2 safety contacts, STOP 0; 1 safety contact, STOP 11 Signalling outputSuitable for the signal processing of outputs with contact sensorsSuitable for signal processing of outputs connected to potentials (AOPDs), e.g. safety light grids/curtains
Replacement article number | 101211929 |
Product type description | SRB211ST/CC (V.2) |
Article number (order number) | 101210352 |
EAN (European Article Number) | 4030661444703 |
eCl@ss number, version 12.0 | 27-37-18-19 |
eCl@ss number, version 11.0 | 27-37-18-19 |
eCl@ss number, version 9.0 | 27-37-18-19 |
ETIM number, version 7.0 | EC001449 |
ETIM number, version 6.0 | EC001449 |
Available until | 31.12.2024 |
| TÜV IFA cULus CCC TILVA |
Standards | EN IEC 62061 EN ISO 13849-1 EN IEC 60947-5-1 EN IEC 60947-5-3 EN IEC 60947-5-5 EN IEC 61508 EN IEC 60204-1 EN IEC 60947-1 |
Climatic stress | EN 60068-2-78 |
Housing material | Glass-fibre reinforced thermoplastic, ventilated |
Gross weight | 250 g |
Electronic Fuse | Yes |
Wire breakage detection | Yes |
Cross-circuit detection | Yes |
Removable Terminals | Yes |
Start input | Yes |
Feedback circuit | Yes |
Automatic reset function | Yes |
Reset edge detection | Yes |
Earth connection detection | Yes |
Integral system diagnostics, status | Yes |
Number of LEDs | 6 |
Number of normally closed (NC) | 2 |
Number of safety contacts | 3 |
Number of Safety contacts, STOP 0 | 3 |
Number of Safety contacts, STOP 1 | 2 |
Number of signalling outputs | 1 |
Safety classification |
Standards | EN IEC 60947-5-1 EN IEC 61508 |
Stop-Category | 0 1 |
Safety classification - Relay outputs |
Performance Level, stop 0, up to | e |
Performance Level, stop 1, up to | d |
Category, Stop 0 | 4 |
Category, Stop 1 | 3 |
Diagnostic Coverage (DC) Level, Stop 0 | ≥ 99 % |
Diagnostic Coverage (DC) Level, Stop 1 | > 60 |
PFH value, Stop 0 | 2.00 x 10⁻⁸ /h |
PFH value, Stop 1 | 2.00 x 10⁻⁷ /h |
Safety Integrity Level (SIL), Stop 0, suitable for applications in | 3 |
Safety Integrity Level (SIL), Stop 1, suitable for applications in | 2 |
Mission time | 20 Year(s) |
Common Cause Failure (CCF), minimum | 65 |
PFD value | 5.30 x 10⁻⁵ |
PFD value | 5.30 x 10⁻⁵ |
Mechanical life, minimum | 10,000,000 Operations |
Mounting | Snaps onto standard DIN rail to EN 60715 |
Terminal designations | IEC/EN 60947-1 |
Termination | Cage clamp rigid or flexible |
Cable section, minimum | 0.25 mm² |
Cable section, maximum | 1.5 mm² |
Tightening torque of Clips | 0.6 Nm |
Width | 22.5 mm |
Height | 100 mm |
Depth | 121 mm |
Degree of protection of the enclosure | IP40 |
Degree of protection of the mounting space | IP54 |
Degree of protection of clips or terminals | IP20 |
Ambient temperature | -25 ... +60 °C |
Storage and transport temperature | -40 ... +85 °C |
Resistance to vibrations | 10...55 Hz, Amplitude 0.35 mm, ± 15 % |
Restistance to shock | 30 g / 11 ms |
Rated impulse withstand voltage Uimp | 4 kV |
Overvoltage category | III |
Degree of pollution | 2 |
Frequency range | 50 Hz 60 Hz |
Operating voltage | 24 VAC -15 % / +10 % |
Ripple voltage | 10 % |
Rated operating voltage | 24 VAC |
Rated operating voltage | 24 VDC |
Rated AC voltage for controls, 50 Hz, minimum | 20.4 VAC |
Rated control voltage at AC 50 Hz, maximum | 26.4 VAC |
Rated AC voltage for controls, 60 Hz, minimum | 20.4 VAC |
Rated control voltage at AC 60 Hz, maximum | 26.4 VAC |
Rated AC voltage for controls at DC minimum | 20.4 VDC |
Rated control voltage at DC, maximum | 28.8 VDC |
Electrical power consumption | 2.4 W |
Electrical power consumption | 5.9 VA |
Contact resistance, maximum | 0.1 Ω |
Note (Contact resistance) | in new state |
Drop-out delay in case of power failure, typically | 80 ms |
Drop-out delay in case of emergency, typically | 30 ms |
