Circuit-breaker, 3p, 220ACircuit-breakers of the NZM..-ME series cover all applications with only four compact sizes and are suitable for the IEC market. The mounting is always flexible due to the modular function groups. With electronic release for the motor protection with phase failure sensitivity. Notes: IEC/EN 60947-4-1, IEC/EN 60947-2, r.m.s. value measurement and thermal memory, adjustable time delay setting to overcome current peaks tr:2-20 at 6xIr as well as infinity (without overload release)
Circuit-breaker, 3p, 220A
Circuit-breakers of the NZM..-ME series cover all applications with only four compact sizes and are suitable for the IEC market. The mounting is always flexible due to the modular function groups. With electronic release for the motor protection with phase failure sensitivity. Notes: IEC/EN 60947-4-1, IEC/EN 60947-2, r.m.s. value measurement and thermal memory, adjustable time delay setting to overcome current peaks tr:2-20 at 6xIr as well as infinity (without overload release)
Product range | Circuit-breaker |
Protective function | Motor protection |
Standard/Approval | |
Installation type | IEC |
Release system | Fixed |
Construction size | Electronic release |
Description | NZM3 |
Number of poles | IEC/EN 60947-4-1, IEC/EN 60947-2 The circuit-breaker fulfills all requirements for AC-3 switching category. R.m.s. value measurement and “thermal memory” Adjustable time delay setting to overcome current peaks tr at 6 x Ir also infinity (without overload releases) All AC-3 rating data applies to direct switching by the circuit-breaker under normal operating conditions. If, for example, a contactor takes over AC-3 switching under normal operating conditions, the full rated uninterrupted current applies to the circuit-breaker, In = Iu. |
Standard equipment | 3 pole |
400/415 V 50 Hz [Icu ] | Screw connection |
Rated current = rated uninterrupted current [In = Iu] | 150 kA |
Overload trip [Ir
] 110 - 220 A
|
220 A |
380 V 400 V [P] | 110 - 220 A |
660 V 690 V [P] | 2 - 14 |
400 V [P] | 110 kW |
660 V 690 V [P] | 200 kW |
400 V [Ie ] | 110 kW |
690 V | 200 kW |
Standards | 196 A |
Protection against direct contact | 202 A |
Climatic proofing | IEC/EN 60947 |
Ambient temperature >Ambient temperature, storage |
Finger and back of hand proof to VDE 0106 Part 100 |
Ambient temperature >Operation |
Damp heat, constant, to IEC 60068-2-78 Damp heat, cyclic, to IEC 60068-2-30 |
Mechanical shock resistance (10 ms half-sinusoidal shock) according to IEC 60068-2-27 | - 40 - + 70 °C |
Safe isolation to EN 61140 >Between auxiliary contacts and main contacts |
-25 - +70 °C |
Safe isolation to EN 61140 >between the auxiliary contacts |
20 (half-sinusoidal shock 20 ms) g |
Weight | 500 V AC |
Mounting position | 300 V AC |
Direction of incoming supply | 6.34 kg |
Degree of protection >Device |
|
Degree of protection >Enclosures |
as required |
Degree of protection >Terminations |
In the operating controls area: IP20 (basic degree of protection) |
Other technical data (sheet catalogue) | With insulating surround: IP40 With door coupling rotary handle: IP66 |
Rated current = rated uninterrupted current [In = Iu] | Tunnel terminal: IP10 Phase isolator and strip terminal: IP00 |
Rated surge voltage invariability [Uimp
] >Main contacts |
Temperature dependency, Derating |
Rated surge voltage invariability [Uimp
] >Auxiliary contacts |
220 A |
Rated operational voltage [Ue] | 8000 V |
Overvoltage category/pollution degree | 6000 V |
Rated insulation voltage [Ui ] | 690 V AC |
Use in unearthed supply systems | III/3 |
Rated short-circuit making capacity [Icm
] >240 V [Icm ] |
1000 V |
Rated short-circuit making capacity [Icm
] >400/415 V [Icm ] |
≦ 690 V |
Rated short-circuit making capacity [Icm
] >440 V 50/60 Hz [Icm ] |
330 kA |
Rated short-circuit making capacity [Icm
] >525 V 50/60 Hz [Icm ] |
330 kA |
Rated short-circuit making capacity [Icm
] >690 V 50/60 H [Ic] |
286 kA |
Rated short-circuit breaking capacity Icn [Icn
] >Icu to IEC/EN 60947 test cycle O-t-CO [Icu] >240 V 50/60 Hz [Icu ] |
143 kA |
Rated short-circuit breaking capacity Icn [Icn
] >Icu to IEC/EN 60947 test cycle O-t-CO [Icu] >400/415 V 50/60 Hz [Icu ] |
74 kA |
Rated short-circuit breaking capacity Icn [Icn
] >Icu to IEC/EN 60947 test cycle O-t-CO [Icu] >440 V 50/60 Hz [Icu ] |
150 kA |
Rated short-circuit breaking capacity Icn [Icn
] >Icu to IEC/EN 60947 test cycle O-t-CO [Icu] >525 V 50/60 Hz [Icu ] |
150 kA |
Rated short-circuit breaking capacity Icn [Icn
] >Icu to IEC/EN 60947 test cycle O-t-CO [Icu] >690 V 50/60 Hz [Icu ] |
130 kA |
Rated short-circuit breaking capacity Icn [Icn
