHS |
conform |
Climatic environmental conditions >Air pressure (operation) |
795 - 1080 hPa |
Temperature >Storage / Transport [ϑ] |
-20 - +60 °C |
Temperature >Operating ambient temperature min. |
0 °C |
Temperature >Operating ambient temperature max. |
+50 °C |
Relative humidity >Relative humidity |
IEC/EN 50178 10 - 95%, non-condensing |
Rated operational voltage [UAux] |
24 V DC (-20/+25%) V |
Residual ripple on the input voltage |
≦ 5 % |
Protection against polarity reversal |
Yes |
Max. current [Imax] |
3 A |
Note |
If contactors with a total power consumption > 3 A are connected, a power feeder module EU5C-SWD-PF1/2 has to be used. |
Short-circuit rating |
no, external fuse FAZ Z3 |
Potential isolation |
No |
Rated operating voltage of 24-V-DC slaves |
typ. UAux - 0.2 V |
Supply voltage [UPow] |
24 DC -20 % + 25 % V |
Input voltage ripple |
≦ 5 % |
Siemens MPI, (optional) |
yes |
Rated current [I] |
0.7 A |
Overload proof |
yes |
Inrush current and duration |
12.5 A/6 ms A |
Heat dissipation at 24 V DC |
1.0 W |
Potential isolation between UPow and 15 V SmartWire-DT supply voltage |
No |
Bridging voltage dips |
10 ms |
Repetition rate |
1 s |
Status indication |
yes LED |
Rated operating voltage [Ue] |
14,5 ± 3 % V |
max. current [Imax] |
0.7 A |
Note |
If SmartWire-DT modules with a total power consumption > 0.7 A are connected, a power feeder module EU5C-SWD-PF2 has to be used. |
Short-circuit rating |
Yes |
Connection type |
Push in terminals |
Solid |
0.2 - 1.5 mm2 |
Flexible with ferrule |
0.25 - 1.5 (AWG 24 - 16) mm2 |
UL/CSA solid or stranded |
24 - 16 AWG |
Station type |
SmartWire-DT master |
Number of SmartWire-DT slaves |
99 |
Baud Rates |
125 250 kBd |
Address allocation |
automatic |
Status indication |
SmartWire-DT master LED: red/green Configurations LED: red/green LED |
Connections |
Plug, 8-pole |
Plug connectors |
Blade terminal SWD4-8MF2 |
Rated operational current for specified heat dissipation [In] |
0 A |
Heat dissipation per pole, current-dependent [Pvid] |
0 W |
Equipment heat dissipation, current-dependent [Pvid] |
0 W |
Static heat dissipation, non-current-dependent [Pvs] |
14.5 W |
Heat dissipation capacity [Pdiss] |
0 W |
Operating ambient temperature min. |
0 °C |
Operating ambient temperature max. |
+50 °C |
10.2 Strength of materials and parts >10.2.2 Corrosion resistance |
Meets the product standard´s requirements. |
10.2 Strength of materials and parts >10.2.3.1 Verification of thermal stability of enclosures |
Meets the product standard´s requirements. |
10.2 Strength of materials and parts >10.2.3.2 Verification of resistance of insulating materials to normal heat |
Meets the product standard´s requirements. |
10.2 Strength of materials and parts >10.2.3.3 Verification of resistance of insulating materials to abnormal heat and fire due to internal electric effects |
Meets the product standard´s requirements. |
10.2 Strength of materials and parts >10.2.4 Resistance to ultra-violet (UV) radiation |
Please enquire |
10.2 Strength of materials and parts >10.2.5 Lifting |
Does not apply, since the entire switchgear needs to be evaluated. |
10.2 Strength of materials and parts >10.2.6 Mechanical impact |
Does not apply, since the entire switchgear needs to be evaluated. |
10.2 Strength of materials and parts >10.2.7 Inscriptions |
Meets the product standard´s requirements. |
10.3 Degree of protection of ASSEMBLIES |
Meets the product standard´s requirements. |
10.4 Clearances and creepage distances |
Meets the product standard´s requirements. |
10.5 Protection against electric shock |
Does not apply, since the entire switchgear needs to be evaluated. |
10.6 Incorporation of switching devices and components |
Does not apply, since the entire switchgear needs to be evaluated. |
10.7 Internal electrical circuits and connections |
Is the panel builder´s responsibility. |
10.8 Connections for external conductors |
