alt
alt

DIL-SWD-32-002
118561 DIL-SWD-32-002
118561

Function element, contactor, SmartWire-DT, DIL/MSC, manual/autoFunction element, Connection to SmartWire-DT: yes, For use with: DILM(C)7… - DILM(C)32…, DILM38…, DILA…, DILMP20…, DILMP32…, DILMP45…, MSC-D(E)-...(24VDC)

Function element, contactor, SmartWire-DT, DIL/MSC, manual/auto
Function element, Connection to SmartWire-DT: yes, For use with: DILM(C)7… - DILM(C)32…, DILM38…, DILA…, DILMP20…, DILMP32…, DILMP45…, MSC-D(E)-...(24VDC)

Product range SmartWire-DT slave
Accessories SWD contactor modules
Function For connecting the contactors to SmartWire-DT
Description Per contactor 1 module necessary.
1 electrical interlock for the surface mounting of reversing starters
Two self-supply digital inputs for potential-free contacts
1-0-A switch for manual or automatic operation.
Messages Contactor switching position, status of the digital inputs 1 and 2, 1-0-A switch position
Commands Contactor actuation
Connection to SmartWire-DT yes
For use with DILM(C)7… - DILM(C)32…
DILM38…
DILA…
DILMP20…
DILMP32…
DILMP45…
MSC-D(E)-...(24VDC)
Setting viaRotary switch
Notes

For current consumption of the contactor coils > 3 A (UL: 2 A) use additional power feed module.

A2 connections must not be bridged.

Wiring sets DILM 12-XRL and PKZM0-XRM12 cannot be used.

Connection terminals for electrical interlocking are not suitable for safety technology.

