Residual current circuit breaker (RCCB), 80A, 4p, 300mA, type A, 110VMains voltage-independent residual current circuit-breaker for fault protection and additional protection, 80A, 4p, 300 mA, type A, 110V
Residual current circuit breaker (RCCB), 80A, 4p, 300mA, type A, 110V
Mains voltage-independent residual current circuit-breaker for fault protection and additional protection, 80A, 4p, 300 mA, type A, 110V
Basic function | Residual current circuit-breakers |
Number of poles | 4 pole |
Application | Switchgear for industrial and advanced commercial applications |
Rated current [In] | 80 A |
Rated short-circuit strength [Icn] | 10 with back-up fuse kA |
Rated fault current [IΔN] | 0.3 A |
Type | Type A |
Tripping | non-delayed s… |
Product range | FRCmM |
Sensitivity | Pulse-current sensitive |
Impulse withstand current | Partly surge-proof 250 A |
Types conform to | IEC/EN 61008 |
Current test marks | As per inscription |
Tripping | non-delayed s… |
Rated voltage according to IEC/EN 60947-2 [Un] | 110/190 V AC |
Rated frequency [f] | 50/60 Hz |
Limit values of the operating voltage >Test circuit |
94 - 210 V AC |
Rated fault current [IΔn] | 300 mA |
Sensitivity | Pulse-current sensitive |
Rated insulation voltage [Ui ] | 440 V |
Rated impulse withstand voltage [Uimp] | 4 (1.2/50μs) kV |
Rated short-circuit strength [Icn] | 10 with back-up fuse kA |
Impulse withstand current | 250 A (8/20 μs) surge-proof |
Max. admissible back-up fuse >Short-circuit [gG/gL] |
80 A |
Max. admissible back-up fuse >Overload [gG/gL] |
80 A |
Rated making and breaking capacity / Rated residual making and breaking capacity [Im / IΔm] | 800 A |
lifespan >Electrical [Operations] |
≧ 4000 |
lifespan >Mechanical [Operations] |
≧ 20000 |
Standard front dimension | 45 mm |
Device height | 80 mm |
Built-in width | 70 (4TE) mm |
Mounting | Quick attachment with 2 latch positions for DIN-rail IEC/EN 60715 |
Degree of Protection | IP40, IP54 (with moisture-proof enclosure) |
Terminals top and bottom | Twin-purpose terminals |
Terminal protection | Busbar tag shroud to BGV A3, ÖVE-EN 6 |
Terminal cross-section >Solid |
1.5 - 35 mm2 |
Terminal cross-section >Stranded |
2 x 16 mm2 |
Terminal cross-section | M5 (with cross-recessed screw as defined in EN ISO 4757-Z2, Pozidriv PZ2) |
Tightening torque of fixing screws | 2 - 2.4 N/m |
Thickness of busbar material | 0.8 - 2 mm |
Admissible ambient temperature range | -25 - +40 °C |
Permissible storage and transport temperatures | -35 - +60 °C |
Climatic proofing | 25-55°C/90-95% relative humidity according to IEC 60068-2 |
Mounting position | As required |
Contact position indicator | red / green |
Trip indication | white / blue |
Rated operational current for specified heat dissipation [In] | 80 A |
Heat dissipation per pole, current-dependent [Pvid] | 2.85 W |
Equipment heat dissipation, current-dependent [Pvid] | 11.4 W |
Static heat dissipation, non-current-dependent [Pvs] | 0 W |
Heat dissipation capacity [Pdiss] | 0 W |
Operating ambient temperature min. | -25 °C |
Operating ambient temperature max. | +75 °C |
10.2 Strength of materials and parts >10.2.2 Corrosion resistance |
Starting at 40 °C, the max. permissible continuous current decreases by 1.2% for every 1 °C |
10.2 Strength of materials and parts >10.2.3.1 Verification of thermal stability of enclosures |
Meets the product standard´s requirements. |
10.2 Strength of materials and parts >10.2.3.2 Verification of resistance of insulating materials to normal heat |
Meets the product standard´s requirements. |
10.2 Strength of materials and parts >10.2.3.3 Verification of resistance of insulating materials to abnormal heat and fire due to internal electric effects |
Meets the product standard´s requirements. |
10.2 Strength of materials and parts >10.2.4 Resistance to ultra-violet (UV) radiation |
Meets the product standard´s requirements. |