Is the panel builder´s responsibility. |
10.9 Insulation properties >10.9.2 Power-frequency electric strength |
Is the panel builder´s responsibility. |
10.9 Insulation properties >10.9.3 Impulse withstand voltage |
Is the panel builder´s responsibility. |
10.9 Insulation properties >10.9.4 Testing of enclosures made of insulating material |
Is the panel builder´s responsibility. |
10.10 Temperature rise |
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices. |
10.11 Short-circuit rating |
Is the panel builder´s responsibility. |
10.12 Electromagnetic compatibility |
Is the panel builder´s responsibility. |
10.13 Mechanical function |
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed. |
Supply voltage AC 50 Hz |
0 - 0 V |
Supply voltage AC 60 Hz |
0 - 0 V |
Supply voltage DC |
20.4 - 28.8 V |
Voltage type of supply voltage |
DC |
Number of HW-interfaces industrial Ethernet |
1 |
Number of interfaces PROFINET |
0 |
Number of HW-interfaces RS-232 |
0 |
Number of HW-interfaces RS-422 |
0 |
Number of HW-interfaces RS-485 |
1 |
Number of HW-interfaces serial TTY |
0 |
Number of HW-interfaces USB |
2 |
Number of HW-interfaces parallel |
0 |
Number of HW-interfaces Wireless |
0 |
Number of HW-interfaces other |
2 |
With SW interfaces |
Yes |
Supporting protocol for TCP/IP |
Yes |
Supporting protocol for PROFIBUS |
No |
Supporting protocol for CAN |
Yes |
Supporting protocol for INTERBUS |
No |
Supporting protocol for ASI |
No |
Supporting protocol for KNX |
No |
Supporting protocol for MODBUS |
Yes |
Supporting protocol for Data-Highway |
No |
Supporting protocol for DeviceNet |
No |
Supporting protocol for SUCONET |
No |
Supporting protocol for LON |
No |
Supporting protocol for PROFINET IO |
No |
Supporting protocol for PROFINET CBA |
No |
Supporting protocol for SERCOS |
No |
Supporting protocol for Foundation Fieldbus |
No |
Supporting protocol for EtherNet/IP |
Yes |
Supporting protocol for AS-Interface Safety at Work |
No |
Supporting protocol for DeviceNet Safety |
No |
Supporting protocol for INTERBUS-Safety |
No |
Supporting protocol for PROFIsafe |
No |
Supporting protocol for SafetyBUS p |
No |
Supporting protocol for other bus systems |
Yes |
Radio standard Bluetooth |
No |
Radio standard WLAN 802.11 |
No |
Radio standard GPRS |
No |
Radio standard GSM |
No |
Radio standard UMTS |
No |
IO link master |
No |
Type of display |
TFT |
With colour display |
Yes |
Number of colours of the display |
65536 |
Number of grey-scales/blue-scales of display |
0 |
Screen diagonal |
8.4 inch |
Number of pixels, horizontal |
640 |
Number of pixels, vertical |
480 |
Useful project memory/user memory |
64000 kByte |
With numeric keyboard |
Yes |
With alpha numeric keyboard |
Yes |
Number of function buttons, programmable |
0 |
Number of buttons with LED |
0 |
Number of system buttons |
1 |
Touch technology |
Resistive touch |
With message indication |
Yes |
With message system (incl. buffer and confirmation) |
Yes |
Process value representation (output) possible |
Yes |
Process default value (input) possible |
Yes |
With recipes |
Yes |
Number of password levels |
200 |
With printer output |
Yes |
Number of online languages |
100 |
Additional software components, loadable |
Yes |
Degree of protection (IP), front side |
IP65 |
Degree of protection (NEMA), front side |
4X |
Operation temperature |
0 - 50 °C |
Rail mounting possible |
No |
Wall mounting/direct mounting |
No |
Suitable for safety functions |
No |
Width of the front |
275 mm |
Height of the front |
208 mm |
Built-in depth |
47 mm |
Product Standards |
UL508, cULus; IEC/EN 61131-2, CE |
UL File No. |
E205091 |
UL Category Control No. |
NRAQ |
CSA File No. |
UL report applies to US and Canada |
CSA Class No. |
- |
North America Certification |
UL listed, certified by UL for use in Canada |
Current Limiting Circuit-Breaker |
No |
Degree of Protection |
IEC:IP20, UL/CSA Tape: open type |