alt
alt

Digital residual current circuit-breaker, 40A, 4p, 300mA, type G/BFQResidual current circuit-breaker FRCdM, 4 pole, Rated current In: 40 A, Rated short-circuit strength Icn: 10 with back-up fuse kA, Rated fault current IΔN: 0.3 A, Residual current circuit-breaker - frequency converter-proof

Digital residual current circuit-breaker, 40A, 4p, 300mA, type G/BFQ
Residual current circuit-breaker FRCdM, 4 pole, Rated current In: 40 A, Rated short-circuit strength Icn: 10 with back-up fuse kA, Rated fault current IΔN: 0.3 A, Residual current circuit-breaker - frequency converter-proof

Basic function Residual current circuit-breakers , digital
Number of poles 4 pole
Application Residual current circuit-breaker - frequency converter-proof
Rated current [In] 40 A
Rated short-circuit strength [Icn] 10 kA
Rated fault current [IΔN] 0.3 A
Type Type G/Bfq (ÖVE E 8601)
Tripping Short time-delayed s…
Product range FRCdM
Sensitivity All current sensitive - frequency converter-proof
Impulse withstand current Surge-proof, 3 kA
Contact sequence FRCdM_4p_TypB
Types conform to IEC/EN 61008
IEC/EN 62423
Current test marks As per inscription
Tripping 10 ms delayed s…
Rated voltage according to IEC/EN 60947-2 [Un] 240/415 V AC
Rated frequency [f] 50/60 Hz
Limit values of the operating voltage
>electronic
50 - 456 V AC
Limit values of the operating voltage
>Test circuit
184 - 440 V AC
Rated fault current [IΔn] 300 mA
Sensitivity All current sensitive - frequency converter-proof
Enhanced sensitivity Suitable for variable frequency drives
Rated insulation voltage [Ui ] 440 V
Rated impulse withstand voltage [Uimp] 4 kV
Rated short-circuit strength [Icn] 10 kA
Impulse withstand current 3 kA (8/20 μs) surge-proof
Max. admissible back-up fuse
>Short-circuit [gG/gL]
63 A
Max. admissible back-up fuse
>Overload [gG/gL]
63 A
Rated making and breaking capacity / Rated residual making and breaking capacity [Im / IΔm] 500 A
lifespan
>Electrical [Operations]
≧ 4000
lifespan
>Mechanical [Operations]
≧ 20000
Rated switching capacity
>30 VDC (resistive load)
2 A
Rated switching capacity
>240 VAC (resistive load)
0.25 A
Max. switching duty (resistive load) 60 W
Max. switching voltage AC 240 V
Max. switching voltage DC 220 V
Maximum switching current 2 A
Min. switching capacity (reference value) 10 μA, 10 mV DC
lifespan
>Electrical (at 20 switching operations per minute) 2 A 30 VDC resistive load
>105 Operations
lifespan
>Electrical (at 20 switching operations per minute) 1 A 30 VDC resistive load
>5 x 105 Operations
Terminal capacity 0.25 - 1.5 mm²
Standard front dimension 45 mm
Device height 80 mm
Built-in width 70 (4TE) mm
Mounting Quick attachment with 2 latch positions for DIN-rail IEC/EN 60715
Degree of Protection IP40, IP54 (with moisture-proof enclosure)
Terminals top and bottom Twin-purpose terminals
Terminal protection finger and hand touch safe, DGUV VS3, EN 50274
Terminal cross-section
>Solid
1.5 - 35 mm2
Terminal cross-section
>Stranded
2 x 16 mm2
Terminal cross-section M5 (with cross-recessed screw as defined in EN ISO 4757-Z2, Pozidriv PZ2)
Tightening torque of fixing screws 2 - 2.4 N/m
Thickness of busbar material 0.8 - 2 mm
Admissible ambient temperature range -25 - +50 °C
Permissible storage and transport temperatures -35 - +60 °C
Climatic proofing 25-55°C/90-95% relative humidity according to IEC 60068-2
Mounting position As required
Contact position indicator red / green
Trip indication white / blue
Rated operational current for specified heat dissipation [In] 40 A
Heat dissipation per pole, current-dependent [Pvid] 1.55 W
Equipment heat dissipation, current-dependent [Pvid] 6.2 W
Static heat dissipation, non-current-dependent [Pvs] 0 W
Heat dissipation capacity [Pdiss] 0 W
Operating ambient temperature min. -25 °C
Operating ambient temperature max. +60 °C
10.2 Strength of materials and parts
>10.2.2 Corrosion resistance
Maximum operating temperature is 60 °C in accordance with the de-rating table
10.2 Strength of materials and parts
>10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard´s requirements.
10.2 Strength of materials and parts
>10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard´s requirements.
