alt
alt

Digital residual current circuit-breaker, 63A, 4p, 300mA, type UResidual current circuit-breaker dRCM, 4 pole, Rated current In: 63 A, Rated short-circuit strength Icn: 10 kA, Rated fault current IΔN: 0.3 A, Switchgear for residential and commercial applications

Digital residual current circuit-breaker, 63A, 4p, 300mA, type U
Residual current circuit-breaker dRCM, 4 pole, Rated current In: 63 A, Rated short-circuit strength Icn: 10 kA, Rated fault current IΔN: 0.3 A, Switchgear for residential and commercial applications

Basic function Residual current circuit-breakers , digital
Number of poles 4 pole
Application Switchgear for residential and commercial applications
Rated current [In] 63 A
Rated short-circuit strength [Icn] 10 kA
Rated fault current [IΔN] 0.3 A
Type Type U
Tripping selective switch off s…
Product range dRCM
Sensitivity Frequency converter-proof
Impulse withstand current surge-proof 5 kA
Current test marks As per inscription
Standards IEC/EN 61008
Rated operational voltage [Ue] [Ue]Rated operating voltage [Ue] 230/400 V AC
Rated frequency [f] 50 Hz
Limit values of the operating voltage
>Test circuit
184 - 440 V AC
Limit values of the operating voltage
>Comment for range of the test button
3-phase application without N (400V AC Phase-Phase) not allowed
Rated fault currents [IΔn ] 30, 300 mA
Rated non-tripping current [IΔno] 0.5 x I ∆n
Sensitivity Frequency converter-proof
Rated insulation voltage [Ui ] 440 V
Sensitivity DC and pulsed current
Rated impulse withstand voltage [Uimp] 4 kV
Rated short-circuit strength [Icn] 10 kA
Maximum max. as short-circuit protective device
>Back-up fuse
Short-circuit and overload:
63 A gG/GL A gL
lifespan
>Electrical [Operations]
≧ 4000
lifespan
>Mechanical [Operations]
≧ 20000
Auxiliary switch for subsequent installation Z-HK 248432
Tripping signal contact for subsequent installation Z-NHK 248434
Remote control and automatic switching device Z-FW/LP 248296
Compact enclosure KLV-TC-4 276241
Sealing cover set Z-RC/AK-4MU 101062
Standard front dimension 45 mm
Standard front dimension 45 mm
Device height 80 mm
Enclosure height
>Enclosure width
80 mm
Built-in width 70 (4TE) mm
Mounting Quick attachment with 2 latch positions on top-hat rail IEC/EN 60715
Degree of Protection IP40, IP54 (with moisture-proof enclosure)
Terminals top and bottom Twin-purpose terminals
Terminal protection DGUV VS3, EN 50274
Degree of protection
>Integrated
IP40
Terminal cross-section
>Solid
1.5 - 35 mm2
Terminal cross-section
>Stranded
2 x 16 mm2
Terminal cross-section
>flexible
2 x 16 mm2
Terminal cross-section M5 (Pozidriv PZ2)
Thickness of busbar material 0.8 - 2 mm
Admissible ambient temperature range -25 … +40 °C
Permissible storage and transport temperatures -35 - +60 °C
Climatic proofing 25-55°C/90-95% relative humidity according to IEC 60068-2
Thickness of busbar material
>Material thickness
0.8 - 2 mm
Rated operational current for specified heat dissipation [In] 63 A
Heat dissipation per pole, current-dependent [Pvid] 0 W
Equipment heat dissipation, current-dependent [Pvid] 8.5 W
Static heat dissipation, non-current-dependent [Pvs] 0 W
Heat dissipation capacity [Pdiss] 0 W
Operating ambient temperature min. -25 °C
Operating ambient temperature max. +50 °C
10.2 Strength of materials and parts
>10.2.2 Corrosion resistance
Starting at 40 °C, the max. permissible continuous current decreases by 1.8% for every 1 °C
10.2 Strength of materials and parts
>10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard´s requirements.
10.2 Strength of materials and parts
>10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard´s requirements.
10.2 Strength of materials and parts
>10.2.3.3 Verification of resistance of insulating materials to abnormal heat and fire due to internal electric effects
Meets the product standard´s requirements.
10.2 Strength of materials and parts
>10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard´s requirements.
10.2 Strength of materials and parts
>10.2.5 Lifting
Meets the product standard´s requirements.
10.2 Strength of materials and parts
>10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2 Strength of materials and parts
>10.2.7 Inscriptions
Does not apply, since the entire switchgear needs to be evaluated.
10.3 Degree of protection of ASSEMBLIES Meets the product standard´s requirements.
10.4 Clearances and creepage distances Does not apply, since the entire switchgear needs to be evaluated.
10.5 Protection against electric shock Meets the product standard´s requirements.
10.6 Incorporation of switching devices and components Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections Does not apply, since the entire switchgear needs to be evaluated.
10.8 Connections for external conductors Is the panel builder´s responsibility.
10.9 Insulation properties
>10.9.2 Power-frequency electric strength
Is the panel builder´s responsibility.
10.9 Insulation properties
>10.9.3 Impulse withstand voltage
Is the panel builder´s responsibility.
10.9 Insulation properties
>10.9.4 Testing of enclosures made of insulating material
Is the panel builder´s responsibility.
10.10 Temperature rise Is the panel builder´s responsibility.
10.11 Short-circuit rating The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.12 Electromagnetic compatibility Is the panel builder´s responsibility. The specifications for the switchgear must be observed.
10.13 Mechanical function Is the panel builder´s responsibility. The specifications for the switchgear must be observed.
Number of poles The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
Rated voltage 4
Rated current 415 V
Rated fault current 63 A
Rated insulation voltage Ui 300 mA
Rated impulse withstand voltage Uimp 440 V
Mounting method 4 kV
Leakage current type DIN rail
Selective protection A
Short-time delayed tripping Yes
Short-circuit breaking capacity (Icw) No
Surge current capacity 10 kA
Frequency 5 kA
Additional equipment possible 50 Hz
With interlocking device Yes
Degree of protection (IP) Yes
Width in number of modular spacings IP20
Built-in depth 4
Ambient temperature during operating 70.5 mm
Pollution degree -25 - 40 °C
Connectable conductor cross section multi-wired 2
Connectable conductor cross section solid-core 1.5 - 16 mm²

As Mnelko, we are a reliable partner in industrial automation solutions, offering high-quality and innovative products with a wide product range to meet all the needs of your business. Our product portfolio consists of solutions designed based on the principles of high performance, durability, and efficiency to support modern industrial processes.
All of our products ensure maximum reliability even in challenging working conditions and help your business operations run smoothly. The products we offer in industrial automation, energy management, cabling solutions, and many other areas adapt flexibly to the needs of different sectors.
Additionally, our products are manufactured using only high-quality materials and comply with international standards. Through the solutions we provide, we enable our customers to increase operational efficiency and optimize costs. Our company closely follows technological advancements and continuously offers innovative products to help our customers gain a competitive advantage.
On each of our product pages, you can find comprehensive information about technical details, areas of use, and product features. You can explore all the products you need to strengthen your industrial processes on our website and enjoy a seamless purchasing experience.

Similar Products

PKNM-32/1N/C/003-F-MW
Eaton
HNB-C20/1N/003-A-HX
Eaton
HNB-C6/1N/003-A-HX
Eaton
HNB-C6/1N/003-HX
Eaton
HNB-B16/1N/003-A
Eaton