alt
alt

UVU-NZM
260154 UVU-NZM
260154

Delay unitOptional accessories for the circuit-breaker series NZM offers a comprehensive portfolio of application options for use world wide. The mounting is always flexible and easy thanks to the modular function groups. Notes: combination of separate delay unit and special releases. For use with emergency switching off devices in conjunction with Emergency switching off button. Not UL/CSA approved. voltage dips of less than the setting between 0.06-16 s do not cause disconnection of the NZM circuit-breaker or N switch-disconnector. Delay time can be set: 70 ms - 4 s. With external condenser: 30.000 µF ≧ 35 V to 8 s, 90.000 µF ≧ 35 V to 16 s. A special release is required. Cannot be installed simultaneously with separate NZM..-XHIV early-make auxiliary contact or NZM..-XA.. shunt release. Delay unit for separate installation. Fixing: top-hat rail or screws. For other operating voltages use a control transformer. Can be used for: NZM1(-4), 2(-4), 3(-4), 4(-4), N(N/O)1(-4), 2(-4), 3(-4), 4(-4), 50/60 Hz 220V-240V, 380V-440V, 480V-550V, DC/AC 24 V

Delay unit
Optional accessories for the circuit-breaker series NZM offers a comprehensive portfolio of application options for use world wide. The mounting is always flexible and easy thanks to the modular function groups. Notes: combination of separate delay unit and special releases. For use with emergency switching off devices in conjunction with Emergency switching off button. Not UL/CSA approved. voltage dips of less than the setting between 0.06-16 s do not cause disconnection of the NZM circuit-breaker or N switch-disconnector. Delay time can be set: 70 ms - 4 s. With external condenser: 30.000 µF ≧ 35 V to 8 s, 90.000 µF ≧ 35 V to 16 s. A special release is required. Cannot be installed simultaneously with separate NZM..-XHIV early-make auxiliary contact or NZM..-XA.. shunt release. Delay unit for separate installation. Fixing: top-hat rail or screws. For other operating voltages use a control transformer. Can be used for: NZM1(-4), 2(-4), 3(-4), 4(-4), N(N/O)1(-4), 2(-4), 3(-4), 4(-4), 50/60 Hz 220V-240V, 380V-440V, 480V-550V, DC/AC 24 V

Product range Accessories
Accessories Undervoltage release
Accessories Undervoltage releases, off-delayed
Standard/Approval IEC
Construction size NZM1/2/3/4
Description Delay unit for combination with special undervoltage releases.
For use with emergency-stop devices in connection with an emergency-stop button.
not UL/CSA approved
Voltage dips of less than the setting between 0.06 – 16 s do not cause disconnection of the NZM circuit-breaker or N switch-disconnector.
Delay time can be set from: 70 ms – 4 s.
With additional external capacitor: 30,000 µF ≧ 35 V to 8 s, 90,000 µF ≧ 35 V to 16 s.
A special release is required.
Cannot be installed simultaneously with separate NZM...-XHIV early-make auxiliary contact or NZM...-XA... shunt release.
Delay unit for separate installation. Fixing: top-hat rail or screws.
For other operating voltages use a control transformer.
Connection type With bolt connection
For use with NZM1(-4), 2(-4), 3(-4), 4(-4)
N(S)1(-4), 2(-4), 3(-4), 4(-4)

50/60 Hz
220 V - 240 V
380 V - 440 V
480 V - 550 V

DC/AC
24 V
Rated operational voltage [Ue]
>Alternating voltage at 50/60 Hz [Ue]
24, 220 - 550 V AC
Rated operational voltage [Ue]
>DC [Ue ]
24 V DC
Inrush current (peak value) [Ie ] < 500 mA
Power consumption 50 VA
Delay time [tsd ] 70 - 4000 ms
With additional external capacitor, 90.000 μF ≧ 35 V 16 s
With additional external capacitor, 30.000 μF ≧ 35 V 8 s
Terminal capacities
>Solid or flexible conductor, with ferrule
1 x (0,5 - 2,5)
2 x (0,5 - 1,5) mm2
Terminal capacities 1 x (20 - 14)
2 x (20 - 16) AWG
10.2 Strength of materials and parts
>10.2.2 Corrosion resistance
Meets the product standard´s requirements.
10.2 Strength of materials and parts
>10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard´s requirements.
10.2 Strength of materials and parts
>10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard´s requirements.
10.2 Strength of materials and parts
>10.2.3.3 Verification of resistance of insulating materials to abnormal heat and fire due to internal electric effects
Meets the product standard´s requirements.
10.2 Strength of materials and parts
>10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard´s requirements.
10.2 Strength of materials and parts
>10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
10.2 Strength of materials and parts
>10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2 Strength of materials and parts
>10.2.7 Inscriptions
Meets the product standard´s requirements.
10.3 Degree of protection of ASSEMBLIES Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances Meets the product standard´s requirements.
10.5 Protection against electric shock Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections Is the panel builder´s responsibility.
10.8 Connections for external conductors Is the panel builder´s responsibility.
10.9 Insulation properties
>10.9.2 Power-frequency electric strength
Is the panel builder´s responsibility.
10.9 Insulation properties
>10.9.3 Impulse withstand voltage
Is the panel builder´s responsibility.
10.9 Insulation properties
>10.9.4 Testing of enclosures made of insulating material
Is the panel builder´s responsibility.
10.10 Temperature rise The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating Is the panel builder´s responsibility. The specifications for the switchgear must be observed.
10.12 Electromagnetic compatibility Is the panel builder´s responsibility. The specifications for the switchgear must be observed.
10.13 Mechanical function The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
Rated control supply voltage Us at AC 50HZ 24 - 550 V
Rated control supply voltage Us at AC 60HZ 24 - 550 V
Rated control supply voltage Us at DC 24 - 24 V
Voltage type for actuating AC/DC
Type of electric connection Screw connection
Number of contacts as normally open contact 0
Number of contacts as normally closed contact 0
Number of contacts as change-over contact 0
Delayed Yes
Suitable for power circuit breaker Yes
Suitable for off-load switch Yes
Suitable for motor safety switch No
Suitable for overload relay No

As Mnelko, we are a reliable partner in industrial automation solutions, offering high-quality and innovative products with a wide product range to meet all the needs of your business. Our product portfolio consists of solutions designed based on the principles of high performance, durability, and efficiency to support modern industrial processes.
All of our products ensure maximum reliability even in challenging working conditions and help your business operations run smoothly. The products we offer in industrial automation, energy management, cabling solutions, and many other areas adapt flexibly to the needs of different sectors.
Additionally, our products are manufactured using only high-quality materials and comply with international standards. Through the solutions we provide, we enable our customers to increase operational efficiency and optimize costs. Our company closely follows technological advancements and continuously offers innovative products to help our customers gain a competitive advantage.
On each of our product pages, you can find comprehensive information about technical details, areas of use, and product features. You can explore all the products you need to strengthen your industrial processes on our website and enjoy a seamless purchasing experience.

Similar Products

NZMH2-4-VX250/VAR
Eaton
NZMH2-VX250-SVE
Eaton
NZMS2-4-VX250/VAR
Eaton
NZMS2-4-VX160
Eaton
NZMS2-MX220-SVE
Eaton
NZMS2-VX250-SVE
Eaton
NZMN2-4-VX160/VAR
Eaton
NZMN2-VX100-BT
Eaton