Product range |
SmartWire-DT slave |
Basic function |
Analog modules |
Function |
For connection of analog I/O signals |
Short Description |
Configurable inputs: PT100, PT1000, Ni1000 |
Analog |
4 |
Connection to SmartWire-DT |
yes |
Standards |
IEC/EN 61131-2 |
Approvals >Approvals |
UL CSA |
Approvals >shipping classification |
DNV GL BV LRS |
Approvals |
|
Dimensions (W x H x D) |
35 x 90 x 101 mm |
Weight |
0.1 kg |
Mounting |
Top-hat rail IEC/EN 60715, 35 mm |
Mounting position |
As required |
Power supply >Rated operational voltage [Ue] |
24 DC -15 % / +20 % V |
Power supply >Residual ripple on the input voltage |
≦ 5 % |
Power supply >Protection against polarity reversal |
Yes |
Power supply >Power loss [P] |
0.6 W |
Climatic proofing |
Dry heat to IEC 60068-2-2 Damp heat as per EN 60068-2-3 |
Air pressure (operation) |
795 - 1080 hPa |
Ambient temperature >Operation [ϑ] |
-25 - +55 °C |
Ambient temperature >Storage / Transport [ϑ] |
-40 - +70 °C |
Relative humidity >Condensation |
Take appropriate measures to prevent condensation |
Relative humidity >Relative humidity, non-condensing (IEC/EN 60068-2-30) |
5 - 95 % |
Protection type (IEC/EN 60529, EN50178, VBG 4) |
IP20 |
Vibrations (IEC/EN 61131-2:2008) >Constant amplitude 3,5 mm |
5 - 8.4 Hz |
Vibrations (IEC/EN 61131-2:2008) >Constant acceleration 1 g |
8.4 - 150 Hz |
Mechanical shock resistance (IEC/EN 60068-2-27) semi-sinusoidal 15 g/11 ms |
9 Impacts |
Drop to IEC/EN 60068-2-31 [Drop height] |
50 mm |
Free fall, packaged (IEC/EN 60068-2-32) |
0.3 m |
Overvoltage category |
II |
Pollution degree |
2 |
Electrostatic discharge (IEC/EN 61131-2:2008) >Air discharge (Level 3) |
8 kV |
Electrostatic discharge (IEC/EN 61131-2:2008) >Contact discharge (Level 2) |
4 kV |
Electromagnetic fields (IEC/EN 61131-2:2008) >80 - 1000 MHz |
10 V/m |
Electromagnetic fields (IEC/EN 61131-2:2008) >1.4 - 2 GHz |
3 V/m |
Electromagnetic fields (IEC/EN 61131-2:2008) >2 - 2.7 GHz |
1 V/m |
Radio interference suppression (SmartWire-DT) |
EN 55011 Class B |
Burst (IEC/EN 61131-2:2008, Level 3) >Supply cable |
2 kV |
Burst (IEC/EN 61131-2:2008, Level 3) >Signal lines |
2 kV |
Burst (IEC/EN 61131-2:2008, Level 3) >SmartWire-DT cables |
2 kV |
Surge (IEC/EN 61131-2:2008, Level 1) >Surge power cables |
1 kV |
Surge (IEC/EN 61131-2:2008, Level 1) >Surge I/O cables |
1 kV |
Radiated RFI (IEC/EN 61131-2:2008, Level 3) |
10 V |
Station type |
SmartWire-DT slave |
Setting the baud rate |
automatic |
Baud rate (data transfer speed) |
maximum250 kbps |
Status SmartWire-DT |
Green LED |
Connection |
Pin contact, 8 pole | Connector: external device plug SWD4-8SF2-5 |
Current consumption [Ie] |
22 mA |
Terminal for I/O sensor >Connection type |
Push in terminals |
Terminal for I/O sensor >Solid |
0.2 - 1.5 (AWG 24 - 16) mm2 |
Terminal for I/O sensor >Flexible with ferrule |
0.25 - 1.5 (AWG 24 - 16) mm2 |
Terminal for I/O sensor |
Minimum length 8 mm |
Quantity |
4 (2, 3-wire connection, screened, length < 10 m) |
Parameter setting >Averaging |
adjustable |
Parameter setting >Temperature sensor |
PT100, PT1000, Ni1000 |
Temperature range |
PT100, PT1000: -100 - +400 Ni1000: -50 - +200 °C |
Resolution |
0.1 °C |
Conversion time |
250 ms |
Display |
°C, °F, raw value |
Total error |
± 1 % |
Repetition accuracy |
± 0.5 % |
Residual ripple on the input voltage |
≦ 5 % |
Inputs for SmartWire-DT |
Yes |
Input to input |
No |
Rated operational current for specified heat dissipation [In] |
0 A |
Heat dissipation per pole, current-dependent [Pvid] |
0 W |
Equipment heat dissipation, current-dependent [Pvid] |
0 W |
Static heat dissipation, non-current-dependent [Pvs] |
0.6 W |
Heat dissipation capacity [Pdiss] |
0 W |
Operating ambient temperature min. |
-25 °C |
Operating ambient temperature max. |
+55 °C |
Degree of Protection |
IP20 |
10.2 Strength of materials and parts >10.2.2 Corrosion resistance |
Meets the product standard´s requirements. |
10.2 Strength of materials and parts >10.2.3.1 Verification of thermal stability of enclosures |
Meets the product standard´s requirements. |
10.2 Strength of materials and parts >10.2.3.2 Verification of resistance of insulating materials to normal heat |
Meets the product standard´s requirements. |
10.2 Strength of materials and parts >10.2.3.3 Verification of resistance of insulating materials to abnormal heat and fire due to internal electric effects |
Meets the product standard´s requirements. |
10.2 Strength of materials and parts >10.2.4 Resistance to ultra-violet (UV) radiation |
Meets the product standard´s requirements. |
10.2 Strength of materials and parts >10.2.5 Lifting |
