alt
alt

UTI0,5-115
206926 UTI0,5-115
206926

Control transformer, 0.5 kVA, Rated input voltage 208 – 600 V, Rated output voltage 2 x 115 VControl transformer, Product range: Single-phase UTI multi-winding transformers, Rated input voltage: 208 – 600 V, Rated output voltage: 2 x 115 V, Rated power: 0.5 kVA, Degree of Protection: IP00, Standards Built and tested to: (universal) control, isolating and safety transformers to, VDE 0550, IEC/EN 61558-2-2/2-4/2-6, VDE 0570 Part 2-2/2-6 (safety transformer), VDE 0570 Part 2-4 (isolating transformer), Suitable for use to: IEC/EN 60204-1, ÖVE-EN 13, VDE 0113, VDE 0100 Part 410

Control transformer, 0.5 kVA, Rated input voltage 208 – 600 V, Rated output voltage 2 x 115 V
Control transformer, Product range: Single-phase UTI multi-winding transformers, Rated input voltage: 208 – 600 V, Rated output voltage: 2 x 115 V, Rated power: 0.5 kVA, Degree of Protection: IP00, Standards Built and tested to: (universal) control, isolating and safety transformers to, VDE 0550, IEC/EN 61558-2-2/2-4/2-6, VDE 0570 Part 2-2/2-6 (safety transformer), VDE 0570 Part 2-4 (isolating transformer), Suitable for use to: IEC/EN 60204-1, ÖVE-EN 13, VDE 0113, VDE 0100 Part 410

Product range Single-phase UTI multi-winding transformers
Rated input voltage 208 – 600 V
Rated output voltage 2 x 115 V
Rated power 0.5 kVA
Cu factor 1,30 kg
Notes

The transformers UTI are suitable for use in control circuits to IEC/EN 60204 or VDE 0113.