10.2 Strength of materials and parts
>10.2.3.3 Verification of resistance of insulating materials to abnormal heat and fire due to internal electric effects
Meets the product standard´s requirements.
10.2 Strength of materials and parts
>10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard´s requirements.
10.2 Strength of materials and parts
>10.2.5 Lifting
Meets the product standard´s requirements.
10.2 Strength of materials and parts
>10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2 Strength of materials and parts
>10.2.7 Inscriptions
Does not apply, since the entire switchgear needs to be evaluated.
10.3 Degree of protection of ASSEMBLIES Meets the product standard´s requirements.
10.4 Clearances and creepage distances Does not apply, since the entire switchgear needs to be evaluated.
10.5 Protection against electric shock Meets the product standard´s requirements.
10.6 Incorporation of switching devices and components Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections Does not apply, since the entire switchgear needs to be evaluated.
10.8 Connections for external conductors Is the panel builder´s responsibility.
10.9 Insulation properties
>10.9.2 Power-frequency electric strength
Is the panel builder´s responsibility.
10.9 Insulation properties
>10.9.3 Impulse withstand voltage
Is the panel builder´s responsibility.
10.9 Insulation properties
>10.9.4 Testing of enclosures made of insulating material
Is the panel builder´s responsibility.
10.10 Temperature rise Is the panel builder´s responsibility.
10.11 Short-circuit rating The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.12 Electromagnetic compatibility Is the panel builder´s responsibility. The specifications for the switchgear must be observed.
10.13 Mechanical function Is the panel builder´s responsibility. The specifications for the switchgear must be observed.
Number of poles The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
Rated voltage 4
Rated current 415 V
Rated fault current 40 A
Rated insulation voltage Ui 300 mA
Rated impulse withstand voltage Uimp 440 V
Mounting method 4 kV
Leakage current type DIN rail
Selective protection B
Short-time delayed tripping No
Short-circuit breaking capacity (Icw) Yes
Surge current capacity 10 kA
Frequency 3 kA
Additional equipment possible 50/60 Hz
With interlocking device Yes
Degree of protection (IP) Yes
Width in number of modular spacings IP20
Built-in depth 4
Ambient temperature during operating 70.5 mm
Pollution degree -25 - 50 °C
Connectable conductor cross section multi-wired 2
Connectable conductor cross section solid-core 1.5 - 16 mm²
Characteristic curve 1.5 - 35 mm²
Characteristic curve KL_rccb_bfq300

As Mnelko, we are a reliable partner in industrial automation solutions, offering high-quality and innovative products with a wide product range to meet all the needs of your business. Our product portfolio consists of solutions designed based on the principles of high performance, durability, and efficiency to support modern industrial processes.
All of our products ensure maximum reliability even in challenging working conditions and help your business operations run smoothly. The products we offer in industrial automation, energy management, cabling solutions, and many other areas adapt flexibly to the needs of different sectors.
Additionally, our products are manufactured using only high-quality materials and comply with international standards. Through the solutions we provide, we enable our customers to increase operational efficiency and optimize costs. Our company closely follows technological advancements and continuously offers innovative products to help our customers gain a competitive advantage.
On each of our product pages, you can find comprehensive information about technical details, areas of use, and product features. You can explore all the products you need to strengthen your industrial processes on our website and enjoy a seamless purchasing experience.

Similar Products

PKNM-32/1N/C/003-F-MW
Eaton
HNB-C20/1N/003-A-HX
Eaton
HNB-C6/1N/003-A-HX
Eaton
HNB-C6/1N/003-HX
Eaton
HNB-B16/1N/003-A
Eaton