Product range |
Main switch maintenance switch Repair switch |
Part group reference |
T3 |
Stop Function |
Emergency switching off function |
Notes |
With red rotary handle and yellow locking ring |
Number of poles |
UL/CSA |
Degree of Protection |
7-pole |
Design |
IP65 |
Contact sequence |
|
Switching angle |
surface mounting |
Design number |
|
Function |
|
400 V [P] |
90 ° |
Rated uninterrupted current [Iu] |
8343 |
Note on rated uninterrupted current !u |
|
Number of contact units |
15 kW |
Standards |
32 A |
Climatic proofing |
Rated uninterrupted current Iu is specified for max. cross-section. |
Ambient temperature >Enclosed |
4 contact unit(s) |
Overvoltage category/pollution degree |
IEC/EN 60947, VDE 0660, IEC/EN 60204, CSA, UL Switch-disconnector according to IEC/EN 60947-3 |
Rated impulse withstand voltage [Uimp] |
Damp heat, constant, to IEC 60068-2-78 Damp heat, cyclic, to IEC 60068-2-30 |
Mechanical shock resistance |
-25 - +40 °C |
Mounting position |
III/3 |
Mechanical variables >Number of poles |
6000 V AC |
Electrical characteristics >Rated operational voltage [Ue] |
12 g |
Electrical characteristics >Rated uninterrupted current [Iu] |
As required |
Electrical characteristics >Note on rated uninterrupted current !u |
7-pole |
Load rating with intermittent operation, class 12 >AB 25 % DF |
690 V AC |
Load rating with intermittent operation, class 12 >AB 40 % DF |
32 A |
Load rating with intermittent operation, class 12 >AB 60 % DF |
Rated uninterrupted current Iu is specified for max. cross-section. |
Short-circuit rating >Fuse |
2 x Ie |
Rated short-time withstand current (1 s current) [Icw
] |
1.6 x Ie |
Note on rated short-time withstand current lcw |
1.3 x Ie |
Rated conditional short-circuit current [Iq] |
35 A gG/gL |
cos ϕ rated making capacity as per IEC 60947-3 |
650 Arms |
Rated breaking capacity cos ϕ to IEC 60947-3 >230 V |
Current for a time of 1 second |
Rated breaking capacity cos ϕ to IEC 60947-3 >400/415 V |
1 kA |
Rated breaking capacity cos ϕ to IEC 60947-3 >500 V |
320 A |
Rated breaking capacity cos ϕ to IEC 60947-3 >690 V |
260 A |
Safe isolation to EN 61140 >between the contacts |
260 A |
Safe isolation to EN 61140 >Current heat loss per contact at Ie |
240 A |
Safe isolation to EN 61140 >Current heat loss per auxiliary circuit at Ie (AC-15/230 V) |
170 A |
Lifespan, mechanical [Operations] |
440 V AC |
Maximum operating frequency [Operations/h] |
1.1 W |
AC >AC-3 >Rating, motor load switch [P] >220 V 230 V [P] |
1.1 CO |
AC >AC-3 >Rating, motor load switch [P] >230 V Star-delta [P] |
> 0.5 x 106 |
AC >AC-3 >Rating, motor load switch [P] >400 V 415 V [P] |
1200 |
AC >AC-3 >Rating, motor load switch [P] >400 V Star-delta [P] |
5.5 kW |
AC >AC-3 >Rating, motor load switch [P] >500 V [P] |
7.5 kW |
AC >AC-3 >Rating, motor load switch [P] >500 V Star-delta [P] |
11 kW |
AC >AC-3 >Rating, motor load switch [P] >690 V [P] |
15 kW |
AC >AC-3 >Rating, motor load switch [P] >690 V Star-delta [P] |
15 kW |
AC >AC-3 >Rated operational current motor load switch >230 V [Ie] |
18.5 kW |
AC >AC-3 >Rated operational current motor load switch >230 V star-delta [Ie] |
11 kW |
AC >AC-3 >Rated operational current motor load switch >400V 415 V [Ie] |
22 kW |
AC >AC-3 >Rated operational current motor load switch >400 V star-delta [Ie] |
23.7 A |
AC >AC-3 >Rated operational current motor load switch >500 V [Ie
] |
32 A |
AC >AC-3 >Rated operational current motor load switch >500 V star-delta [Ie
] |
23.7 A |
AC >AC-3 >Rated operational current motor load switch >690 V [Ie] |
32 A |
AC >AC-3 >Rated operational current motor load switch >690 V star-delta [Ie] |
23.7 A |
AC >AC-21A >Rated operational current switch >440 V [Ie] |
32 A |
AC >AC-23A >Motor rating AC-23A, 50 - 60 Hz [P] >230 V [P] |
14.7 A |
AC >AC-23A >Motor rating AC-23A, 50 - 60 Hz [P] >400 V 415 V [P] |
25.5 A |
AC >AC-23A >Motor rating AC-23A, 50 - 60 Hz [P] >500 V [P] |
32 A |
AC >AC-23A >Motor rating AC-23A, 50 - 60 Hz [P] >690 V [P] |