Transformer-protective circuit-breaker →#088907

Standards
>Built and tested to
(universal) control, isolating and safety transformers to
VDE 0550
IEC/EN 61558-2-2/2-4/2-6
VDE 0570 Part 2-2/2-6 (safety transformer)
VDE 0570 Part 2-4 (isolating transformer)
Standards
>Suitable for use to
IEC/EN 60204-1, ÖVE-EN 13
VDE 0113, VDE 0100 Part 410
Ambient temperature -25 - 40
Terminations
Insulation class B
Rated frequency 50 - 60 Hz
Primary tapping ± 20 %
Degree of Protection IP00
Separate windings
Fully vacuum-impregnated
Reinforced insulation
Rated duty factor 100 % DF
Note The following applies for the no-load loss, short-circuit loss (copper losses), short-circuit voltage and efficiency values: all details relate to a temperature of 20 °C
Total weight 6.8 kg
No-load losses 26 W
Short-circuit losses 23 W
Shortcircuit voltage 3.5 %
Efficiency 0.918
Rated operational current for specified heat dissipation [In] 0 A
Heat dissipation per pole, current-dependent [Pvid] 0 W
Equipment heat dissipation, current-dependent [Pvid] 0 W
Static heat dissipation, non-current-dependent [Pvs] 49 W
Heat dissipation capacity [Pdiss] 0 W
Operating ambient temperature min. -25 °C
Operating ambient temperature max. +40 °C
10.2 Strength of materials and parts
>10.2.2 Corrosion resistance
Meets the product standard´s requirements.
10.2 Strength of materials and parts
>10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard´s requirements.
10.2 Strength of materials and parts
>10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard´s requirements.
10.2 Strength of materials and parts
>10.2.3.3 Verification of resistance of insulating materials to abnormal heat and fire due to internal electric effects
Meets the product standard´s requirements.
10.2 Strength of materials and parts
>10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard´s requirements.
10.2 Strength of materials and parts
>10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
10.2 Strength of materials and parts
>10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2 Strength of materials and parts
>10.2.7 Inscriptions
Meets the product standard´s requirements.
10.3 Degree of protection of ASSEMBLIES Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances Meets the product standard´s requirements.
10.5 Protection against electric shock Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections Is the panel builder´s responsibility.
10.8 Connections for external conductors Is the panel builder´s responsibility.
10.9 Insulation properties
>10.9.2 Power-frequency electric strength
Is the panel builder´s responsibility.
10.9 Insulation properties
>10.9.3 Impulse withstand voltage
Is the panel builder´s responsibility.
10.9 Insulation properties
>10.9.4 Testing of enclosures made of insulating material
Is the panel builder´s responsibility.
10.10 Temperature rise The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating Is the panel builder´s responsibility. The specifications for the switchgear must be observed.
10.12 Electromagnetic compatibility Is the panel builder´s responsibility. The specifications for the switchgear must be observed.
10.13 Mechanical function The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
Built as safety transformer Yes
Built as isolating transformer Yes
Built as energy saving transformer No
Primary voltage 1 208 - 600 V
Primary voltage 2 0 - 0 V
Primary voltage 3 0 - 0 V
Primary voltage 4 0 - 0 V
Primary voltage 5 0 - 0 V
Primary voltage 6 0 - 0 V
Primary voltage 7 0 - 0 V
Primary voltage 8 0 - 0 V
Primary voltage 9 0 - 0 V
Primary voltage 10 0 - 0 V
Secondary voltage 1 115 - 115 V
Secondary voltage 2 115 - 115 V
Secondary voltage 3 0 - 0 V
Secondary voltage 4 0 - 0 V
Secondary voltage 5 0 - 0 V
Secondary voltage 6 0 - 0 V
Secondary voltage 7 0 - 0 V
Secondary voltage 8 0 - 0 V
Secondary voltage 9 0 - 0 V
Secondary voltage 10 0 - 0 V
Rated apparent power 500 VA
Type of insulation material acc. IEC 85 B
Short-circuit-proof No
Relative short circuit voltage 3.5 %
Width 121 mm
Height 133 mm
Depth 120 mm
Degree of protection (IP) IP00
Ring core No
Suitable for mounting on PCB No
Modular version No
Conductor material Copper
Product Standards UL 506; UL5085-1; UL 5085-2; CSA-C22.2 No. 66; CSA-C22.2 No. 66.1-06; CSA-C22.2 No. 66.2-06; IEC/EN 61558-2-2; CE marking
UL File No. E167225
UL Category Control No. XPTQ2, XPTQ8
CSA File No. UL report applies to both US and Canada
CSA Class No.
North America Certification UL recognized, certified by UL for use in Canada
Specially designed for North America No
Suitable for Branch circuits
Max. Voltage Rating 600 V AC
Degree of Protection IEC: IP00, UL/CSA Type: -

As Mnelko, we are a reliable partner in industrial automation solutions, offering high-quality and innovative products with a wide product range to meet all the needs of your business. Our product portfolio consists of solutions designed based on the principles of high performance, durability, and efficiency to support modern industrial processes.
All of our products ensure maximum reliability even in challenging working conditions and help your business operations run smoothly. The products we offer in industrial automation, energy management, cabling solutions, and many other areas adapt flexibly to the needs of different sectors.
Additionally, our products are manufactured using only high-quality materials and comply with international standards. Through the solutions we provide, we enable our customers to increase operational efficiency and optimize costs. Our company closely follows technological advancements and continuously offers innovative products to help our customers gain a competitive advantage.
On each of our product pages, you can find comprehensive information about technical details, areas of use, and product features. You can explore all the products you need to strengthen your industrial processes on our website and enjoy a seamless purchasing experience.

Similar Products

STN0,2(230/230)
Eaton
STN0,16(230/230)
Eaton
STN0,06(230/230)
Eaton
DTZ12,5(*/*)*
Eaton
DTZ8,0(*/*)*
Eaton