] >Ics to IEC/EN 60947 test cycle O-t-CO-t-CO [Ics] >240 V 50/60 Hz [Ics ] |
65 kA |
Rated short-circuit breaking capacity Icn [Icn
] >Ics to IEC/EN 60947 test cycle O-t-CO-t-CO [Ics] >400/415 V 50/60 Hz [Ics ] |
35 kA |
Rated short-circuit breaking capacity Icn [Icn
] >Ics to IEC/EN 60947 test cycle O-t-CO-t-CO [Ics] >440 V 50/60 Hz [Ics ] |
150 kA |
Rated short-circuit breaking capacity Icn [Icn
] >Ics to IEC/EN 60947 test cycle O-t-CO-t-CO [Ics] >525 V 50/60 Hz [Ics ] |
150 kA |
Rated short-circuit breaking capacity Icn [Icn
] >Ics to IEC/EN 60947 test cycle O-t-CO-t-CO [Ics] >690 V 50/60 Hz [Ics] |
130 kA |
Rated short-circuit breaking capacity Icn [Icn ] | 33 kA |
Rated short-time withstand current >t = 0.3 s [Icw ] |
9 kA |
Rated short-time withstand current >t = 1 s [Icw ] |
Maximum back-up fuse, if the expected short-circuit currents at the installation location exceed the switching capacity of the circuit-breaker. |
Utilization category to IEC/EN 60947-2 | 3.3 kA |
Lifespan, mechanical(of which max. 50 % trip by shunt/undervoltage release) [Operations] | 3.3 kA |
Lifespan, electrical >AC-1 >400 V 50/60 Hz [Operations] |
A |
Lifespan, electrical >AC-1 >415 V 50/60 Hz [Operations] |
15000 |
Lifespan, electrical >AC-1 >690 V 50/60 Hz [Operations] |
5000 |
Lifespan, electrical >AC--3 >400 V 50/60 Hz [Operations] |
5000 |
Lifespan, electrical >AC--3 >415 V 50/60 Hz [Operations] |
3000 |
Lifespan, electrical >AC--3 >690 V 50/60 Hz [Operations] |
2000 |
Lifespan, electrical >Max. operating frequency |
2000 |
Total break time at short-circuit | 2000 |
Standard equipment | 60 Ops/h |
Optional accessories | < 10 ms |
Round copper conductor >Box terminal >Solid |
Screw connection |
Round copper conductor >Box terminal >Stranded |
Box terminal Tunnel terminal connection on rear |
Round copper conductor >Tunnel terminal >Solid |
2 x 16 mm2 |
Round copper conductor >Tunnel terminal >Stranded >1-hole |
1 x (35 - 240) 2 x (25-120) mm2 |
Round copper conductor >Tunnel terminal >Stranded >Double hole fitting |
1 x 16 mm2 |
Round copper conductor >Bolt terminal and rear-side connection >Direct on the switch >Solid |
1 x (16 - 185) mm2 |
Round copper conductor >Bolt terminal and rear-side connection >Direct on the switch >Stranded |
2 x (50 - 240) mm2 |
Round copper conductor >Bolt terminal and rear-side connection >Connection width extension >Connection width extension |
1 x 16 2 x 16 mm2 |
Al circular conductor >Tunnel terminal >Solid |
1 x (25 - 240) 2 x (25 - 240) mm2 |
Al circular conductor >Tunnel terminal >Stranded >Stranded |
2 x 300 mm2 |
Al circular conductor >Tunnel terminal >Stranded >Double hole |
1 x 16 mm2 |
Al circular conductor >Tunnel terminal >Stranded |
1 x (25 - 185) 2) mm2 |
Al circular conductor >Bolt terminal and rear-side connection >Direct on the switch >Solid |
1 x (50 - 240) 2 x (50 - 240) mm2 |
Al circular conductor >Bolt terminal and rear-side connection >Direct on the switch >Stranded |
2) Up to 240 mm² can be connected depending on the cable manufacturer. |
Cu strip (number of segments x width x segment thickness) >Box terminal [min.] |
1 x 16 2 x (10 - 16) mm2 |
Cu strip (number of segments x width x segment thickness) >Box terminal [max.] |
1 x (25 - 120) 2 x (25 - 120) mm2 |
Cu strip (number of segments x width x segment thickness) >Bolt terminal and rear-side connection >Flat copper strip, with holes [min.] |
6 x 16 x 0.8 mm |
Cu strip (number of segments x width x segment thickness) >Bolt terminal and rear-side connection >Flat copper strip, with holes [max.] |
10 x 24 x 1.0 + 5 x 24 x 1.0 (2 x) 8 x 24 x 1.0 mm |
Cu strip (number of segments x width x segment thickness) >Bolt terminal and rear-side connection >Connection width extension |
6 x 16 x 0.8 mm |
Copper busbar (width x thickness) [mm] >Bolt terminal and rear-side connection >Screw connection |
10 x 32 x 1.0 + 5 x 32 x 1.0 mm |
Copper busbar (width x thickness) [mm] >Bolt terminal and rear-side connection >Direct on the switch [min.] |
(2 x) 10 x 50 x 1.0 mm |
Copper busbar (width x thickness) [mm] >Bolt terminal and rear-side connection >Direct on the switch [max.] |
M10 |
Copper busbar (width x thickness) [mm] >Bolt terminal and rear-side connection >Connection width extension >Connection width extension [max.] |
20 x 5 mm |
Control cables | 30 x 10 + 30 x 5 mm |
Rated operational current for specified heat dissipation [In] | 2 x (10 x 50) mm |
Equipment heat dissipation, current-dependent [Pvid] | 1 x (0.75 - 2.5) 2 x (0.75 - 1.5) mm2 |
Operating ambient temperature min. | 220 A |
Operating ambient temperature max. | 14.52 W |
10.2 Strength of materials and parts >10.2.2 Corrosion resistance |
-25 °C |