Does not apply, since the entire switchgear needs to be evaluated. |
10.2 Strength of materials and parts >10.2.6 Mechanical impact |
Does not apply, since the entire switchgear needs to be evaluated. |
10.2 Strength of materials and parts >10.2.7 Inscriptions |
Meets the product standard´s requirements. |
10.3 Degree of protection of ASSEMBLIES |
Meets the product standard´s requirements. |
10.4 Clearances and creepage distances |
Meets the product standard´s requirements. |
10.5 Protection against electric shock |
Does not apply, since the entire switchgear needs to be evaluated. |
10.6 Incorporation of switching devices and components |
Does not apply, since the entire switchgear needs to be evaluated. |
10.7 Internal electrical circuits and connections |
Is the panel builder´s responsibility. |
10.8 Connections for external conductors |
Is the panel builder´s responsibility. |
10.9 Insulation properties >10.9.2 Power-frequency electric strength |
Is the panel builder´s responsibility. |
10.9 Insulation properties >10.9.3 Impulse withstand voltage |
Is the panel builder´s responsibility. |
10.9 Insulation properties >10.9.4 Testing of enclosures made of insulating material |
Is the panel builder´s responsibility. |
10.10 Temperature rise |
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices. |
10.11 Short-circuit rating |
Is the panel builder´s responsibility. |
10.12 Electromagnetic compatibility |
Is the panel builder´s responsibility. |
10.13 Mechanical function |
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed. |
Supply voltage AC 50 Hz |
0 - 0 V |
Supply voltage AC 60 Hz |
0 - 0 V |
Supply voltage DC |
0 - 0 V |
Voltage type of supply voltage |
DC |
Input, current |
No |
Input, voltage |
No |
Input, resistor |
No |
Input, resistance thermometer |
Yes |
Input, thermocouple |
No |
Input signal, configurable |
No |
Resolution of the analogue inputs |
12 Bit |
Output, current |
No |
Output, voltage |
No |
Output signal configurable |
No |
Resolution of the analogue outputs |
0 Bit |
Number of analogue inputs |
4 |
Number of analogue outputs |
0 |
Analogue inputs configurable |
Yes |
Analogue outputs configurable |
Yes |
Number of HW-interfaces industrial Ethernet |
0 |
Number of interfaces PROFINET |
0 |
Number of HW-interfaces RS-232 |
0 |
Number of HW-interfaces RS-422 |
0 |
Number of HW-interfaces RS-485 |
0 |
Number of HW-interfaces serial TTY |
0 |
Number of HW-interfaces parallel |
0 |
Number of HW-interfaces Wireless |
0 |
Number of HW-interfaces USB |
0 |
Number of HW-interfaces other |
0 |
Supporting protocol for TCP/IP |
No |
Supporting protocol for PROFIBUS |
No |
Supporting protocol for CAN |
No |
Supporting protocol for INTERBUS |
No |
Supporting protocol for ASI |
No |
Supporting protocol for KNX |
No |
Supporting protocol for MODBUS |
No |
Supporting protocol for Data-Highway |
No |
Supporting protocol for DeviceNet |
No |
Supporting protocol for SUCONET |
No |
Supporting protocol for LON |
No |
Supporting protocol for PROFINET IO |
No |
Supporting protocol for PROFINET CBA |
No |
Supporting protocol for SERCOS |
No |
Supporting protocol for Foundation Fieldbus |
No |
Supporting protocol for EtherNet/IP |
No |
Supporting protocol for AS-Interface Safety at Work |
No |
Supporting protocol for DeviceNet Safety |
No |
Supporting protocol for INTERBUS-Safety |
No |
Supporting protocol for PROFIsafe |
No |
Supporting protocol for SafetyBUS p |
No |
Supporting protocol for other bus systems |
Yes |
Radio standard Bluetooth |
No |
Radio standard WLAN 802.11 |
No |
Radio standard GPRS |
No |
Radio standard GSM |
No |
Radio standard UMTS |
No |
IO link master |
No |
System accessory |
Yes |
Degree of protection (IP) |
IP20 |
Degree of protection (NEMA) |
|
Type of electric connection |
Flat plug-in connection |
Fieldbus connection over separate bus coupler possible |
Yes |
Rail mounting possible |
Yes |
Wall mounting/direct mounting |
Yes |
Front build in possible |
No |
Rack-assembly possible |
No |
Suitable for safety functions |
No |
Category according to EN 954-1 |
|
SIL according to IEC 61508 |
None |
Performance level acc. EN ISO 13849-1 |
None |
Appendant operation agent (Ex ia) |
No |
Appendant operation agent (Ex ib) |
No |
Explosion safety category for gas |
None |
Explosion safety category for dust |
None |
Width |
35 mm |
Height |
90 mm |
Depth |
97 mm |
UL File No. |
E29184 |
UL Category Control No. |
NKCR |
CSA File No. |
2324643 |
CSA Class No. |
3211-07 |
North America Certification |
UL listed, CSA certified |
Specially designed for North America |
No |