Circuit-breaker, 3p, 50ACircuit-breaker NZM1, 3 pole, Switching capacity 400/415 V 50 Hz( Icu ): 50 kA, Rated current = rated uninterrupted current Rated current = rated uninterrupted current( In = Iu ): 50 A, Installation type: Fixed, Box terminal, Standard/Approval: IEC, Protective function: System and cable protection
Circuit-breaker, 3p, 50A
Circuit-breaker NZM1, 3 pole, Switching capacity 400/415 V 50 Hz( Icu ): 50 kA, Rated current = rated uninterrupted current Rated current = rated uninterrupted current( In = Iu ): 50 A, Installation type: Fixed, Box terminal, Standard/Approval: IEC, Protective function: System and cable protection
Product range | Circuit-breaker | |||
Protective function | System and cable protection | |||
Standard/Approval | IEC | |||
Installation type | Fixed | |||
Release system | Thermomagnetic release | |||
Construction size | NZM1 | |||
Number of poles | 3 pole | |||
Standard equipment | Box terminal | |||
400/415 V 50 Hz [Icu ] | ||||
Rated current = rated uninterrupted current [In = Iu] | 50 kA | |||
Overload trip [Ir
] 40 - 50 A
|
||||
Short-circuit releases [Irm ] | 50 A | |||
Standards | ||||
Protection against direct contact | 40 - 50 A | |||
Climatic proofing | 6 - 10 | |||
Ambient temperature >Ambient temperature, storage |
300 - 500 A | |||
Ambient temperature >Operation |
||||
Mechanical shock resistance (10 ms half-sinusoidal shock) according to IEC 60068-2-27 | IEC/EN 60947 | |||
Safe isolation to EN 61140 >Between auxiliary contacts and main contacts |
Finger and back of hand proof to VDE 0106 Part 100 | |||
Safe isolation to EN 61140 >between the auxiliary contacts |
Damp heat, constant, to IEC 60068-2-78 Damp heat, cyclic, to IEC 60068-2-30 |
|||
Mounting position | - 40 - + 70 °C | |||
Direction of incoming supply | -25 - +70 °C | |||
Degree of protection >Device |
20 (half-sinusoidal shock 20 ms) g | |||
Degree of protection >Enclosures |
500 V AC | |||
Degree of protection >Terminations |
300 V AC | |||
Other technical data (sheet catalogue) | ||||
Rated current = rated uninterrupted current [In = Iu] | as required | |||
Rated surge voltage invariability [Uimp
] >Main contacts |
In the operating controls area: IP20 (basic degree of protection) | |||
Rated surge voltage invariability [Uimp
] >Auxiliary contacts |
With insulating surround: IP40 With door coupling rotary handle: IP66 |
|||
Rated operational voltage [Ue] | Tunnel terminal: IP10 Phase isolator and strip terminal: IP00 |
|||
Rated operational voltage [Ue] | Temperature dependency, Derating | |||
Overvoltage category/pollution degree | ||||
Rated insulation voltage [Ui ] | 50 A | |||
Use in unearthed supply systems | 6000 V | |||
Rated short-circuit making capacity [Icm
] >240 V [Icm ] |
6000 V | |||
Rated short-circuit making capacity [Icm
] >400/415 V [Icm ] |
690 V AC | |||
Rated short-circuit making capacity [Icm
] >440 V 50/60 Hz [Icm ] |
450 V DC | |||
Rated short-circuit making capacity [Icm
] >525 V 50/60 Hz [Icm ] |
The following settings are required in order to ensure correct tripping: The fast-response release will take longer to respond when used for DC applications. Because of this, the setting on the trip block inscription, which is specified for AC currents, must be set to a lower value for DC currents. DC correction factor for instantaneous release response value: o NZM1: 1.25 o NZM2: 1.35 o NZM3: 1.45 Example: NZM3 Ie = 500A. Desired DC tripping current: 10 * Ie = 5000A. Calculation: • Desired DC value / correction factor = AC setting on trip block • 5000A / 1.45 = 3448 A ~ 7 * Ie = Value that needs to be set on the trip block Permitted circuit configurations: |
|||
Rated short-circuit making capacity [Icm
] >690 V 50/60 H [Ic] |
III/3 | |||
Rated short-circuit breaking capacity Icn [Icn
] >Icu to IEC/EN 60947 test cycle O-t-CO [Icu] >240 V 50/60 Hz [Icu ] |
690 V | |||
Rated short-circuit breaking capacity Icn [Icn
] >Icu to IEC/EN 60947 test cycle O-t-CO [Icu] >400/415 V 50/60 Hz [Icu ] |
≦ 690 V | |||
Rated short-circuit breaking capacity Icn [Icn
] >Icu to IEC/EN 60947 test cycle O-t-CO [Icu] >440 V 50/60 Hz [Icu ] |
||||
Rated short-circuit breaking capacity Icn [Icn
] >Icu to IEC/EN 60947 test cycle O-t-CO [Icu] >525 V 50/60 Hz [Icu ] |
187 kA | |||
Rated short-circuit breaking capacity Icn [Icn
] >Icu to IEC/EN 60947 test cycle O-t-CO [Icu] >690 V 50/60 Hz [Icu ] |
105 kA | |||
Rated short-circuit breaking capacity Icn [Icn
] >Icu to IEC/EN 60947 test cycle O-t-CO [Icu] >500 V DC [Icu] |
74 kA | |||