10.2 Strength of materials and parts >10.2.3.1 Verification of thermal stability of enclosures |
+70 °C |
10.2 Strength of materials and parts >10.2.3.2 Verification of resistance of insulating materials to normal heat |
Meets the product standard´s requirements. |
10.2 Strength of materials and parts >10.2.3.3 Verification of resistance of insulating materials to abnormal heat and fire due to internal electric effects |
Meets the product standard´s requirements. |
10.2 Strength of materials and parts >10.2.4 Resistance to ultra-violet (UV) radiation |
Meets the product standard´s requirements. |
10.2 Strength of materials and parts >10.2.5 Lifting |
Meets the product standard´s requirements. |
10.2 Strength of materials and parts >10.2.6 Mechanical impact |
Meets the product standard´s requirements. |
10.2 Strength of materials and parts >10.2.7 Inscriptions |
Does not apply, since the entire switchgear needs to be evaluated. |
10.3 Degree of protection of ASSEMBLIES | Does not apply, since the entire switchgear needs to be evaluated. |
10.4 Clearances and creepage distances | Meets the product standard´s requirements. |
10.5 Protection against electric shock | Does not apply, since the entire switchgear needs to be evaluated. |
10.6 Incorporation of switching devices and components | Meets the product standard´s requirements. |
10.7 Internal electrical circuits and connections | Does not apply, since the entire switchgear needs to be evaluated. |
10.8 Connections for external conductors | Does not apply, since the entire switchgear needs to be evaluated. |
10.9 Insulation properties >10.9.2 Power-frequency electric strength |
Is the panel builder´s responsibility. |
10.9 Insulation properties >10.9.3 Impulse withstand voltage |
Is the panel builder´s responsibility. |
10.9 Insulation properties >10.9.4 Testing of enclosures made of insulating material |
Is the panel builder´s responsibility. |
10.10 Temperature rise | Is the panel builder´s responsibility. |
10.11 Short-circuit rating | Is the panel builder´s responsibility. |
10.12 Electromagnetic compatibility | The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices. |
10.13 Mechanical function | Is the panel builder´s responsibility. The specifications for the switchgear must be observed. |
Overload release current setting | Is the panel builder´s responsibility. The specifications for the switchgear must be observed. |
Adjustment range undelayed short-circuit release | The device meets the requirements, provided the information in the instruction leaflet (IL) is observed. |
With thermal protection | 110 - 220 A |
Phase failure sensitive | 220 - 3080 A |
Switch off technique | Yes |
Rated operating voltage | Yes |
Rated permanent current Iu | Electronic |
Rated operation power at AC-3, 230 V | 690 - 690 V |
Rated operation power at AC-3, 400 V | 220 A |
Type of electrical connection of main circuit | 55 kW |
Type of control element | 110 kW |
Device construction | Screw connection |
With integrated auxiliary switch | Rocker lever |
With integrated under voltage release | Built-in device fixed built-in technique |
Number of poles | No |
Rated short-circuit breaking capacity lcu at 400 V, AC | No |
Degree of protection (IP) | 3 |
Height | 150 kA |
Width | IP20 |
Depth | 275 mm |
Characteristic curve | 140 mm |
Characteristic curve | 166 mm |
Characteristic curve |
As Mnelko, we are a reliable partner in industrial automation solutions, offering high-quality and innovative products with a wide product range to meet all the needs of your business. Our product portfolio consists of solutions designed based on the principles of high performance, durability, and efficiency to support modern industrial processes.
All of our products ensure maximum reliability even in challenging working conditions and help your business operations run smoothly. The products we offer in industrial automation, energy management, cabling solutions, and many other areas adapt flexibly to the needs of different sectors.
Additionally, our products are manufactured using only high-quality materials and comply with international standards. Through the solutions we provide, we enable our customers to increase operational efficiency and optimize costs. Our company closely follows technological advancements and continuously offers innovative products to help our customers gain a competitive advantage.
On each of our product pages, you can find comprehensive information about technical details, areas of use, and product features. You can explore all the products you need to strengthen your industrial processes on our website and enjoy a seamless purchasing experience.