Delay unitOptional accessories for the circuit-breaker series NZM offers a comprehensive portfolio of application options for use world wide. The mounting is always flexible and easy thanks to the modular function groups. Notes: combination of separate delay unit and special releases. For use with emergency switching off devices in conjunction with Emergency switching off button. Not UL/CSA approved. voltage dips of less than the setting between 0.06-16 s do not cause disconnection of the NZM circuit-breaker or N switch-disconnector. Delay time can be set: 70 ms - 4 s. With external condenser: 30.000 µF ≧ 35 V to 8 s, 90.000 µF ≧ 35 V to 16 s. A special release is required. Cannot be installed simultaneously with separate NZM..-XHIV early-make auxiliary contact or NZM..-XA.. shunt release. Delay unit for separate installation. Fixing: top-hat rail or screws. For other operating voltages use a control transformer. Can be used for: NZM1(-4), 2(-4), 3(-4), 4(-4), N(N/O)1(-4), 2(-4), 3(-4), 4(-4), 50/60 Hz 220V-240V, 380V-440V, 480V-550V, DC/AC 24 V
Delay unit
Optional accessories for the circuit-breaker series NZM offers a comprehensive portfolio of application options for use world wide. The mounting is always flexible and easy thanks to the modular function groups. Notes: combination of separate delay unit and special releases. For use with emergency switching off devices in conjunction with Emergency switching off button. Not UL/CSA approved. voltage dips of less than the setting between 0.06-16 s do not cause disconnection of the NZM circuit-breaker or N switch-disconnector. Delay time can be set: 70 ms - 4 s. With external condenser: 30.000 µF ≧ 35 V to 8 s, 90.000 µF ≧ 35 V to 16 s. A special release is required. Cannot be installed simultaneously with separate NZM..-XHIV early-make auxiliary contact or NZM..-XA.. shunt release. Delay unit for separate installation. Fixing: top-hat rail or screws. For other operating voltages use a control transformer. Can be used for: NZM1(-4), 2(-4), 3(-4), 4(-4), N(N/O)1(-4), 2(-4), 3(-4), 4(-4), 50/60 Hz 220V-240V, 380V-440V, 480V-550V, DC/AC 24 V
Product range | Accessories |
Accessories | Undervoltage release |
Accessories | Undervoltage releases, off-delayed |
Standard/Approval | IEC |
Construction size | NZM1/2/3/4 |
Description | Delay unit for combination with special undervoltage releases. For use with emergency-stop devices in connection with an emergency-stop button. not UL/CSA approved Voltage dips of less than the setting between 0.06 – 16 s do not cause disconnection of the NZM circuit-breaker or N switch-disconnector. Delay time can be set from: 70 ms – 4 s. With additional external capacitor: 30,000 µF ≧ 35 V to 8 s, 90,000 µF ≧ 35 V to 16 s. A special release is required. Cannot be installed simultaneously with separate NZM...-XHIV early-make auxiliary contact or NZM...-XA... shunt release. Delay unit for separate installation. Fixing: top-hat rail or screws. For other operating voltages use a control transformer. |
Connection type | With bolt connection |
For use with | NZM1(-4), 2(-4), 3(-4), 4(-4) N(S)1(-4), 2(-4), 3(-4), 4(-4) 50/60 Hz 220 V - 240 V 380 V - 440 V 480 V - 550 V DC/AC 24 V |
Rated operational voltage [Ue] >Alternating voltage at 50/60 Hz [Ue] |
24, 220 - 550 V AC |
Rated operational voltage [Ue] >DC [Ue ] |
24 V DC |
Inrush current (peak value) [Ie ] | < 500 mA |
Power consumption | 50 VA |
Delay time [tsd ] | 70 - 4000 ms |
With additional external capacitor, 90.000 μF ≧ 35 V | 16 s |
With additional external capacitor, 30.000 μF ≧ 35 V | 8 s |
Terminal capacities >Solid or flexible conductor, with ferrule |
1 x (0,5 - 2,5) 2 x (0,5 - 1,5) mm2 |
Terminal capacities | 1 x (20 - 14) 2 x (20 - 16) AWG |
10.2 Strength of materials and parts >10.2.2 Corrosion resistance |
Meets the product standard´s requirements. |
10.2 Strength of materials and parts >10.2.3.1 Verification of thermal stability of enclosures |
Meets the product standard´s requirements. |
10.2 Strength of materials and parts >10.2.3.2 Verification of resistance of insulating materials to normal heat |