Rated short-circuit breaking capacity Icn [Icn
] >Ics to IEC/EN 60947 test cycle O-t-CO-t-CO [Ics] >240 V 50/60 Hz [Ics ] |
40 kA | |||
Rated short-circuit breaking capacity Icn [Icn
] >Ics to IEC/EN 60947 test cycle O-t-CO-t-CO [Ics] >400/415 V 50/60 Hz [Ics ] |
17 kA | |||
Rated short-circuit breaking capacity Icn [Icn
] >Ics to IEC/EN 60947 test cycle O-t-CO-t-CO [Ics] >440 V 50/60 Hz [Ics ] |
85 kA | |||
Rated short-circuit breaking capacity Icn [Icn
] >Ics to IEC/EN 60947 test cycle O-t-CO-t-CO [Ics] >525 V 50/60 Hz [Ics ] |
50 kA | |||
Rated short-circuit breaking capacity Icn [Icn
] >Ics to IEC/EN 60947 test cycle O-t-CO-t-CO [Ics] >690 V 50/60 Hz [Ics] |
35 kA | |||
Rated short-circuit breaking capacity Icn [Icn
] >Ics to IEC/EN 60947 test cycle O-t-CO-t-CO [Ics] >450 V DC [Ics] |
20 kA | |||
Rated short-circuit breaking capacity Icn [Icn ] | 10 kA | |||
Utilization category to IEC/EN 60947-2 | 15 kA | |||
Lifespan, mechanical(of which max. 50 % trip by shunt/undervoltage release) [Operations] | 85 kA | |||
Lifespan, electrical >AC-1 >400 V 50/60 Hz [Operations] |
50 kA | |||
Lifespan, electrical >AC-1 >415 V 50/60 Hz [Operations] |
35 kA | |||
Lifespan, electrical >AC-1 >690 V 50/60 Hz [Operations] |
10 kA | |||
Lifespan, electrical >DC-1 >450 V DC [Operations] |
7.5 kA | |||
Lifespan, electrical >Max. operating frequency |
15 kA | |||
Total break time at short-circuit | Maximum back-up fuse, if the expected short-circuit currents at the installation location exceed the switching capacity of the circuit-breaker. | |||
Standard equipment | A | |||
Optional accessories | 20000 | |||
Round copper conductor >Box terminal >Solid |
10000 | |||
Round copper conductor >Box terminal >Stranded |
10000 | |||
Round copper conductor >Box terminal |
7500 | |||
Round copper conductor >Tunnel terminal >Solid |
10000 | |||
Round copper conductor >Tunnel terminal >Stranded >1-hole |
120 Ops/h | |||
Round copper conductor >Bolt terminal and rear-side connection >Direct on the switch >Solid |
< 10 ms | |||
Round copper conductor >Bolt terminal and rear-side connection >Direct on the switch >Stranded |
||||
Round copper conductor >Bolt terminal and rear-side connection >Direct on the switch |
Box terminal | |||
Al circular conductor >Tunnel terminal >Solid |
Screw connection Tunnel terminal connection on rear |
|||
Al circular conductor >Tunnel terminal >Stranded >Stranded |
1 x (10 - 16) 2 x (6 - 16) mm2 |
|||
Al circular conductor >Bolt terminal and rear-side connection >Direct on the switch >Solid |
1 x (10 - 70) 3) 2 x (6-25) mm2 |
|||
Al circular conductor >Bolt terminal and rear-side connection >Direct on the switch >Stranded |
3) Up to 95 mm² can be connected depending on the cable manufacturer. | |||
Cu strip (number of segments x width x segment thickness) >Box terminal [min.] |
1 x 16 mm2 | |||
Cu strip (number of segments x width x segment thickness) >Box terminal [max.] |
1 x (25 - 95) mm2 | |||
Copper busbar (width x thickness) [mm] >Bolt terminal and rear-side connection >Screw connection |
1 x (10 - 16) 2 x (6 - 16) mm2 |
|||
Copper busbar (width x thickness) [mm] >Bolt terminal and rear-side connection >Direct on the switch [min.] |
1 x (10 - 70) 3) 2 x 25 mm2 |
|||
Copper busbar (width x thickness) [mm] >Bolt terminal and rear-side connection >Direct on the switch [max.] |
3) Up to 95 mm² can be connected depending on the cable manufacturer. | |||
Control cables | 1 x 16 mm2 | |||
Rated operational current for specified heat dissipation [In] | 1 x (25 - 95) mm2 | |||
Equipment heat dissipation, current-dependent [Pvid] | 1 x (10 - 16) 2 x (10 - 16) mm2 |
|||
Operating ambient temperature min. | 1 x (25 - 35) 2 x (25 - 35) mm2 |
|||
Operating ambient temperature max. | 2 x 9 x 0.8 mm | |||
10.2 Strength of materials and parts >10.2.2 Corrosion resistance |
9 x 9 x 0.8 mm | |||
10.2 Strength of materials and parts >10.2.3.1 Verification of thermal stability of enclosures |
M6 | |||
10.2 Strength of materials and parts >10.2.3.2 Verification of resistance of insulating materials to normal heat |
12 x 5 mm | |||
10.2 Strength of materials and parts >10.2.3.3 Verification of resistance of insulating materials to abnormal heat and fire due to internal electric effects |
16 x 5 mm | |||
10.2 Strength of materials and parts >10.2.4 Resistance to ultra-violet (UV) radiation |
1 x (0.75 - 2.5) 2 x (0.75 - 1.5) mm2 |
|||
10.2 Strength of materials and parts >10.2.5 Lifting |
||||
10.2 Strength of materials and parts >10.2.6 Mechanical impact |
