alt
alt

RCD/MCB, 6A, 30mA, miniature circuit-breaker trip curve: C, 1pole+N, residual current circuit-breaker trip characteristic: AFI/LS combination switch, HNB, 1-pole+N, rated current in: 6A, rated fault current IΔN: 0.03 A, rated breaking capacity in accordance with IEC/EN 61009: 6 kA, switching devices for residential and non-residential buildings

RCD/MCB, 6A, 30mA, miniature circuit-breaker trip curve: C, 1pole+N, residual current circuit-breaker trip characteristic: A
FI/LS combination switch, HNB, 1-pole+N, rated current in: 6A, rated fault current IΔN: 0.03 A, rated breaking capacity in accordance with IEC/EN 61009: 6 kA, switching devices for residential and non-residential buildings

Basic function Combined RCD/MCB devices
Number of poles 1 pole+N
Tripping characteristic C
Rated current [In] 6 A
Rated switching capacity according to IEC/EN 61009 6 kA
Rated fault current [IΔN] 0.03 A
Type Type A
Product range HNB-HX
Impulse withstand current Partly surge-proof 250 A
Rated operational current for specified heat dissipation [In] 6 A
Equipment heat dissipation, current-dependent [Pvid] 1.7 W
Operating ambient temperature min. -25 °C
Operating ambient temperature max. +40 °C
10.2 Strength of materials and parts
>10.2.2 Corrosion resistance
Meets the product standard´s requirements.
10.2 Strength of materials and parts
>10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard´s requirements.
10.2 Strength of materials and parts
>10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard´s requirements.
10.2 Strength of materials and parts
>10.2.3.3 Verification of resistance of insulating materials to abnormal heat and fire due to internal electric effects
Meets the product standard´s requirements.
10.2 Strength of materials and parts
>10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard´s requirements.
10.2 Strength of materials and parts
>10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
10.2 Strength of materials and parts
>10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2 Strength of materials and parts
>10.2.7 Inscriptions
Meets the product standard´s requirements.
10.3 Degree of protection of ASSEMBLIES Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances Meets the product standard´s requirements.
10.5 Protection against electric shock Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections Is the panel builder´s responsibility.
10.8 Connections for external conductors Is the panel builder´s responsibility.
10.9 Insulation properties
>10.9.2 Power-frequency electric strength
Is the panel builder´s responsibility.
10.9 Insulation properties
>10.9.3 Impulse withstand voltage
Is the panel builder´s responsibility.
10.9 Insulation properties
>10.9.4 Testing of enclosures made of insulating material
Is the panel builder´s responsibility.
10.10 Temperature rise The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating Is the panel builder´s responsibility. The specifications for the switchgear must be observed.
10.12 Electromagnetic compatibility Is the panel builder´s responsibility. The specifications for the switchgear must be observed.
10.13 Mechanical function The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
Number of poles (total) 2
Number of protected poles 1
Rated voltage 230 V
Rated insulation voltage Ui 500 V
Rated impulse withstand voltage Uimp 4 kV
Rated current 6 A
Rated fault current 0.03 A
Leakage current type A
Current limiting class 3
Rated short-circuit breaking capacity acc. EN 61009 6 kA
Rated short-circuit breaking capacity IEC 60947-2 0 kA
Rated short-circuit breaking capacity Icn acc. EN 61009-1 6 kA
Disconnection characteristic
Surge current capacity 0.25 kA
Voltage type AC
Frequency 50 Hz
Release characteristic C
Concurrently switching N-neutral Yes
With interlocking device No
Over voltage category 3
Pollution degree 2
Ambient temperature during operating -25 - 40 °C
Width in number of modular spacings 2
Built-in depth 69.5 mm
Suitable for flush-mounted installation No
Anti-nuisance tripping version No
Degree of protection (IP) IP20
Connectable conductor cross section solid-core 1 - 25 mm²
Connectable conductor cross section multi-wired 1 - 25 mm²

As Mnelko, we are a reliable partner in industrial automation solutions, offering high-quality and innovative products with a wide product range to meet all the needs of your business. Our product portfolio consists of solutions designed based on the principles of high performance, durability, and efficiency to support modern industrial processes.
All of our products ensure maximum reliability even in challenging working conditions and help your business operations run smoothly. The products we offer in industrial automation, energy management, cabling solutions, and many other areas adapt flexibly to the needs of different sectors.
Additionally, our products are manufactured using only high-quality materials and comply with international standards. Through the solutions we provide, we enable our customers to increase operational efficiency and optimize costs. Our company closely follows technological advancements and continuously offers innovative products to help our customers gain a competitive advantage.
On each of our product pages, you can find comprehensive information about technical details, areas of use, and product features. You can explore all the products you need to strengthen your industrial processes on our website and enjoy a seamless purchasing experience.

Similar Products

PKNM-32/1N/C/003-F-MW
Eaton
HNB-C20/1N/003-A-HX
Eaton
HNB-C6/1N/003-A-HX
Eaton
HNB-C6/1N/003-HX
Eaton
HNB-B16/1N/003-A
Eaton