alt
alt

NZM4-XBSM-N
189830 NZM4-XBSM-N
189830

Interface module for NZM4 PXR25, connection for communication, neutral conductor voltageOptional accessories for the circuit-breaker series NZM offers a comprehensive portfolio of application options for use world wide. The mounting is always flexible and easy thanks to the modular function groups. Notes: Breaker status modules - For multi purpose connection of optional circuit-breaker features. Required for communication. Type of connections depends on the version of the breaker status module. Detection of circuit-breaker status (I, +, 0) for the electronic release. Breaker status can be communicated. Auxiliary power supply connection for 2 x 24 V DC. Connection for communication adapter module (CAM). CAM available for various fieldbus communication systems (Profibus DP, SmartWire-DT, Ethernet based fieldbus). Connection to internal Modbus RTU module. Connection to Vn voltage tap-off.

Interface module for NZM4 PXR25, connection for communication, neutral conductor voltage
Optional accessories for the circuit-breaker series NZM offers a comprehensive portfolio of application options for use world wide. The mounting is always flexible and easy thanks to the modular function groups. Notes: Breaker status modules - For multi purpose connection of optional circuit-breaker features. Required for communication. Type of connections depends on the version of the breaker status module. Detection of circuit-breaker status (I, +, 0) for the electronic release. Breaker status can be communicated. Auxiliary power supply connection for 2 x 24 V DC. Connection for communication adapter module (CAM). CAM available for various fieldbus communication systems (Profibus DP, SmartWire-DT, Ethernet based fieldbus). Connection to internal Modbus RTU module. