alt
alt

EMS-DO-T-2,4-SWD
170106 EMS-DO-T-2,4-SWD
170106

DOL starter, 24 V DC, 0,18 - 2,4 A, Push in terminals, SmartWire-DT slaveDOL starter, Actuating voltage: 24 V DC, Standards: IEC/EN 60947-4-2

DOL starter, 24 V DC, 0,18 - 2,4 A, Push in terminals, SmartWire-DT slave
DOL starter, Actuating voltage: 24 V DC, Standards: IEC/EN 60947-4-2

Product range Electronic motor starter
Product range SmartWire-DT slave
Subrange SmartWire-DT electronic motor starters
Basic function DOL starters (complete devices)
Function For connecting to SmartWire-DT for expanded diagnostics.
Description DOL starting
Motor protection
Circuit design: safety output stage with bypass, three-phase disconnect.
Motor current additionally adjustable via SmartWire-DT.
Messages Operational readiness
Operating direction feedback
Motor current in %
Motor current in A
Thermal motor image in %
Overload prewarning
Trip indications (overload, phase failure, etc.)
Set short-circuit release value
Device Type
Commands Operating the motor starter
Manual reset
Automatic reset
Max. rating for three-phase motors, 50 - 60 Hz
>AC-53a
>380 V 400 V 415 V [P]
0.06 - 0.75 kW
Setting range of overload releases [Ir] 0,18 - 2,4 A_x
Actuating voltage 24 V DC
Connection technique Push in terminals
Connection to SmartWire-DT yes
Standards IEC/EN 60947-4-2
Dimensions
>Width
30 mm
Dimensions
>Height
157 mm
Dimensions
>Depth
124 mm
Weight 0.3 kg
Mounting Top-hat rail IEC/EN 60715, 35 mm
Protection type (IEC/EN 60529, EN50178, VBG 4) IP20
Mounting position Vertical
Lifespan, electrical [Operations] 3 x 107
Max. switching frequency 7200 (pulse pause time 50:50) Operations/h
Terminal capacity
>Solid
1 x (0.2 - 2.5)
1 x AWG20 - 14 mm2
Terminal capacity
>flexible, with ferrule
2 x (0,2 - 2,5)
1 x AWG24 - 14 mm2
Terminal capacity
>Notes
Minimum length 10 mm.
Terminal capacity
>flexible, with twin ferrule
2 x (0,2 - 1,5)
2 x AWG24 - 16 mm2
Terminal capacity
>Notes
Minimum length 10 mm.
Operating ambient temperature -5 - +60, in accordance with IEC 60068-2-1 °C
Storage [ϑ] -40 - +80 °C
Rated impulse withstand voltage [Uimp] 6000 V AC
Overvoltage category/pollution degree III/2
Rated operational voltage [Ue ] 42 - 550 V
Rated operational current
>AC-51 [Ie]
0.15 - 2.40 A
Rated operational current
>AC-53a [Ie]
0.15 - 2.4 A
Heat dissipation [PV] 0.1 - 2 W
Static heat dissipation, non-current-dependent [Pvs] 1 W
Basic insulation to IEC/EN60947-1
>between feedback signal output and switch voltage
500 V AC
Current measurement
>Setting range of overload releases [Ir]
0,18 - 2,4 A_x
Current measurement
>Release class
10 CLASS
Current measurement
>Recovery time [tW]
2 (manual startup)
20 (automatic restart) min.
Current measurement
>Balance monitoring
>Magnitude Imax > Irated ((Imax - Imin)/Imax)
If ≧ 33, pick-up time of 120 s
If ≧ 67, pick-up time of 1.8 s %
Current measurement
>Balance monitoring
>Magnitude Imax < Irated ((Imax - Imin)/Irated)
If ≧ 33, pick-up time of 120 s
If ≧ 67, pick-up time of 1.8 s %
Stall protection
>Pick-up time I (L1) or I (L3)
33 A
Stall protection
>Pick-up time
0.5 S
Short-circuit rating
>Type “1” coordination
>Short-circuit protective device
50 kA, 500 V AC: Fuse 16 A gG/gL
50 kA, 500 V AC: fuse 30 A CCMR
50 kA, 415 V AC: PKM0-4
15 kA, 415 V AC: PKM0-6,3
2.5 kA, 400 V AC: FAZ-B16/3
Input data
>Supply voltage [UAUX]
24 (-15 - +20 %) V DC
Input data
>Residual ripple on the input voltage
≦ 5 %
Input data
>Input current
70 mA
Input data
>Current draw inrush
120 mA
Input data
>Current draw (operation) [UAUX]
50 mA
Electrostatic discharge (ESD)
>applied standard
IEC EN 61000-4-2, Level 3
Electrostatic discharge (ESD)
>Air discharge
