alt
alt

+IP23/32A
200763 +IP23/32A
200763

IP23 enclosures, For use with STZ2.5 … STZ4.0, DTZ1.0 … DTZ2.0IP23 enclosure for STZ2.5 to STZ4.0 and DTZ1.0 to DTZ2.0, enclosure can be used with primary or secondary voltage of 42 V to max, 1000 V including tapping

IP23 enclosures, For use with STZ2.5 … STZ4.0, DTZ1.0 … DTZ2.0
IP23 enclosure for STZ2.5 to STZ4.0 and DTZ1.0 to DTZ2.0, enclosure can be used with primary or secondary voltage of 42 V to max, 1000 V including tapping

Product range Accessories
Accessories IP23 enclosures
For use with STZ2.5 … STZ4.0
DTZ1.0 … DTZ2.0
Cu factor 0,00 kg
Notes

For the version with enhanced climatic proofing the transformer features a special insulating varnish. This version enables the transformer to be used in areas with a high humidity.

When ordering, the type reference must include the following details:

ETSP25(*/*)

1st wildcard ≙ Nominal input voltage

2nd wildcard ≙ Rated output voltage

Ordering example

  • Required throughput rating 55 kVA
  • Desired rated input voltage 400 V
  • Desired rated output voltage 230 V

Selection notes

SN = S x (1 - Lower voltage ⁄ Higher voltage)

= 55 kVA x (1 - 230V/400V = 23.4 kVA

SN = kVA type rating

S = Throughput rating

  • The kVA type rating is always lower than the throughput rating.
  • For version with delta stabilizing winding, please enquire.

The correct type reference is

ETSP25(400/230)

Transformer-protective circuit-breaker → 088907

Ambient temperature -25 - 40
Operating ambient temperature min. -25 °C
Operating ambient temperature max. +40 °C
10.2 Strength of materials and parts
>10.2.2 Corrosion resistance
Meets the product standard´s requirements.
10.2 Strength of materials and parts
>10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard´s requirements.
10.2 Strength of materials and parts
>10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard´s requirements.
10.2 Strength of materials and parts
>10.2.3.3 Verification of resistance of insulating materials to abnormal heat and fire due to internal electric effects
Meets the product standard´s requirements.
10.2 Strength of materials and parts
>10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard´s requirements.
10.2 Strength of materials and parts
>10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
10.2 Strength of materials and parts
>10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2 Strength of materials and parts
>10.2.7 Inscriptions
Meets the product standard´s requirements.
10.3 Degree of protection of ASSEMBLIES Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances Meets the product standard´s requirements.
10.5 Protection against electric shock Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections Is the panel builder´s responsibility.
10.8 Connections for external conductors Is the panel builder´s responsibility.
10.9 Insulation properties
>10.9.2 Power-frequency electric strength
Is the panel builder´s responsibility.
10.9 Insulation properties
>10.9.3 Impulse withstand voltage
Is the panel builder´s responsibility.
10.9 Insulation properties
>10.9.4 Testing of enclosures made of insulating material
Is the panel builder´s responsibility.
10.10 Temperature rise The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating Is the panel builder´s responsibility. The specifications for the switchgear must be observed.
10.12 Electromagnetic compatibility Is the panel builder´s responsibility. The specifications for the switchgear must be observed.
10.13 Mechanical function The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
Material housing Steel
Width 360 mm
Height 263 mm
Depth 315 mm
With transparent cover No
Suitable for emergency stop No
Model Built-in
Degree of protection (IP) IP23
Degree of protection (NEMA) Other

As Mnelko, we are a reliable partner in industrial automation solutions, offering high-quality and innovative products with a wide product range to meet all the needs of your business. Our product portfolio consists of solutions designed based on the principles of high performance, durability, and efficiency to support modern industrial processes.
All of our products ensure maximum reliability even in challenging working conditions and help your business operations run smoothly. The products we offer in industrial automation, energy management, cabling solutions, and many other areas adapt flexibly to the needs of different sectors.
Additionally, our products are manufactured using only high-quality materials and comply with international standards. Through the solutions we provide, we enable our customers to increase operational efficiency and optimize costs. Our company closely follows technological advancements and continuously offers innovative products to help our customers gain a competitive advantage.
On each of our product pages, you can find comprehensive information about technical details, areas of use, and product features. You can explore all the products you need to strengthen your industrial processes on our website and enjoy a seamless purchasing experience.

Similar Products

STN0,2(230/230)
Eaton
STN0,16(230/230)
Eaton
STN0,06(230/230)
Eaton
DTZ12,5(*/*)*
Eaton
DTZ8,0(*/*)*
Eaton