Pull-in delay at automatic start, maximum, typically | 250 ms |
Pull-in delay at RESET, typically | 20 ms |
Material of the contacts, electrical | AgSn0, Ag-Ni, self-cleaning, positive drive |
Voltage, Utilisation category AC-15 | 230 VAC |
Current, Utilisation category AC-15 | 6 A |
Voltage, Utilisation category DC-13 | 24 VDC |
Current, Utilisation category DC-13 | 6 A |
Switching capacity, minimum | 10 VDC |
Switching capacity, minimum | 10 mA |
Switching capacity, maximum | 250 VAC |
Switching capacity, maximum | 8 A |
Voltage, Utilisation category AC-15 | 230 VAC |
Current, Utilisation category AC-15 | 3 A |
Voltage, Utilisation category DC-13 | 24 VDC |
Current, Utilisation category DC-13 | 2 A |
Switching capacity, minimum | 10 VDC |
Switching capacity, minimum | 10 mA |
Switching capacity, maximum | 250 VAC |
Switching capacity, maximum | 6 A |
Conduction resistance, maximum | 40 Ω |
Voltage, Utilisation category DC-12 | 24 VDC |
Current, Utilisation category DC-12 | 0.1 A |
Switching capacity, maximum | 24 VDC |
Switching capacity, maximum | 2 A |
EMC rating | EMC-Directive |
Indicated operating states | Position relay K2 Position relay K1 Internal operating voltage Ui Position relay K3/K4 |
Note (applications) | Safety sensor Guard system Emergency-Stop button Pull-wire emergency stop switches Safety light curtain |
Note (General) | Inductive loads (e.g. contactors, relays, etc.) are to be suppressed by means of a suitable circuit. |
Note (Wiring diagram) | The wiring diagram is shown with guard doors closed and in de-energised condition. Automatic start: The automatic start is programmed by connecting the feedback circuit to the terminals X1/X3. If the feedback circuit is not required, establish a bridge. Input level: The example shows a 2-channel control of a guard door monitoring with two position switches, whereof one with positive break, external reset button (R) and feedback circuit (H2). The control recognises cross-short, cable break and earth leakages in the monitoring circuit. For 1-channel control, connect NC contact to S11/S12 and bridge S12/S22 Connect potential p-type outputs of safety light grids/curtains to S12/S22. The devices must have the same reference potential. The safety enabling circuit 37/38 conforms to EN 60204-1 for STOP Category 1. The safety enabling circuits 13/14 and 23/24 conform to EN 60204-1 for STOP Category 0. F1 = Hybrid fuse |
As Mnelko, we are a reliable partner in industrial automation solutions, offering high-quality and innovative products with a wide product range to meet all the needs of your business. Our product portfolio consists of solutions designed based on the principles of high performance, durability, and efficiency to support modern industrial processes.
All of our products ensure maximum reliability even in challenging working conditions and help your business operations run smoothly. The products we offer in industrial automation, energy management, cabling solutions, and many other areas adapt flexibly to the needs of different sectors.
Additionally, our products are manufactured using only high-quality materials and comply with international standards. Through the solutions we provide, we enable our customers to increase operational efficiency and optimize costs. Our company closely follows technological advancements and continuously offers innovative products to help our customers gain a competitive advantage.
On each of our product pages, you can find comprehensive information about technical details, areas of use, and product features. You can explore all the products you need to strengthen your industrial processes on our website and enjoy a seamless purchasing experience.