Meets the product standard´s requirements. |
10.2 Strength of materials and parts >10.2.3.3 Verification of resistance of insulating materials to abnormal heat and fire due to internal electric effects |
Meets the product standard´s requirements. |
10.2 Strength of materials and parts >10.2.4 Resistance to ultra-violet (UV) radiation |
Meets the product standard´s requirements. |
10.2 Strength of materials and parts >10.2.5 Lifting |
Does not apply, since the entire switchgear needs to be evaluated. |
10.2 Strength of materials and parts >10.2.6 Mechanical impact |
Does not apply, since the entire switchgear needs to be evaluated. |
10.2 Strength of materials and parts >10.2.7 Inscriptions |
Meets the product standard´s requirements. |
10.3 Degree of protection of ASSEMBLIES | Does not apply, since the entire switchgear needs to be evaluated. |
10.4 Clearances and creepage distances | Meets the product standard´s requirements. |
10.5 Protection against electric shock | Does not apply, since the entire switchgear needs to be evaluated. |
10.6 Incorporation of switching devices and components | Does not apply, since the entire switchgear needs to be evaluated. |
10.7 Internal electrical circuits and connections | Is the panel builder´s responsibility. |
10.8 Connections for external conductors | Is the panel builder´s responsibility. |
10.9 Insulation properties >10.9.2 Power-frequency electric strength |
Is the panel builder´s responsibility. |
10.9 Insulation properties >10.9.3 Impulse withstand voltage |
Is the panel builder´s responsibility. |
10.9 Insulation properties >10.9.4 Testing of enclosures made of insulating material |
Is the panel builder´s responsibility. |
10.10 Temperature rise | The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices. |
10.11 Short-circuit rating | Is the panel builder´s responsibility. The specifications for the switchgear must be observed. |
10.12 Electromagnetic compatibility | Is the panel builder´s responsibility. The specifications for the switchgear must be observed. |
10.13 Mechanical function | The device meets the requirements, provided the information in the instruction leaflet (IL) is observed. |
Rated control supply voltage Us at AC 50HZ | 24 - 550 V |
Rated control supply voltage Us at AC 60HZ | 24 - 550 V |
Rated control supply voltage Us at DC | 24 - 24 V |
Voltage type for actuating | AC/DC |
Type of electric connection | Screw connection |
Number of contacts as normally open contact | 0 |
Number of contacts as normally closed contact | 0 |
Number of contacts as change-over contact | 0 |
Delayed | Yes |
Suitable for power circuit breaker | Yes |
Suitable for off-load switch | Yes |
Suitable for motor safety switch | No |
Suitable for overload relay | No |
As Mnelko, we are a reliable partner in industrial automation solutions, offering high-quality and innovative products with a wide product range to meet all the needs of your business. Our product portfolio consists of solutions designed based on the principles of high performance, durability, and efficiency to support modern industrial processes.
All of our products ensure maximum reliability even in challenging working conditions and help your business operations run smoothly. The products we offer in industrial automation, energy management, cabling solutions, and many other areas adapt flexibly to the needs of different sectors.
Additionally, our products are manufactured using only high-quality materials and comply with international standards. Through the solutions we provide, we enable our customers to increase operational efficiency and optimize costs. Our company closely follows technological advancements and continuously offers innovative products to help our customers gain a competitive advantage.
On each of our product pages, you can find comprehensive information about technical details, areas of use, and product features. You can explore all the products you need to strengthen your industrial processes on our website and enjoy a seamless purchasing experience.