8 kV
Electrostatic discharge (ESD)
>Contact discharge
6 kV
Electromagnetic fields (RFI)
>applied standard
IEC/EN 61000-4-3
Electromagnetic fields (RFI) 800 - 1000 MHz: 10
1.4 - 2 GHz: 10
2.0 - 2.7 GHz: 3 V/m
Radio interference suppression EN 55011, Class A (emitted interference, line-conducted)
EN 61000-6-3, Class A (emitted interference, radiated)
Note on use This product is designed for operation in industrial environments (environment 2). The use in residential environments (environment 1) could cause electrical interference so that addition suppression must be planned.
Burst 2
IEC/EN 61000-4-4, level 3 kV
power pulses (Surge) 1 kV (symmetrical)
2 kV (asymmetrical)
according to IEC/EN 61000-4-5
Immunity to line-conducted interference to (IEC/EN 61000-4-6) 10 V
Rated operational current for specified heat dissipation [In] 2.4 A
Heat dissipation per pole, current-dependent [Pvid] 0.7 W
Equipment heat dissipation, current-dependent [Pvid] 2.1 W
Static heat dissipation, non-current-dependent [Pvs] 1 W
Heat dissipation capacity [Pdiss] 0 W
Operating ambient temperature min. -5 °C
Operating ambient temperature max. +60 °C
10.2 Strength of materials and parts
>10.2.2 Corrosion resistance
Meets the product standard´s requirements.
10.2 Strength of materials and parts
>10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard´s requirements.
10.2 Strength of materials and parts
>10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard´s requirements.
10.2 Strength of materials and parts
>10.2.3.3 Verification of resistance of insulating materials to abnormal heat and fire due to internal electric effects
Meets the product standard´s requirements.
10.2 Strength of materials and parts
>10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard´s requirements.
10.2 Strength of materials and parts
>10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
10.2 Strength of materials and parts
>10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2 Strength of materials and parts
>10.2.7 Inscriptions
Meets the product standard´s requirements.
10.3 Degree of protection of ASSEMBLIES Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances Meets the product standard´s requirements.
10.5 Protection against electric shock Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections Is the panel builder´s responsibility.
10.8 Connections for external conductors Is the panel builder´s responsibility.
10.9 Insulation properties
>10.9.2 Power-frequency electric strength
Is the panel builder´s responsibility.
10.9 Insulation properties
>10.9.3 Impulse withstand voltage
Is the panel builder´s responsibility.
10.9 Insulation properties
>10.9.4 Testing of enclosures made of insulating material
Is the panel builder´s responsibility.
10.10 Temperature rise The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating Is the panel builder´s responsibility. The specifications for the switchgear must be observed.
10.12 Electromagnetic compatibility Is the panel builder´s responsibility. The specifications for the switchgear must be observed.
10.13 Mechanical function The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
Kind of motor starter Direct starter
With short-circuit release No
Rated control supply voltage Us at AC 50HZ 0 - 0 V
Rated control supply voltage Us at AC 60HZ 0 - 0 V
Rated control supply voltage Us at DC 24 - 24 V
Voltage type for actuating DC
Rated operation power at AC-3, 230 V, 3-phase 0.37 kW
Rated operation power at AC-3, 400 V 0.75 kW
Rated power, 460 V, 60 Hz, 3-phase 0.736 kW
Rated power, 575 V, 60 Hz, 3-phase 0 kW
Rated operation current Ie 2.4 A
Rated operation current at AC-3, 400 V 2.4 A
