Miniature circuit breaker (MCB), 13A, 2p, C-Char, ACMiniature circuit breaker (MCB) FAZ-T, 2 pole, Tripping characteristic: C, Rated current In: 13 A, Switchgear for industrial and advanced commercial applications
Miniature circuit breaker (MCB), 13A, 2p, C-Char, AC
Miniature circuit breaker (MCB) FAZ-T, 2 pole, Tripping characteristic: C, Rated current In: 13 A, Switchgear for industrial and advanced commercial applications
Basic function | Miniature circuit-breakers |
Number of poles | 2 pole |
Tripping characteristic | C |
Application | Switchgear for industrial and advanced commercial applications |
Rated current [In] | 13 A |
Rated switching capacity acc. to IEC/EN 60947-2 [Icu] | 25 kA |
Product range | FAZ-T |
Standards | IEC/EN 60947-2 |
Rated voltage according to IEC/EN 60947-2 [Un] | 415 V AC |
Rated switching capacity acc. to IEC/EN 60947-2 [Icu] | 25 kA |
Rated service short-circuit breaking capacity according to IEC/EN 60947-2 [Ics] | 12,5 kA |
Max operational voltage according to IEC/EN 60947-2 | 440 V AC |
Rated switching capacity according to IEC/EN 60947-2 (max operational voltage) [Icu] | 15 kA |
Rated service short-circuit breaking capacity according to IEC/EN 60947-2 (max operational voltage) [Ics] | 7,5 kA |
Max operational voltage DC according to IEC/EN 60947-2 | 60/pole V DC |
Rated voltage according to IEC/EN 60898-1 [Un] | 415 V AC |
Rated switching capacity according to IEC/EN 60898-1 [Icn] | 15 kA |
Rated service short-circuit breaking capacity according to IEC/EN 60898-1 [Ics] | 7,5 kA |
Rated insulation voltage [Ui ] | 440 V |
Rated frequency [f] | 50/60 Hz |
Characteristic | B, C, D |
Direction of incoming supply | as required |
lifespan >Electrical [Operations] |
≧ 4000 |
lifespan >Mechanical [Operations] |
≧ 10000 |
Standard front dimension | 45 mm |
Enclosure height | 80 mm |
Mounting width per pole | 17.5 mm |
Mounting | Quick attachment with 3 latch positions for top-hat rail IEC/EN 60715 |
Degree of Protection | IP20 |
Terminals top and bottom | Twin-purpose terminals |
Terminal protection | Finger- and back-of-hand proof according to BGV A3 and ÖVE-EN 6 |
Terminal capacities | 1 - 25 mm2 |
Tightening torque of fixing screws | max. 2.4 N/m |
Thickness of busbar material | 0.8 (exept N 0.5 SU) mm |
Mounting position | As required |
Rated operational current for specified heat dissipation [In] | 13 A |
Heat dissipation per pole, current-dependent [Pvid] | 0 W |
Equipment heat dissipation, current-dependent [Pvid] | 5.3 W |
Static heat dissipation, non-current-dependent [Pvs] | 0 W |
Heat dissipation capacity [Pdiss] | 0 W |
Operating ambient temperature min. | -40 °C |
Operating ambient temperature max. | +75 °C |
10.2 Strength of materials and parts >10.2.2 Corrosion resistance |
linear, per +1 °C, results in a 0.5% reduction of current carrying capacity |
10.2 Strength of materials and parts >10.2.3.1 Verification of thermal stability of enclosures |
Meets the product standard´s requirements. |
10.2 Strength of materials and parts >10.2.3.2 Verification of resistance of insulating materials to normal heat |
Meets the product standard´s requirements. |
10.2 Strength of materials and parts >10.2.3.3 Verification of resistance of insulating materials to abnormal heat and fire due to internal electric effects |
Meets the product standard´s requirements. |
10.2 Strength of materials and parts >10.2.4 Resistance to ultra-violet (UV) radiation |
Meets the product standard´s requirements. |
10.2 Strength of materials and parts >10.2.5 Lifting |
Meets the product standard´s requirements. |
10.2 Strength of materials and parts >10.2.6 Mechanical impact |
Does not apply, since the entire switchgear needs to be evaluated. |
10.2 Strength of materials and parts >10.2.7 Inscriptions |
Does not apply, since the entire switchgear needs to be evaluated. |
