RCD/MCB, 32A, 100mA, miniature circuit-breaker trip curve C, 3 p, residual current circuit-breaker trip characteristic: ARCBO (residual-current circuit breaker with overload protection) PKPM3, 3 pole, Tripping characteristic: C, Rated current In: 32 A, Rated switching capacity according to IEC/EN 61009: 10 kA, Rated fault current IΔN: 0.1 A, Pulse-current sensitive, Partly surge-proof 250 A, Switchgear for residential and commercial applications
RCD/MCB, 32A, 100mA, miniature circuit-breaker trip curve C, 3 p, residual current circuit-breaker trip characteristic: A
RCBO (residual-current circuit breaker with overload protection) PKPM3, 3 pole, Tripping characteristic: C, Rated current In: 32 A, Rated switching capacity according to IEC/EN 61009: 10 kA, Rated fault current IΔN: 0.1 A, Pulse-current sensitive, Partly surge-proof 250 A, Switchgear for residential and commercial applications
Basic function | Combined RCD/MCB devices |
Number of poles | 3 pole |
Tripping characteristic | C |
Application | Switchgear for residential and commercial applications |
Rated current [In] | 32 A |
Rated switching capacity according to IEC/EN 61009 | 10 kA |
Rated fault current [IΔN] | 0.1 A |
Type | Type A |
Tripping | non-delayed s… |
Product range | PKPM3 |
Sensitivity | Pulse-current sensitive |
Impulse withstand current | Partly surge-proof 250 A |
Types conform to | IEC/EN 61009 |
Current test marks | As per inscription |
Tripping | non-delayed s… |
Rated frequency [f] | 50 Hz |
Rated fault currents [IΔn ] | 30, 100 mA |
Rated non-tripping current [IΔno] | 0.5 |
Sensitivity | Pulse-current sensitive |
Rated impulse withstand voltage [Uimp] | 4 (1.2/50μs) kV |
Max. admissible back-up fuse >Short-circuit [gG/gL] |
100 A |
Characteristic | C |
Selectivity Class | 3 |
lifespan >Electrical [Operations] |
≧ 2000 |
lifespan >Mechanical [Operations] |
≧ 10000 |
Standard front dimension | 45 mm |
Device height | 80 mm |
Built-in width | 70 (4TE) mm |
Mounting | Tristable slide catch enables removal from existing combination. |
Degree of Protection | IP20, IP40 (when fitted) |
Terminals top and bottom | Twin-purpose terminals |
Terminal protection | finger and hand touch safe, DGUV VS3, EN 50274 |
Terminal capacity | rigid conductors 1 x (1 - 25) mm2 |
Tightening torque of fixing screws | 2 - 2.4 N/m |
Thickness of busbar material | 0.8 - 2 mm |
Admissible ambient temperature range | -25 - +40 °C |
Permissible storage and transport temperatures | -35 - +60 °C |
Climatic proofing | in accordance with IEC/EN 61009 |
Rated operational current for specified heat dissipation [In] | 32 A |
Heat dissipation per pole, current-dependent [Pvid] | 0 W |
Equipment heat dissipation, current-dependent [Pvid] | 12.8 W |
Static heat dissipation, non-current-dependent [Pvs] | 0 W |
Heat dissipation capacity [Pdiss] | 0 W |
Operating ambient temperature min. | -25 °C |
Operating ambient temperature max. | +40 °C |
10.2 Strength of materials and parts >10.2.2 Corrosion resistance |
0 |
10.2 Strength of materials and parts >10.2.3.1 Verification of thermal stability of enclosures |
Meets the product standard´s requirements. |
10.2 Strength of materials and parts >10.2.3.2 Verification of resistance of insulating materials to normal heat |
Meets the product standard´s requirements. |
10.2 Strength of materials and parts >10.2.3.3 Verification of resistance of insulating materials to abnormal heat and fire due to internal electric effects |
Meets the product standard´s requirements. |
10.2 Strength of materials and parts >10.2.4 Resistance to ultra-violet (UV) radiation |
Meets the product standard´s requirements. |
10.2 Strength of materials and parts >10.2.5 Lifting |
Meets the product standard´s requirements. |
10.2 Strength of materials and parts >10.2.6 Mechanical impact |
Does not apply, since the entire switchgear needs to be evaluated. |
10.2 Strength of materials and parts >10.2.7 Inscriptions |
