alt
alt

DS7-34DSX070N0-D
134954 DS7-34DSX070N0-D
134954

Soft starter, 70 A, 200 - 480 V AC, 24 V DC, Frame size: FS3, Communication Interfaces: SmartWire-DTSoft starter, Product range: SmartWire-DT slave, Description: With internal bypass contacts, Function: Soft starters for three-phase loads, Mains supply voltage (50/60 Hz): ULN= 200 - 480 V AC, Supply voltage: Us= 24 V DC, Control voltage: UC= 24 V DC, Assigned motor rating (Standard connection, In-Line) at 400 V, 50 Hz: P= 37 kW, at 460 V, 60 Hz: P= 50 HP, Rated operational current AC-53: Ie= 70 A, Rated operational voltage: Ue= 200 V, 230 V, 400 V, 480 V, Connection to SmartWire-DT: yes, Frame size: FS3, Standards: IEC/EN 60947-4-2, UL 508, CSA22.2-14

Soft starter, 70 A, 200 - 480 V AC, 24 V DC, Frame size: FS3, Communication Interfaces: SmartWire-DT
Soft starter, Product range: SmartWire-DT slave, Description: With internal bypass contacts, Function: Soft starters for three-phase loads, Mains supply voltage (50/60 Hz): ULN= 200 - 480 V AC, Supply voltage: Us= 24 V DC, Control voltage: UC= 24 V DC, Assigned motor rating (Standard connection, In-Line) at 400 V, 50 Hz: P= 37 kW, at 460 V, 60 Hz: P= 50 HP, Rated operational current AC-53: Ie= 70 A, Rated operational voltage: Ue= 200 V, 230 V, 400 V, 480 V, Connection to SmartWire-DT: yes, Frame size: FS3, Standards: IEC/EN 60947-4-2, UL 508, CSA22.2-14

