alt
alt

EU1E-SWD-1XA-2
174720 EU1E-SWD-1XA-2
174720

SmartWire-DT IP67 T-Connector analog module, one 0 - 20 mA analog output with power supply, one M12 I/O socketSmartWire-DT module with IP67 degree of protection, can be used to connect one analog output, 24 VDC 70 mA short-circuit proof sensor power supply, automatic address setting, 0 – 20 mA output, 12-bit resolution, short-circuit proof, I/O connection with M12 socket

SmartWire-DT IP67 T-Connector analog module, one 0 - 20 mA analog output with power supply, one M12 I/O socket
SmartWire-DT module with IP67 degree of protection, can be used to connect one analog output, 24 VDC 70 mA short-circuit proof sensor power supply, automatic address setting, 0 – 20 mA output, 12-bit resolution, short-circuit proof, I/O connection with M12 socket

Product range SmartWire-DT slave
Basic function Analog modules
Function For connection of analog I/O signals
Short Description Output: 0 - 20 mA
Analog 1
Connection to SmartWire-DT yes
Standards IEC/EN 61131-2
Dimensions (W x H x D) 85.6 x 56.9 x 20.1 mm
Weight 0.07 kg
Mounting DIN-rail, screw fixing (M4), mounting section (Clip M20)
Mounting position As required
Power supply
>Power loss [P]
1.1 W
Climatic proofing Dry heat to IEC 60068-2-2
Damp heat as per EN 60068-2-3
Air pressure (operation) 795 - 1080 hPa
Ambient temperature
>Operation [ϑ]
-25 - +70 °C
Ambient temperature
>Storage / Transport [ϑ]
-40 - +70 °C
Relative humidity
>Condensation
permissible
Relative humidity
>Relative humidity, non-condensing (IEC/EN 60068-2-30)
5 - 95 %
Protection type (IEC/EN 60529, EN50178, VBG 4) IP69K
Vibrations (IEC/EN 61131-2:2008)
>Constant amplitude 3,5 mm
5 - 8.4 Hz
Vibrations (IEC/EN 61131-2:2008)
>Constant acceleration 1 g
8.4 - 150 Hz
Mechanical shock resistance (IEC/EN 60068-2-27) semi-sinusoidal 30 g/11 ms 9 Impacts
Drop to IEC/EN 60068-2-31 [Drop height] 50 mm
Free fall, packaged (IEC/EN 60068-2-32) 0.3 m
Overvoltage category II
Pollution degree 3
Electrostatic discharge (IEC/EN 61131-2:2008)
>Air discharge (Level 3)
8 kV
Electrostatic discharge (IEC/EN 61131-2:2008)
>Contact discharge (Level 2)
4 kV
Electromagnetic fields (IEC/EN 61131-2:2008)
>80 - 1000 MHz
10 V/m
Electromagnetic fields (IEC/EN 61131-2:2008)
>1.4 - 2 GHz
3 V/m
Electromagnetic fields (IEC/EN 61131-2:2008)
>2 - 2.7 GHz
1 V/m
Radio interference suppression (SmartWire-DT) EN 55011 Class A
Burst (IEC/EN 61131-2:2008, Level 3)
>Supply cable
2 kV
Burst (IEC/EN 61131-2:2008, Level 3)
>Signal lines
1 kV
Burst (IEC/EN 61131-2:2008, Level 3)
>SmartWire-DT cables
1 kV
Surge (IEC/EN 61131-2:2008, Level 1)
>Surge power cables
0.5 kV
Surge (IEC/EN 61131-2:2008, Level 1)
>Surge I/O cables
1 kV
Radiated RFI (IEC/EN 61131-2:2008, Level 3) 10 V
Station type SmartWire-DT slave
Setting the baud rate automatic
Baud rate (data transfer speed) maximum2000 kbps
Status SmartWire-DT Green LED
SWD-IN M12 plug (A-keyed), 5 pole
SWD-OUT M12 socket (A-keyed), 5 pole
Current consumption (24V, without sensor and without I/O supply)
>Current consumption (24 V SWD supply)
67 mA
Sensor supply
>Max. current consumption per M12 I/O plug
70 mA
Sensor supply
>Overload and short-circuit proof
yes, with diagnostics
Terminal for I/O sensor
>Connection type
5-pin M12 socket (A-keyed)
Quantity 1 (2-wire connection, screened)
Parameter setting
>Type
Current
Max. current
>Output current
0 - 20 mA
Max. current
>Load resistance
< 500 Ω
Overload and short-circuit proof yes
Resolution 12 Bit
Conversion time 20 ms
Total error ± 1 %
Repetition accuracy ± 0.5 %
Outputs to SmartWire-DT No
Rated operational current for specified heat dissipation [In] 0 A
Heat dissipation per pole, current-dependent [Pvid] 0 W
Equipment heat dissipation, current-dependent [Pvid] 0 W
Static heat dissipation, non-current-dependent [Pvs] 1.1 W
Heat dissipation capacity [Pdiss] 0 W
Operating ambient temperature min. -25 °C
Operating ambient temperature max. +70 °C
Degree of Protection IP69K
10.2 Strength of materials and parts
>10.2.2 Corrosion resistance
Meets the product standard´s requirements.
10.2 Strength of materials and parts
>10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard´s requirements.
10.2 Strength of materials and parts
>10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard´s requirements.
10.2 Strength of materials and parts
>10.2.3.3 Verification of resistance of insulating materials to abnormal heat and fire due to internal electric effects
Meets the product standard´s requirements.
10.2 Strength of materials and parts
>10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard´s requirements.
10.2 Strength of materials and parts
>10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
10.2 Strength of materials and parts
>10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2 Strength of materials and parts
>10.2.7 Inscriptions
Meets the product standard´s requirements.
10.3 Degree of protection of ASSEMBLIES Meets the product standard´s requirements.
10.4 Clearances and creepage distances Meets the product standard´s requirements.
10.5 Protection against electric shock Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections Is the panel builder´s responsibility.
10.8 Connections for external conductors Is the panel builder´s responsibility.
10.9 Insulation properties
>10.9.2 Power-frequency electric strength
Is the panel builder´s responsibility.
10.9 Insulation properties
>10.9.3 Impulse withstand voltage
Is the panel builder´s responsibility.
10.9 Insulation properties
>10.9.4 Testing of enclosures made of insulating material
Is the panel builder´s responsibility.
10.10 Temperature rise The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating Is the panel builder´s responsibility.
10.12 Electromagnetic compatibility Is the panel builder´s responsibility.
10.13 Mechanical function The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
Supply voltage AC 50 Hz 0 - 0 V
Supply voltage AC 60 Hz 0 - 0 V
Supply voltage DC 0 - 0 V
Voltage type of supply voltage DC
Input, current No
Input, voltage No
Input, resistor No
Input, resistance thermometer No
Input, thermocouple No
Input signal, configurable No
Resolution of the analogue inputs 0 Bit
Output, current Yes
Output, voltage No
Output signal configurable Yes
Resolution of the analogue outputs 12 Bit
Number of analogue inputs 0
Number of analogue outputs 1
Analogue inputs configurable No
Analogue outputs configurable Yes
Number of HW-interfaces industrial Ethernet 0
Number of interfaces PROFINET 0
Number of HW-interfaces RS-232 0
Number of HW-interfaces RS-422 0
Number of HW-interfaces RS-485 0
Number of HW-interfaces serial TTY 0
Number of HW-interfaces parallel 0
Number of HW-interfaces Wireless 0
Number of HW-interfaces USB 0
Number of HW-interfaces other 0
Supporting protocol for TCP/IP No
Supporting protocol for PROFIBUS No
Supporting protocol for CAN No
Supporting protocol for INTERBUS No
Supporting protocol for ASI No
Supporting protocol for KNX No
Supporting protocol for MODBUS No
Supporting protocol for Data-Highway No
Supporting protocol for DeviceNet No
Supporting protocol for SUCONET No
Supporting protocol for LON No
Supporting protocol for PROFINET IO No
Supporting protocol for PROFINET CBA No
Supporting protocol for SERCOS No
Supporting protocol for Foundation Fieldbus No
Supporting protocol for EtherNet/IP No
Supporting protocol for AS-Interface Safety at Work No
Supporting protocol for DeviceNet Safety No
Supporting protocol for INTERBUS-Safety No
Supporting protocol for PROFIsafe No
Supporting protocol for SafetyBUS p No
Supporting protocol for other bus systems Yes
Radio standard Bluetooth No
Radio standard WLAN 802.11 No
Radio standard GPRS No
Radio standard GSM No
Radio standard UMTS No
IO link master No
System accessory Yes
Degree of protection (IP) IP69K
Degree of protection (NEMA)
Type of electric connection Other
Fieldbus connection over separate bus coupler possible Yes
Rail mounting possible Yes
Wall mounting/direct mounting Yes
Front build in possible No
Rack-assembly possible No
Suitable for safety functions No
Category according to EN 954-1
SIL according to IEC 61508 None
Performance level acc. EN ISO 13849-1 None
Appendant operation agent (Ex ia) No
Appendant operation agent (Ex ib) No
Explosion safety category for gas None
Explosion safety category for dust None
Width 85.6 mm
Height 56.9 mm
Depth 20.1 mm
UL File No. E170645
North America Certification UL listed, CSA certified
Specially designed for North America No

As Mnelko, we are a reliable partner in industrial automation solutions, offering high-quality and innovative products with a wide product range to meet all the needs of your business. Our product portfolio consists of solutions designed based on the principles of high performance, durability, and efficiency to support modern industrial processes.
All of our products ensure maximum reliability even in challenging working conditions and help your business operations run smoothly. The products we offer in industrial automation, energy management, cabling solutions, and many other areas adapt flexibly to the needs of different sectors.
Additionally, our products are manufactured using only high-quality materials and comply with international standards. Through the solutions we provide, we enable our customers to increase operational efficiency and optimize costs. Our company closely follows technological advancements and continuously offers innovative products to help our customers gain a competitive advantage.
On each of our product pages, you can find comprehensive information about technical details, areas of use, and product features. You can explore all the products you need to strengthen your industrial processes on our website and enjoy a seamless purchasing experience.

Similar Products

DS7-34DSX200N0-D
Eaton
DS7-34DSX160N0-D
Eaton
DS7-34DSX135N0-D
Eaton
DS7-34DSX081N0-D
Eaton
NZM-XSWD-704
Eaton
DS7-34DSX100N0-D
Eaton
DS7-34DSX032N0-D
Eaton