Overload release current setting 0.18 - 2.4 A
Rated conditional short-circuit current, type 1, 480 Y/277 V 0 A
Rated conditional short-circuit current, type 1, 600 Y/347 V 0 A
Rated conditional short-circuit current, type 2, 230 V 0 A
Rated conditional short-circuit current, type 2, 400 V 0 A
Number of auxiliary contacts as normally open contact 0
Number of auxiliary contacts as normally closed contact 0
Ambient temperature, upper operating limit 60 °C
Temperature compensated overload protection Yes
Release class CLASS 10
Type of electrical connection of main circuit Spring clamp connection
Type of electrical connection for auxiliary- and control current circuit Spring clamp connection
Rail mounting possible Yes
With transformer No
Number of command positions 0
Suitable for emergency stop No
Coordination class according to IEC 60947-4-3 Class 1
Number of indicator lights 4
External reset possible Yes
With fuse No
Degree of protection (IP) IP20
Degree of protection (NEMA) Other
Supporting protocol for TCP/IP No
Supporting protocol for PROFIBUS No
Supporting protocol for CAN No
Supporting protocol for INTERBUS No
Supporting protocol for ASI No
Supporting protocol for MODBUS No
Supporting protocol for Data-Highway No
Supporting protocol for DeviceNet No
Supporting protocol for SUCONET No
Supporting protocol for LON No
Supporting protocol for PROFINET IO No
Supporting protocol for PROFINET CBA No
Supporting protocol for SERCOS No
Supporting protocol for Foundation Fieldbus No
Supporting protocol for EtherNet/IP No
Supporting protocol for AS-Interface Safety at Work No
Supporting protocol for DeviceNet Safety No
Supporting protocol for INTERBUS-Safety No
Supporting protocol for PROFIsafe No
Supporting protocol for SafetyBUS p No
Supporting protocol for other bus systems Yes
Width 30 mm
Height 157 mm
Depth 139 mm
Product Standards IEC/EN 60947-5; UL 508; CSA-C22.2 No. 14; CE marking
UL File No. E29096
UL Category Control No. NLDX, NLDX7
CSA File No. UL report applies to both US and Canada
North America Certification UL listed, certified by UL for use in Canada
Specially designed for North America No
Characteristic curve 2100DIA-20

As Mnelko, we are a reliable partner in industrial automation solutions, offering high-quality and innovative products with a wide product range to meet all the needs of your business. Our product portfolio consists of solutions designed based on the principles of high performance, durability, and efficiency to support modern industrial processes.
All of our products ensure maximum reliability even in challenging working conditions and help your business operations run smoothly. The products we offer in industrial automation, energy management, cabling solutions, and many other areas adapt flexibly to the needs of different sectors.
Additionally, our products are manufactured using only high-quality materials and comply with international standards. Through the solutions we provide, we enable our customers to increase operational efficiency and optimize costs. Our company closely follows technological advancements and continuously offers innovative products to help our customers gain a competitive advantage.
On each of our product pages, you can find comprehensive information about technical details, areas of use, and product features. You can explore all the products you need to strengthen your industrial processes on our website and enjoy a seamless purchasing experience.

Similar Products

DS7-34DSX200N0-D
Eaton
DS7-34DSX160N0-D
Eaton
DS7-34DSX135N0-D
Eaton
DS7-34DSX081N0-D
Eaton
NZM-XSWD-704
Eaton
DS7-34DSX100N0-D
Eaton
DS7-34DSX032N0-D
Eaton