Product range SmartWire-DT slave
Subrange SmartWire-DT Soft starters
Description With internal bypass contacts
Function Soft starters for three-phase loads
Mains supply voltage (50/60 Hz) [ULN] 200 - 480 V AC
Supply voltage [Us] 24 V DC
Control voltage [UC] 24 V DC
at 400 V, 50 Hz [P] 37 kW
at 460 V, 60 Hz [P] 50 HP
AC-53 [Ie] 70 A
Rated operational voltage [Ue] 200 V
230 V
400 V
480 V
Connection to SmartWire-DT yes
Frame size FS3
Standards IEC/EN 60947-4-2
UL 508
CSA22.2-14
Approvals CE
Approvals UL
CSA
C-Tick
UkrSEPRO
Climatic proofing Damp heat, constant, to IEC 60068-2-3
Damp heat, cyclic, to IEC 60068-2-10
Ambient temperature
>Operation [ϑ]
-5 - +40
up to 60 at 2% derating per Kelvin temperature rise °C
Ambient temperature
>Storage [ϑ]
-25 - +60 °C
Altitude 0 - 1000 m, above that 1 % derating per 100 m , up to 2000 m m
Mounting position Vertical
Degree of protection
>Degree of Protection
IP20 (terminals IP00)
Degree of protection
>Integrated
Protection type IP40 can be achieved on all sides with covers from the NZM range.
Protection against direct contact Finger- and back-of-hand proof
Overvoltage category/pollution degree II/2
Shock resistance 8 g/11 ms
Vibration resistance to EN 60721-3-2 2M2
Radio interference level (IEC/EN 55011) B
Static heat dissipation, non-current-dependent [Pvs] 13 W
Weight 1.8 kg
Rated operating voltage [Ue] 200 - 480 V AC
Supply frequency [fLN] 50/60 Hz
Rated operational current [Ie ]
>AC-53 [Ie]
70 A
Assigned motor rating (Standard connection, In-Line)
>at 230 V, 50 Hz [P]
15 kW
Assigned motor rating (Standard connection, In-Line)
>at 400 V, 50 Hz [P]
37 kW
Assigned motor rating (Standard connection, In-Line)
>at 200 V, 60 Hz [P]
20 HP
Assigned motor rating (Standard connection, In-Line)
>at 230 V, 60 Hz [P]
25 HP
Assigned motor rating (Standard connection, In-Line)
>at 460 V, 60 Hz [P]
50 HP
Overload cycle to IEC/EN 60947-4-2
>AC-53a
68 A: AC-53a: 3 - 5: 75 - 10
Overload cycle to IEC/EN 60947-4-2
>Internal bypass contacts
Short-circuit rating
>Type “1” coordination
NZMN1-M80
Short-circuit rating
>Type „2“ coordination (additional with the fuses for coordination type „1“)
3 x 170M4008
Fuse base (number x part no.) 3 x 170H3004
Cable lengths
>Solid
1 x (25 - 70)
2 x (6 - 25) mm2
Cable lengths
>Stranded
1 x (25 - 70)
2 x (6 - 25) mm2
Cable lengths
>Solid or stranded
1 x (12 - 2/0) AWG
Cable lengths
>Copper band
2 x 9 x 0.89 x 9 x 0.8 MM
Cable lengths
>Tightening torque
6 (≤ 10 mm²); 9 (> 10 mm²) Nm
Cable lengths
>Screwdriver (PZ: Pozidriv)
PZ2; 1 x 6 mm mm
Control cables
>Solid
1 x (0.5 - 2.5)
2 x (0.5 - 1.0) mm2
Control cables
>Flexible with ferrule
1 x (0.5 - 1.5)
2 x (0.5 - 0.75) mm2
Control cables
>Stranded
1 x (0.5 - 1.5)
2 x (0.5 - 1.0) mm2
Control cables
>Solid or stranded
1 x (21 - 14)
2 x (21 - 18) AWG
Control cables
>Tightening torque
0.4 Nm
Control cables
>Screwdriver
0,6 x 3,5 mm
Digital inputs
>Control voltage
>DC-operated
24 V DC +10 %/- 15 % oder über SWD V DC
Digital inputs
>Current consumption 24 V
>External 24 V
1.6 mA
Digital inputs
>Pick-up voltage
>DC-operated
17.3 - 27 V DC
Digital inputs
>Drop-out voltage [x Us ]
>DC operated
0 - 3 V DC
Digital inputs
>Pick-up time
>DC operated
250 ms
Digital inputs
>Drop-out time
>DC operated
350 ms
Regulator supply
>Voltage [Us]
24 V DC +10 %/- 15 % V
Regulator supply
>Current consumption [Ie]
50 mA
Regulator supply
>Current consumption at peak performance (close bypass) at 24 V DC [IPeak]
0,6/50 A/ms
Regulator supply
>Notes
External supply voltage
Relay outputs
>Number
2 (TOR, Ready)
Relay outputs
>Voltage range
250 V AC
Relay outputs
>AC-11 current range
1 A, AC-11 A
Ramp times
>Acceleration
1 - 30 s
Ramp times
>Deceleration
0 - 30 s
Start voltage (= turn-off voltage) 30100 %
Start pedestal 30 - 100 %
Current limitation (0 - 8) x Ie
Fields of application
>Fields of application
Soft starting of three-phase asynchronous motors
Fields of application
>1-phase motors
Fields of application
>3-phase motors
Fast switching (semiconductor contactor) - (minimum ramp time 1s)
Soft start function
Reversing starter External solution required
Suppression of closing transients
Current limitation ●, with PKE
Fault memory 8 Faults
Suppression of DC components for motors
Potential isolation between power and control sections
Communication Interfaces SmartWire-DT
Rated operational current for specified heat dissipation [In]

Rated impulse withstand voltage:

  • 1.2 µs/50 µs (rise time/fall time of the pulse to IEC/EN 60947‐2 or ‐3)
  • Applies for control circuit/power section/enclosure
Heat dissipation per pole, current-dependent [Pvid] 70 A
Equipment heat dissipation, current-dependent [Pvid] 0 W
Static heat dissipation, non-current-dependent [Pvs] 13 W
Heat dissipation capacity [Pdiss] 13 W
Operating ambient temperature min. 0 W
Operating ambient temperature max. -5 °C
10.2 Strength of materials and parts
>10.2.2 Corrosion resistance
+40 °C
10.2 Strength of materials and parts
>10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard´s requirements.
10.2 Strength of materials and parts
>10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard´s requirements.
10.2 Strength of materials and parts
>10.2.3.3 Verification of resistance of insulating materials to abnormal heat and fire due to internal electric effects
Meets the product standard´s requirements.
10.2 Strength of materials and parts
>10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard´s requirements.
10.2 Strength of materials and parts
>10.2.5 Lifting
Meets the product standard´s requirements.
10.2 Strength of materials and parts
>10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2 Strength of materials and parts
>10.2.7 Inscriptions
Does not apply, since the entire switchgear needs to be evaluated.
10.3 Degree of protection of ASSEMBLIES Meets the product standard´s requirements.
10.4 Clearances and creepage distances Does not apply, since the entire switchgear needs to be evaluated.
10.5 Protection against electric shock Meets the product standard´s requirements.
10.6 Incorporation of switching devices and components Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections Does not apply, since the entire switchgear needs to be evaluated.
10.8 Connections for external conductors Is the panel builder´s responsibility.
10.9 Insulation properties
>10.9.2 Power-frequency electric strength
Is the panel builder´s responsibility.
10.9 Insulation properties
>10.9.3 Impulse withstand voltage
Is the panel builder´s responsibility.
10.9 Insulation properties
>10.9.4 Testing of enclosures made of insulating material
Is the panel builder´s responsibility.
10.10 Temperature rise Is the panel builder´s responsibility.
10.11 Short-circuit rating The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.12 Electromagnetic compatibility Is the panel builder´s responsibility. The specifications for the switchgear must be observed.
10.13 Mechanical function Is the panel builder´s responsibility. The specifications for the switchgear must be observed.
Rated operation current Ie at 40 °C Tu The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
Rated operating voltage Ue 70 A
Rated power three-phase motor, inline, at 230 V 230 - 460 V
Rated power three-phase motor, inline, at 400 V 15 kW
Rated power three-phase motor, inside delta, at 230 V 37 kW
Rated power three-phase motor, inside delta, at 400 V 0 kW
Function 0 kW
Internal bypass Single direction
With display Yes
Torque control No
Rated surrounding temperature without derating No
Rated control supply voltage Us at AC 50HZ 40 °C
Rated control supply voltage Us at AC 60HZ 0 - 0 V
Rated control supply voltage Us at DC 0 - 0 V
Voltage type for actuating 24 - 24 V
Integrated motor overload protection DC
Release class No
Degree of protection (IP) Other
Degree of protection (NEMA) IP20
Product Standards 1
Specially designed for North America IEC/EN 60947-4-2; GB 14048.6; UL 508; CSA-C22.2 No 0-M91; CSA-C22.2 No 14-05 CE marking
Suitable for No
Current Limiting Circuit-Breaker Branch circuits
Max. Voltage Rating No
Degree of Protection 480 V

As Mnelko, we are a reliable partner in industrial automation solutions, offering high-quality and innovative products with a wide product range to meet all the needs of your business. Our product portfolio consists of solutions designed based on the principles of high performance, durability, and efficiency to support modern industrial processes.
All of our products ensure maximum reliability even in challenging working conditions and help your business operations run smoothly. The products we offer in industrial automation, energy management, cabling solutions, and many other areas adapt flexibly to the needs of different sectors.
Additionally, our products are manufactured using only high-quality materials and comply with international standards. Through the solutions we provide, we enable our customers to increase operational efficiency and optimize costs. Our company closely follows technological advancements and continuously offers innovative products to help our customers gain a competitive advantage.
On each of our product pages, you can find comprehensive information about technical details, areas of use, and product features. You can explore all the products you need to strengthen your industrial processes on our website and enjoy a seamless purchasing experience.

Similar Products

DS7-34DSX200N0-D
Eaton
DS7-34DSX160N0-D
Eaton
DS7-34DSX135N0-D
Eaton
DS7-34DSX081N0-D
Eaton
NZM-XSWD-704
Eaton
DS7-34DSX100N0-D
Eaton
DS7-34DSX032N0-D
Eaton