50 A | |||
10.2 Strength of materials and parts >10.2.7 Inscriptions |
13.2 W | |||
10.3 Degree of protection of ASSEMBLIES | -25 °C | |||
10.4 Clearances and creepage distances | +70 °C | |||
10.5 Protection against electric shock | ||||
10.6 Incorporation of switching devices and components | Meets the product standard´s requirements. | |||
10.7 Internal electrical circuits and connections | Meets the product standard´s requirements. | |||
10.8 Connections for external conductors | Meets the product standard´s requirements. | |||
10.9 Insulation properties >10.9.2 Power-frequency electric strength |
Meets the product standard´s requirements. | |||
10.9 Insulation properties >10.9.3 Impulse withstand voltage |
Meets the product standard´s requirements. | |||
10.9 Insulation properties >10.9.4 Testing of enclosures made of insulating material |
Does not apply, since the entire switchgear needs to be evaluated. | |||
10.10 Temperature rise | Does not apply, since the entire switchgear needs to be evaluated. | |||
10.11 Short-circuit rating | Meets the product standard´s requirements. | |||
10.12 Electromagnetic compatibility | Does not apply, since the entire switchgear needs to be evaluated. | |||
10.13 Mechanical function | Meets the product standard´s requirements. | |||
Rated permanent current Iu | Does not apply, since the entire switchgear needs to be evaluated. | |||
Rated voltage | Does not apply, since the entire switchgear needs to be evaluated. | |||
Rated short-circuit breaking capacity lcu at 400 V, 50 Hz | Is the panel builder´s responsibility. | |||
Overload release current setting | Is the panel builder´s responsibility. | |||
Adjustment range short-term delayed short-circuit release | Is the panel builder´s responsibility. | |||
Adjustment range undelayed short-circuit release | Is the panel builder´s responsibility. | |||
Integrated earth fault protection | Is the panel builder´s responsibility. | |||
Type of electrical connection of main circuit | The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices. | |||
Device construction | Is the panel builder´s responsibility. The specifications for the switchgear must be observed. | |||
Suitable for DIN rail (top hat rail) mounting | Is the panel builder´s responsibility. The specifications for the switchgear must be observed. | |||
DIN rail (top hat rail) mounting optional | The device meets the requirements, provided the information in the instruction leaflet (IL) is observed. | |||
Number of auxiliary contacts as normally closed contact | ||||
Number of auxiliary contacts as normally open contact | ||||
Number of auxiliary contacts as change-over contact | 50 A | |||
With switched-off indicator | 690 - 690 V | |||
With under voltage release | 50 kA | |||
Number of poles | 40 - 50 A | |||
Position of connection for main current circuit | 0 - 0 A | |||
Type of control element | 300 - 500 A | |||
Complete device with protection unit | No | |||
Motor drive integrated | Frame clamp | |||
Motor drive optional | Built-in device fixed built-in technique | |||
Degree of protection (IP) | No | |||
Characteristic curve | Yes | |||
Characteristic curve | 0 | |||
Characteristic curve | 0 |
As Mnelko, we are a reliable partner in industrial automation solutions, offering high-quality and innovative products with a wide product range to meet all the needs of your business. Our product portfolio consists of solutions designed based on the principles of high performance, durability, and efficiency to support modern industrial processes.
All of our products ensure maximum reliability even in challenging working conditions and help your business operations run smoothly. The products we offer in industrial automation, energy management, cabling solutions, and many other areas adapt flexibly to the needs of different sectors.
Additionally, our products are manufactured using only high-quality materials and comply with international standards. Through the solutions we provide, we enable our customers to increase operational efficiency and optimize costs. Our company closely follows technological advancements and continuously offers innovative products to help our customers gain a competitive advantage.
On each of our product pages, you can find comprehensive information about technical details, areas of use, and product features. You can explore all the products you need to strengthen your industrial processes on our website and enjoy a seamless purchasing experience.