7.5 kW |
AC >AC-23A >Rated operational current motor load switch >230 V [Ie] |
15 kW |
AC >AC-23A >Rated operational current motor load switch >400 V 415 V [Ie] |
15 kW |
AC >AC-23A >Rated operational current motor load switch >500 V [Ie] |
15 kW |
AC >AC-23A >Rated operational current motor load switch >690 V [Ie] |
32 A |
DC >DC-1, Load-break switches L/R = 1 ms >Rated operational current [Ie] |
32 A |
DC >DC-1, Load-break switches L/R = 1 ms >Voltage per contact pair in series |
26.4 A |
DC >DC-21A [Ie
] >Rated operational current [Ie] |
17 A |
DC >DC-21A [Ie
] >Contacts |
25 A |
DC >DC-23A, motor load switch
L/R = 15 ms >24 V >Rated operational current [Ie] |
60 V |
DC >DC-23A, motor load switch
L/R = 15 ms >24 V >Contacts |
1 A |
DC >DC-23A, motor load switch
L/R = 15 ms >48 V >Rated operational current [Ie] |
1 Quantity |
DC >DC-23A, motor load switch
L/R = 15 ms >48 V >Contacts |
25 A |
DC >DC-23A, motor load switch
L/R = 15 ms >60 V >Rated operational current [Ie] |
1 Quantity |
DC >DC-23A, motor load switch
L/R = 15 ms >60 V >Contacts |
25 A |
DC >DC-23A, motor load switch
L/R = 15 ms >120 V >Rated operational current [Ie] |
2 Quantity |
DC >DC-23A, motor load switch
L/R = 15 ms >120 V >Contacts |
25 A |
DC >DC-23A, motor load switch
L/R = 15 ms >240 V >Rated operational current [Ie] |
3 Quantity |
DC >DC-23A, motor load switch
L/R = 15 ms >240 V >Contacts |
12 A |
DC >DC-13, Control switches L/R = 50 ms >Rated operational current [Ie] |
3 Quantity |
DC >DC-13, Control switches L/R = 50 ms >Voltage per contact pair in series |
5 A |
Control circuit reliability at 24 V DC, 10 mA [Fault probability] |
5 Quantity |
Solid or stranded |
20 A |
Flexible with ferrules to DIN 46228 |
24 V |
Terminal screw |
< 10 -5, < 1 fault in 100000 operations HF
|
Tightening torque for terminal screw |
1 x (1 - 6) 2 x (1 - 6) mm2
|
Notes |
1 x (0.75 - 4) 2 x (0.75 - 4) mm2 |
Contacts >Rated operational voltage [Ue] |
M4 |
Contacts >Rated uninterrupted current max. >Main conducting paths >General use |
1.6 Nm |
Contacts >Rated uninterrupted current max. >Auxiliary contacts >General Use [IU] |
B10d values as per EN ISO 13849-1, table C1 |
Contacts >Rated uninterrupted current max. >Auxiliary contacts >Pilot Duty |
600 V AC |
Switching capacity >Maximum motor rating >Single-phase >120 V AC |
25 A |
Switching capacity >Maximum motor rating >Single-phase >200 V AC |
10 A |
Switching capacity >Maximum motor rating >Single-phase >240 V AC |
A 600 P 600 |
Switching capacity >Maximum motor rating >Three-phase >200 V AC |
1.5 HP |
Switching capacity >Maximum motor rating >Three-phase >240 V AC |
3 HP |
Switching capacity >Maximum motor rating >Three-phase >480 V AC |
3 HP |
Switching capacity >Maximum motor rating >Three-phase >600 V AC |
3 HP |
Short Circuit Current Rating >Basic Rating |
3 HP |
Short Circuit Current Rating >max. Fuse |
7.5 HP |
Short Circuit Current Rating >High fault rating |
10 HP |
Short Circuit Current Rating >max. Fuse |
5 kA |
Terminal capacity >Solid or flexible conductor with ferrule |
40 A |
Terminal capacity >Terminal screw |
10 kA |
Terminal capacity >Tightening torque |
40, Class J A |
Rated operational current for specified heat dissipation [In] |
14 - 10 AWG |
Heat dissipation per pole, current-dependent [Pvid] |
M4 |
Equipment heat dissipation, current-dependent [Pvid] |
17.7 lb-in |
Static heat dissipation, non-current-dependent [Pvs] |
32 A |
Heat dissipation capacity [Pdiss] |
1.1 W |
Operating ambient temperature min. |
0 W |
Operating ambient temperature max. |
0 W |
10.2 Strength of materials and parts >10.2.2 Corrosion resistance |
0 W |
10.2 Strength of materials and parts >10.2.3.1 Verification of thermal stability of enclosures |
-25 °C |
10.2 Strength of materials and parts >10.2.3.2 Verification of resistance of insulating materials to normal heat |
+40 °C |
10.2 Strength of materials and parts >10.2.3.3 Verification of resistance of insulating materials to abnormal heat and fire due to internal electric effects |
Meets the product standard´s requirements. |
10.2 Strength of materials and parts >10.2.4 Resistance to ultra-violet (UV) radiation |
Meets the product standard´s requirements. |
10.2 Strength of materials and parts >10.2.5 Lifting |
Meets the product standard´s requirements. |
10.2 Strength of materials and parts >10.2.6 Mechanical impact |
Meets the product standard´s requirements. |
10.2 Strength of materials and parts >10.2.7 Inscriptions |
UV resistance only in connection with protective shield. |
10.3 Degree of protection of ASSEMBLIES |
Does not apply, since the entire switchgear needs to be evaluated. |
10.4 Clearances and creepage distances |
Does not apply, since the entire switchgear needs to be evaluated. |
10.5 Protection against electric shock |
Meets the product standard´s requirements. |
10.6 Incorporation of switching devices and components |
Does not apply, since the entire switchgear needs to be evaluated. |
10.7 Internal electrical circuits and connections |
Meets the product standard´s requirements. |
10.8 Connections for external conductors |
Does not apply, since the entire switchgear needs to be evaluated. |
10.9 Insulation properties >10.9.2 Power-frequency electric strength |
Does not apply, since the entire switchgear needs to be evaluated. |
10.9 Insulation properties >10.9.3 Impulse withstand voltage |
Is the panel builder´s responsibility. |
10.9 Insulation properties >10.9.4 Testing of enclosures made of insulating material |
Is the panel builder´s responsibility. |
10.10 Temperature rise |
Is the panel builder´s responsibility. |
10.11 Short-circuit rating |
Is the panel builder´s responsibility. |
10.12 Electromagnetic compatibility |
Is the panel builder´s responsibility. |
10.13 Mechanical function |
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices. |
Version as main switch |
Is the panel builder´s responsibility. The specifications for the switchgear must be observed. |
Version as maintenance-/service switch |
Is the panel builder´s responsibility. The specifications for the switchgear must be observed. |
Version as safety switch |
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed. |
Version as emergency stop installation |
Yes |
Version as reversing switch |
Yes |
Number of switches |
No |
Max. rated operation voltage Ue AC |
Yes |
Rated operating voltage |
No |
Rated permanent current Iu |
1 |
Rated permanent current at AC-23, 400 V |
690 V |
Rated permanent current at AC-21, 400 V |
690 - 690 V |
Rated operation power at AC-3, 400 V |
32 A |
Rated short-time withstand current lcw |
32 A |
Rated operation power at AC-23, 400 V |
32 A |
Switching power at 400 V |
11 kW |
Conditioned rated short-circuit current Iq |
0.65 kA |
Number of poles |
15 kW |
Number of auxiliary contacts as normally closed contact |
15 kW |
Number of auxiliary contacts as normally open contact |
1 kA |
Number of auxiliary contacts as change-over contact |
7 |
Motor drive optional |
0 |
Motor drive integrated |
0 |
Voltage release optional |
0 |
Device construction |
No |
Suitable for ground mounting |
No |
Suitable for front mounting 4-hole |
No |
Suitable for front mounting centre |
Complete device in housing |
Suitable for distribution board installation |
Yes |
Suitable for intermediate mounting |
No |
Colour control element |
No |
Type of control element |
No |
Interlockable |
No |
Type of electrical connection of main circuit |
Red |
Degree of protection (IP), front side |
Door coupling rotary drive |
Degree of protection (NEMA) |
Yes |
Product Standards |
Screw connection |
UL File No. |
IP65 |
UL Category Control No. |
12 |
CSA File No. |
UL 60947-4-1;CSA - C22.2 No. 60947-4-1-14; CSA-C22.2 No. 94; IEC/EN 60947-3; CE marking |
CSA Class No. |
E36332 |
North America Certification |
NLRV |
Specially designed for North America |
12528 |
Suitable for |
3211-07 |
Degree of Protection |
UL listed, CSA certified |