Does not apply, since the entire switchgear needs to be evaluated. |
10.3 Degree of protection of ASSEMBLIES | Meets the product standard´s requirements. |
10.4 Clearances and creepage distances | Does not apply, since the entire switchgear needs to be evaluated. |
10.5 Protection against electric shock | Meets the product standard´s requirements. |
10.6 Incorporation of switching devices and components | Does not apply, since the entire switchgear needs to be evaluated. |
10.7 Internal electrical circuits and connections | Does not apply, since the entire switchgear needs to be evaluated. |
10.8 Connections for external conductors | Is the panel builder´s responsibility. |
10.9 Insulation properties >10.9.2 Power-frequency electric strength |
Is the panel builder´s responsibility. |
10.9 Insulation properties >10.9.3 Impulse withstand voltage |
Is the panel builder´s responsibility. |
10.9 Insulation properties >10.9.4 Testing of enclosures made of insulating material |
Is the panel builder´s responsibility. |
10.10 Temperature rise | Is the panel builder´s responsibility. |
10.11 Short-circuit rating | The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices. |
10.12 Electromagnetic compatibility | Is the panel builder´s responsibility. The specifications for the switchgear must be observed. |
10.13 Mechanical function | Is the panel builder´s responsibility. The specifications for the switchgear must be observed. |
Number of poles (total) | The device meets the requirements, provided the information in the instruction leaflet (IL) is observed. |
Number of protected poles | 3 |
Rated voltage | 3 |
Rated insulation voltage Ui | 400 V |
Rated impulse withstand voltage Uimp | 500 V |
Rated current | 4 kV |
Rated fault current | 32 A |
Leakage current type | 0.1 A |
Current limiting class | A |
Rated short-circuit breaking capacity acc. EN 61009 | 3 |
Rated short-circuit breaking capacity IEC 60947-2 | 10 kA |
Rated short-circuit breaking capacity Icn acc. EN 61009-1 | 0 kA |
Disconnection characteristic | 10 kA |
Surge current capacity | |
Voltage type | 0.25 kA |
Frequency | AC |
Release characteristic | 50 Hz |
Concurrently switching N-neutral | C |
With interlocking device | Yes |
Over voltage category | No |
Pollution degree | 3 |
Ambient temperature during operating | 2 |
Width in number of modular spacings | -25 - 40 °C |
Built-in depth | 4 |
Suitable for flush-mounted installation | 70 mm |
Anti-nuisance tripping version | No |
Degree of protection (IP) | No |
Connectable conductor cross section solid-core | IP20 |
Connectable conductor cross section multi-wired | 1 - 25 mm² |
As Mnelko, we are a reliable partner in industrial automation solutions, offering high-quality and innovative products with a wide product range to meet all the needs of your business. Our product portfolio consists of solutions designed based on the principles of high performance, durability, and efficiency to support modern industrial processes.
All of our products ensure maximum reliability even in challenging working conditions and help your business operations run smoothly. The products we offer in industrial automation, energy management, cabling solutions, and many other areas adapt flexibly to the needs of different sectors.
Additionally, our products are manufactured using only high-quality materials and comply with international standards. Through the solutions we provide, we enable our customers to increase operational efficiency and optimize costs. Our company closely follows technological advancements and continuously offers innovative products to help our customers gain a competitive advantage.
On each of our product pages, you can find comprehensive information about technical details, areas of use, and product features. You can explore all the products you need to strengthen your industrial processes on our website and enjoy a seamless purchasing experience.