10.2 Strength of materials and parts >10.2.5 Lifting |
Meets the product standard´s requirements. |
10.2 Strength of materials and parts >10.2.6 Mechanical impact |
Does not apply, since the entire switchgear needs to be evaluated. |
10.2 Strength of materials and parts >10.2.7 Inscriptions |
Does not apply, since the entire switchgear needs to be evaluated. |
10.3 Degree of protection of ASSEMBLIES | Meets the product standard´s requirements. |
10.4 Clearances and creepage distances | Does not apply, since the entire switchgear needs to be evaluated. |
10.5 Protection against electric shock | Meets the product standard´s requirements. |
10.6 Incorporation of switching devices and components | Does not apply, since the entire switchgear needs to be evaluated. |
10.7 Internal electrical circuits and connections | Does not apply, since the entire switchgear needs to be evaluated. |
10.8 Connections for external conductors | Is the panel builder´s responsibility. |
10.9 Insulation properties >10.9.2 Power-frequency electric strength |
Is the panel builder´s responsibility. |
10.9 Insulation properties >10.9.3 Impulse withstand voltage |
Is the panel builder´s responsibility. |
10.9 Insulation properties >10.9.4 Testing of enclosures made of insulating material |
Is the panel builder´s responsibility. |
10.10 Temperature rise | Is the panel builder´s responsibility. |
10.11 Short-circuit rating | The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices. |
10.12 Electromagnetic compatibility | Is the panel builder´s responsibility. The specifications for the switchgear must be observed. |
10.13 Mechanical function | Is the panel builder´s responsibility. The specifications for the switchgear must be observed. |
Number of poles | The device meets the requirements, provided the information in the instruction leaflet (IL) is observed. |
Rated voltage | 4 |
Rated current | 110 V |
Rated fault current | 80 A |
Rated insulation voltage Ui | 300 mA |
Rated impulse withstand voltage Uimp | 440 V |
Mounting method | 4 kV |
Leakage current type | DIN rail |
Selective protection | A |
Short-time delayed tripping | No |
Short-circuit breaking capacity (Icw) | No |
Surge current capacity | 10 kA |
Frequency | 0.25 kA |
Additional equipment possible | 50/60 Hz |
With interlocking device | Yes |
Degree of protection (IP) | Yes |
Width in number of modular spacings | IP20 |
Built-in depth | 4 |
Ambient temperature during operating | 70.5 mm |
Pollution degree | -25 - 40 °C |
Connectable conductor cross section multi-wired | 2 |
Connectable conductor cross section solid-core | 1.5 - 16 mm² |
As Mnelko, we are a reliable partner in industrial automation solutions, offering high-quality and innovative products with a wide product range to meet all the needs of your business. Our product portfolio consists of solutions designed based on the principles of high performance, durability, and efficiency to support modern industrial processes.
All of our products ensure maximum reliability even in challenging working conditions and help your business operations run smoothly. The products we offer in industrial automation, energy management, cabling solutions, and many other areas adapt flexibly to the needs of different sectors.
Additionally, our products are manufactured using only high-quality materials and comply with international standards. Through the solutions we provide, we enable our customers to increase operational efficiency and optimize costs. Our company closely follows technological advancements and continuously offers innovative products to help our customers gain a competitive advantage.
On each of our product pages, you can find comprehensive information about technical details, areas of use, and product features. You can explore all the products you need to strengthen your industrial processes on our website and enjoy a seamless purchasing experience.