10.3 Degree of protection of ASSEMBLIES | Meets the product standard´s requirements. |
10.4 Clearances and creepage distances | Does not apply, since the entire switchgear needs to be evaluated. |
10.5 Protection against electric shock | Meets the product standard´s requirements. |
10.6 Incorporation of switching devices and components | Does not apply, since the entire switchgear needs to be evaluated. |
10.7 Internal electrical circuits and connections | Does not apply, since the entire switchgear needs to be evaluated. |
10.8 Connections for external conductors | Is the panel builder´s responsibility. |
10.9 Insulation properties >10.9.2 Power-frequency electric strength |
Is the panel builder´s responsibility. |
10.9 Insulation properties >10.9.3 Impulse withstand voltage |
Is the panel builder´s responsibility. |
10.9 Insulation properties >10.9.4 Testing of enclosures made of insulating material |
Is the panel builder´s responsibility. |
10.10 Temperature rise | Is the panel builder´s responsibility. |
10.11 Short-circuit rating | The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices. |
10.12 Electromagnetic compatibility | Is the panel builder´s responsibility. The specifications for the switchgear must be observed. |
10.13 Mechanical function | Is the panel builder´s responsibility. The specifications for the switchgear must be observed. |
Release characteristic | The device meets the requirements, provided the information in the instruction leaflet (IL) is observed. |
Number of poles (total) | C |
Number of protected poles | 2 |
Rated current | 2 |
Rated voltage | 13 A |
Rated insulation voltage Ui | 230 V |
Rated impulse withstand voltage Uimp | 440 V |
Rated short-circuit breaking capacity Icn EN 60898 at 230 V | 4 kV |
Rated short-circuit breaking capacity Icn EN 60898 at 400 V | 15 kA |
Rated short-circuit breaking capacity Icu IEC 60947-2 at 230 V | 15 kA |
Rated short-circuit breaking capacity Icu IEC 60947-2 at 400 V | 25 kA |
Voltage type | 25 kA |
Frequency | AC |
Current limiting class | 50 - 60 Hz |
Suitable for flush-mounted installation | 3 |
Concurrently switching N-neutral | No |
Over voltage category | No |
Pollution degree | 3 |
Additional equipment possible | 2 |
Width in number of modular spacings | Yes |
Built-in depth | 2 |
Degree of protection (IP) | 70.5 mm |
Ambient temperature during operating | IP20 |
Connectable conductor cross section multi-wired | -25 - 75 °C |
Connectable conductor cross section solid-core | 1 - 25 mm² |
Characteristic curve | 1 - 25 mm² |
As Mnelko, we are a reliable partner in industrial automation solutions, offering high-quality and innovative products with a wide product range to meet all the needs of your business. Our product portfolio consists of solutions designed based on the principles of high performance, durability, and efficiency to support modern industrial processes.
All of our products ensure maximum reliability even in challenging working conditions and help your business operations run smoothly. The products we offer in industrial automation, energy management, cabling solutions, and many other areas adapt flexibly to the needs of different sectors.
Additionally, our products are manufactured using only high-quality materials and comply with international standards. Through the solutions we provide, we enable our customers to increase operational efficiency and optimize costs. Our company closely follows technological advancements and continuously offers innovative products to help our customers gain a competitive advantage.
On each of our product pages, you can find comprehensive information about technical details, areas of use, and product features. You can explore all the products you need to strengthen your industrial processes on our website and enjoy a seamless purchasing experience.