alt
alt

Residual current circuit breaker (RCCB), 80A, 4pole, 30mA, type ACResidual current circuit-breaker PFGM, 4 pole, Rated current In: 80 A, Rated short-circuit strength Icn: 10 kA, Rated fault current IΔN: 0.03 A, Switchgear for residential and commercial applications

Residual current circuit breaker (RCCB), 80A, 4pole, 30mA, type AC
Residual current circuit-breaker PFGM, 4 pole, Rated current In: 80 A, Rated short-circuit strength Icn: 10 kA, Rated fault current IΔN: 0.03 A, Switchgear for residential and commercial applications

Basic function Residual current circuit-breakers
Number of poles 4 pole
Application Residual current circuit-breaker for residential and commercial applications
Rated current [In] 80 A
Rated short-circuit strength [Icn] 10 kA
Rated fault current [IΔN] 0.03 A
Type Type AC
Tripping non-delayed s…
Product range PFGM
Sensitivity AC current sensitive
Impulse withstand current Partly surge-proof 250 A
Standards IEC/EN 61008
Rated operational voltage [Ue] [Ue]Rated operating voltage [Ue] 230/400 V AC
Rated frequency [f] 50 Hz
Limit values of the operating voltage
>Test circuit
340 - 456 V AC
Limit values of the operating voltage
>Comment for range of the test button
3-phase application without N (400V AC Phase-Phase) not allowed
Sensitivity AC current sensitive
Rated insulation voltage [Ui ] 440 V
Rated impulse withstand voltage [Uimp] 4 kV
Rated short-circuit strength [Icn] 10 kA
Rated making and breaking capacity / Rated residual making and breaking capacity [Im / IΔm] 630 A
lifespan
>Electrical [Operations]
≧ 4000
lifespan
>Mechanical [Operations]
≧ 20000
Auxiliary switch for subsequent installation Z-HK 248432
Tripping signal contact for subsequent installation Z-NHK 248434
Remote control and automatic switching device Z-FW/LP 248296
Compact enclosure KLV-TC-4 276241
Switching interlock IS/SPE-1TE 101911
Sealing cover set Z-RC/AK-4TE 101062
Standard front dimension 45 mm
Device height 80 mm
Built-in width 70 (4TE) mm
Mounting Quick attachment with 2 latch positions for DIN-rail IEC/EN 60715
Degree of Protection IP40, IP54 (with moisture-proof enclosure)
Terminals top and bottom Open mouthed/lift terminals
Terminal protection BGV A3, ÖVE-EN 6
Terminal cross-section
>Solid
1.5 - 35 mm2
Terminal cross-section
>Stranded
2 x 16 mm2
Thickness of busbar material 0.8 - 2 mm
Permissible storage and transport temperatures -35 - +60 °C
Climatic proofing 25-55°C/90-95% relative humidity according to IEC 60068-2
Thickness of busbar material
>Material thickness
0.8 - 2 mm
Rated operational current for specified heat dissipation [In] 80 A
Heat dissipation per pole, current-dependent [Pvid] 0 W
Equipment heat dissipation, current-dependent [Pvid] 11.4 W
Static heat dissipation, non-current-dependent [Pvs] 0 W
Heat dissipation capacity [Pdiss] 0 W
Operating ambient temperature min. -25 °C
Operating ambient temperature max. +60 °C
10.2 Strength of materials and parts
>10.2.2 Corrosion resistance
Starting at 40 °C, the max. permissible continuous current decreases by 1.2% for every 1 °C
10.2 Strength of materials and parts
>10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard´s requirements.
10.2 Strength of materials and parts
>10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard´s requirements.
10.2 Strength of materials and parts
>10.2.3.3 Verification of resistance of insulating materials to abnormal heat and fire due to internal electric effects
Meets the product standard´s requirements.
10.2 Strength of materials and parts
>10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard´s requirements.
10.2 Strength of materials and parts
>10.2.5 Lifting
Meets the product standard´s requirements.
10.2 Strength of materials and parts
>10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2 Strength of materials and parts
>10.2.7 Inscriptions
Does not apply, since the entire switchgear needs to be evaluated.
10.3 Degree of protection of ASSEMBLIES Meets the product standard´s requirements.
10.4 Clearances and creepage distances Does not apply, since the entire switchgear needs to be evaluated.
10.5 Protection against electric shock Meets the product standard´s requirements.
10.6 Incorporation of switching devices and components Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections Does not apply, since the entire switchgear needs to be evaluated.
10.8 Connections for external conductors Is the panel builder´s responsibility.
10.9 Insulation properties
>10.9.2 Power-frequency electric strength
Is the panel builder´s responsibility.
10.9 Insulation properties
>10.9.3 Impulse withstand voltage
Is the panel builder´s responsibility.
10.9 Insulation properties
>10.9.4 Testing of enclosures made of insulating material
Is the panel builder´s responsibility.
10.10 Temperature rise Is the panel builder´s responsibility.
10.11 Short-circuit rating The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.12 Electromagnetic compatibility Is the panel builder´s responsibility. The specifications for the switchgear must be observed.
10.13 Mechanical function Is the panel builder´s responsibility. The specifications for the switchgear must be observed.
Number of poles The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
Rated voltage 4
Rated current 400 V
Rated fault current 80 A
Rated insulation voltage Ui 30 mA
Rated impulse withstand voltage Uimp 440 V
Mounting method 4 kV
Leakage current type DIN rail
Selective protection AC
Short-time delayed tripping No
Short-circuit breaking capacity (Icw) No
Surge current capacity 10 kA
Frequency 0.25 kA
Additional equipment possible 50 Hz
With interlocking device Yes
Degree of protection (IP) Yes
Width in number of modular spacings IP20
Built-in depth 4
Ambient temperature during operating 69.5 mm
Pollution degree -25 - 40 °C
Connectable conductor cross section multi-wired 2
Connectable conductor cross section solid-core 1.5 - 16 mm²

As Mnelko, we are a reliable partner in industrial automation solutions, offering high-quality and innovative products with a wide product range to meet all the needs of your business. Our product portfolio consists of solutions designed based on the principles of high performance, durability, and efficiency to support modern industrial processes.
All of our products ensure maximum reliability even in challenging working conditions and help your business operations run smoothly. The products we offer in industrial automation, energy management, cabling solutions, and many other areas adapt flexibly to the needs of different sectors.
Additionally, our products are manufactured using only high-quality materials and comply with international standards. Through the solutions we provide, we enable our customers to increase operational efficiency and optimize costs. Our company closely follows technological advancements and continuously offers innovative products to help our customers gain a competitive advantage.
On each of our product pages, you can find comprehensive information about technical details, areas of use, and product features. You can explore all the products you need to strengthen your industrial processes on our website and enjoy a seamless purchasing experience.

Similar Products

PKNM-32/1N/C/003-F-MW
Eaton
HNB-C20/1N/003-A-HX
Eaton
HNB-C6/1N/003-A-HX
Eaton
HNB-C6/1N/003-HX
Eaton
HNB-B16/1N/003-A
Eaton