Standards IEC/EN 61131-2
EN 50178
IEC/EN 60947
Dimensions (W x H x D) 45 x 38 x 76 mm
Weight 0.04 kg
Mounting on DILM7…DILM38
Mounting position as DILM7 to DILM38
Protection type (IEC/EN 60529, EN50178, VBG 4) IP20
Vibrations (IEC/EN 61131-2:2008)
>Constant amplitude 3,5 mm
5 - 8.4 Hz
Vibrations (IEC/EN 61131-2:2008)
>Constant acceleration 1 g
8.4 - 150 Hz
Mechanical shock resistance (IEC/EN 60068-2-27) semi-sinusoidal 15 g/11 ms 9 Impacts
Drop to IEC/EN 60068-2-31 [Drop height] 50 mm
Free fall, packaged (IEC/EN 60068-2-32) 0.3 m
Overvoltage category II
Pollution degree 2
Electrostatic discharge (IEC/EN 61131-2:2008)
>Air discharge (Level 3)
8 kV
Electrostatic discharge (IEC/EN 61131-2:2008)
>Contact discharge (Level 2)
4 kV
Electromagnetic fields (IEC/EN 61131-2:2008)
>80 - 1000 MHz
10 V/m
Electromagnetic fields (IEC/EN 61131-2:2008)
>1.4 - 2 GHz
3 V/m
Electromagnetic fields (IEC/EN 61131-2:2008)
>2 - 2.7 GHz
1 V/m
Radio interference suppression (SmartWire-DT) EN 55011 Class A
Burst (IEC/EN 61131-2:2008, Level 3)
>CAN/DP bus cable
1 kV
Burst (IEC/EN 61131-2:2008, Level 3)
>SmartWire-DT cables
1 kV
Radiated RFI (IEC/EN 61131-2:2008, Level 3) 10 V
Operating ambient temperature (IEC 60068-2) - 25 - +60 °C
Condensation Take appropriate measures to prevent condensation
Storage - 30 - 70 °C
Relative humidity, non-condensing (IEC/EN 60068-2-30) 5 - 95 %
Station type SmartWire-DT slave
Address allocation automatic
SmartWire-DT status LED green/orange LED
Connections Plug, 8-pole
Plug connectors External device plug SWD4-8SF2-5
Current consumption 40 mA
Pick-up power
>for DILM 7-9
3 W
Pick-up power
>for DILM 12-15
4.5 W
Pick-up power
>for DILM 17-38
12 W
Pick-up current
>for DILM 7-9
125 mA
Pick-up current
>for DILM 12-15
188 mA
Pick-up current
>for DILM 17-38
500 mA
Holding power
>for DILM 7-9
3 W
Holding power
>for DILM 12-15
4.5 W
Holding power
>for DILM 17-38
0.5 W
Holding current
>for DILM 17-38
21 mA
Holding current
>for DILM 12-15
188 mA
Holding current
>for DILM 7-9
125 mA
Manual/automatic mode yes
Setting viaRotary switch
Number 2
Rated voltage [Ue ] 15 V DC
Input current at 1 signal, typical 3 mA
Potential isolation No
Cable length ≦ 2.8 m
Connection type Push in terminals
Solid 0.2 - 1.5 (AWG 24 - 16) mm2
Flexible with ferrule 0.25 - 1.5 mm2
Notes own supply
Minimum length 8 mm.
Rated operational current for specified heat dissipation [In] 0 A
Heat dissipation per pole, current-dependent [Pvid] 0 W
Equipment heat dissipation, current-dependent [Pvid] 0 W
Static heat dissipation, non-current-dependent [Pvs] 0.8 W
Heat dissipation capacity [Pdiss] 0 W
Operating ambient temperature min. -25 °C
Operating ambient temperature max. +60 °C
10.2 Strength of materials and parts
>10.2.2 Corrosion resistance
Meets the product standard´s requirements.
10.2 Strength of materials and parts
>10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard´s requirements.
10.2 Strength of materials and parts
>10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard´s requirements.
10.2 Strength of materials and parts
>10.2.3.3 Verification of resistance of insulating materials to abnormal heat and fire due to internal electric effects
Meets the product standard´s requirements.
10.2 Strength of materials and parts
>10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard´s requirements.
10.2 Strength of materials and parts
>10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
10.2 Strength of materials and parts
>10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2 Strength of materials and parts
>10.2.7 Inscriptions
Meets the product standard´s requirements.
10.3 Degree of protection of ASSEMBLIES Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances Meets the product standard´s requirements.
10.5 Protection against electric shock Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections Is the panel builder´s responsibility.
10.8 Connections for external conductors Is the panel builder´s responsibility.
10.9 Insulation properties
>10.9.2 Power-frequency electric strength
Is the panel builder´s responsibility.
10.9 Insulation properties
>10.9.3 Impulse withstand voltage
Is the panel builder´s responsibility.
10.9 Insulation properties
>10.9.4 Testing of enclosures made of insulating material
Is the panel builder´s responsibility.
10.10 Temperature rise The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating Is the panel builder´s responsibility. The specifications for the switchgear must be observed.
10.12 Electromagnetic compatibility Is the panel builder´s responsibility. The specifications for the switchgear must be observed.
10.13 Mechanical function The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
Supply voltage AC 50 Hz 0 - 0 V
Supply voltage AC 60 Hz 0 - 0 V
Supply voltage DC 15 - 15 V
Voltage type of supply voltage DC
Number of digital inputs 2
Number of digital outputs 1
Digital inputs configurable No
Digital outputs configurable No
Input current at signal 1 3 mA
Permitted voltage at input 15 - 15 V
Type of voltage (input voltage) DC
Type of digital output Other
Output current 0.5 A
Permitted voltage at output 20.4 - 28.8 V
Type of output voltage DC
Short-circuit protection, outputs available No
Number of HW-interfaces industrial Ethernet 0
Number of interfaces PROFINET 0
Number of HW-interfaces RS-232 0
Number of HW-interfaces RS-422 0
Number of HW-interfaces RS-485 0
Number of HW-interfaces serial TTY 0
Number of HW-interfaces parallel 0
Number of HW-interfaces Wireless 0
Number of HW-interfaces USB 0
Number of HW-interfaces other 1
With optical interface No
Supporting protocol for TCP/IP No
Supporting protocol for PROFIBUS No
Supporting protocol for CAN No
Supporting protocol for INTERBUS No
Supporting protocol for ASI No
Supporting protocol for KNX No
Supporting protocol for MODBUS No
Supporting protocol for Data-Highway No
Supporting protocol for DeviceNet No
Supporting protocol for SUCONET No
Supporting protocol for LON No
Supporting protocol for PROFINET IO No
Supporting protocol for PROFINET CBA No
Supporting protocol for SERCOS No
Supporting protocol for Foundation Fieldbus No
Supporting protocol for EtherNet/IP No
Supporting protocol for AS-Interface Safety at Work No
Supporting protocol for DeviceNet Safety No
Supporting protocol for INTERBUS-Safety No
Supporting protocol for PROFIsafe No
Supporting protocol for SafetyBUS p No
Supporting protocol for other bus systems Yes
Radio standard Bluetooth No
Radio standard WLAN 802.11 No
Radio standard GPRS No
Radio standard GSM No
Radio standard UMTS No
IO link master No
System accessory Yes
Degree of protection (IP) IP20
Type of electric connection Spring clamp connection
Time delay at signal exchange 10 - 84 ms
Fieldbus connection over separate bus coupler possible Yes
Rail mounting possible No
Wall mounting/direct mounting No
Front build in possible No
Rack-assembly possible No
Suitable for safety functions No
Category according to EN 954-1 1
SIL according to IEC 61508 None
Performance level acc. EN ISO 13849-1 None
Appendant operation agent (Ex ia) No
Appendant operation agent (Ex ib) No
Explosion safety category for gas None
Explosion safety category for dust None
Width 45 mm
Height 38 mm
Depth 81 mm
Product Standards IEC/EN 60947-4-1; UL 508; CSA-C22.2 No. 14-05; CE marking
UL File No. E29184
UL Category Control No. NKCR
CSA File No. 2324643
CSA Class No. 3211-07
North America Certification UL listed, CSA certified
Specially designed for North America No

As Mnelko, we are a reliable partner in industrial automation solutions, offering high-quality and innovative products with a wide product range to meet all the needs of your business. Our product portfolio consists of solutions designed based on the principles of high performance, durability, and efficiency to support modern industrial processes.
All of our products ensure maximum reliability even in challenging working conditions and help your business operations run smoothly. The products we offer in industrial automation, energy management, cabling solutions, and many other areas adapt flexibly to the needs of different sectors.
Additionally, our products are manufactured using only high-quality materials and comply with international standards. Through the solutions we provide, we enable our customers to increase operational efficiency and optimize costs. Our company closely follows technological advancements and continuously offers innovative products to help our customers gain a competitive advantage.
On each of our product pages, you can find comprehensive information about technical details, areas of use, and product features. You can explore all the products you need to strengthen your industrial processes on our website and enjoy a seamless purchasing experience.

Similar Products

DS7-34DSX200N0-D
Eaton
DS7-34DSX160N0-D
Eaton
DS7-34DSX135N0-D
Eaton
DS7-34DSX081N0-D
Eaton
NZM-XSWD-704
Eaton
DS7-34DSX100N0-D
Eaton
DS7-34DSX032N0-D
Eaton