alt
alt

NZMH3-S400-SVE
168918 NZMH3-S400-SVE
168918

Circuit-breaker, 3p, 400A, withdrawable unitSeries NZM circuit-breakers cover all application cases with just four compact sizes and are suitable for the IEC market. Installation is always flexible thanks to the use of modular function groups.

Circuit-breaker, 3p, 400A, withdrawable unit
Series NZM circuit-breakers cover all application cases with just four compact sizes and are suitable for the IEC market. Installation is always flexible thanks to the use of modular function groups.

Description Motor protection in conjunction with overload relay
With short-circuit release
Without overload release Ir
IEC/EN 60947-4-1, IEC/EN 60947-2

The circuit-breaker fulfills all requirements for AC-3 switching category.

Rated current = rated uninterrupted current [In = Iu] 400 A
400/415 V 50 Hz [Icu ] 150 kA
Short-circuit releases [Irm ]
>Non-delayed [Ii = In x …]
7 - 12.5
380 V 400 V [P] 200 kW
400 V [Ie ] 349 A
Ambient temperature
>Ambient temperature, storage
- 40 - + 70 °C
Ambient temperature
>Operation
-25 - +70 °C
Rated current = rated uninterrupted current [In = Iu] 400 A
Rated short-circuit breaking capacity Icn [Icn ]
>Icu to IEC/EN 60947 test cycle O-t-CO [Icu]
>400/415 V 50/60 Hz [Icu ]
150 kA
Rated short-circuit breaking capacity Icn [Icn ]
>Icu to IEC/EN 60947 test cycle O-t-CO [Icu]
>500 V DC [Icu]
70 kA
Rated short-circuit breaking capacity Icn [Icn ]
>Icu to IEC/EN 60947 test cycle O-t-CO [Icu]
>750 V DC [Icu]
70 kA
Rated short-circuit breaking capacity Icn [Icn ]
>Ics to IEC/EN 60947 test cycle O-t-CO-t-CO [Ics]
>500 V DC [Ics]
70 kA
Rated short-circuit breaking capacity Icn [Icn ]
>Ics to IEC/EN 60947 test cycle O-t-CO-t-CO [Ics]
>750 V DC [Ics]
70 kA
Rated operational current for specified heat dissipation [In] 400 A
Equipment heat dissipation, current-dependent [Pvid] 72.48 W
Operating ambient temperature min. -25 °C
Operating ambient temperature max. +70 °C
10.2 Strength of materials and parts
>10.2.2 Corrosion resistance
Meets the product standard´s requirements.
10.2 Strength of materials and parts
>10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard´s requirements.
10.2 Strength of materials and parts
>10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard´s requirements.
10.2 Strength of materials and parts
>10.2.3.3 Verification of resistance of insulating materials to abnormal heat and fire due to internal electric effects
Meets the product standard´s requirements.
10.2 Strength of materials and parts
>10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard´s requirements.
10.2 Strength of materials and parts
>10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
10.2 Strength of materials and parts
>10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2 Strength of materials and parts
>10.2.7 Inscriptions
Meets the product standard´s requirements.
10.3 Degree of protection of ASSEMBLIES Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances Meets the product standard´s requirements.
10.5 Protection against electric shock Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections Is the panel builder´s responsibility.
10.8 Connections for external conductors Is the panel builder´s responsibility.
10.9 Insulation properties
>10.9.2 Power-frequency electric strength
Is the panel builder´s responsibility.
10.9 Insulation properties
>10.9.3 Impulse withstand voltage
Is the panel builder´s responsibility.
10.9 Insulation properties
>10.9.4 Testing of enclosures made of insulating material
Is the panel builder´s responsibility.
10.10 Temperature rise The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating Is the panel builder´s responsibility. The specifications for the switchgear must be observed.
10.12 Electromagnetic compatibility Is the panel builder´s responsibility. The specifications for the switchgear must be observed.
10.13 Mechanical function The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
Overload release current setting 0 - 0 A
Adjustment range undelayed short-circuit release 7 - 12.5 A
With thermal protection No
Phase failure sensitive No
Switch off technique Magnetic
Rated operating voltage 690 - 690 V
Rated permanent current Iu 400 A
Rated operation power at AC-3, 230 V 132 kW
Rated operation power at AC-3, 400 V 200 kW
Type of electrical connection of main circuit Other
Type of control element Rocker lever
Device construction Built-in device plug-in technique
With integrated auxiliary switch No
With integrated under voltage release No
Number of poles 3
Rated short-circuit breaking capacity lcu at 400 V, AC 150 kA
Degree of protection (IP) IP20
Height 215.2 mm
Width 140 mm
Depth 335 mm
Characteristic curve 1230DIA-43

As Mnelko, we are a reliable partner in industrial automation solutions, offering high-quality and innovative products with a wide product range to meet all the needs of your business. Our product portfolio consists of solutions designed based on the principles of high performance, durability, and efficiency to support modern industrial processes.
All of our products ensure maximum reliability even in challenging working conditions and help your business operations run smoothly. The products we offer in industrial automation, energy management, cabling solutions, and many other areas adapt flexibly to the needs of different sectors.
Additionally, our products are manufactured using only high-quality materials and comply with international standards. Through the solutions we provide, we enable our customers to increase operational efficiency and optimize costs. Our company closely follows technological advancements and continuously offers innovative products to help our customers gain a competitive advantage.
On each of our product pages, you can find comprehensive information about technical details, areas of use, and product features. You can explore all the products you need to strengthen your industrial processes on our website and enjoy a seamless purchasing experience.

Similar Products

NZMH2-4-VX250/VAR
Eaton
NZMH2-VX250-SVE
Eaton
NZMS2-4-VX250/VAR
Eaton
NZMS2-4-VX160
Eaton
NZMS2-MX220-SVE
Eaton
NZMS2-VX250-SVE
Eaton
NZMN2-4-VX160/VAR
Eaton
NZMN2-VX100-BT
Eaton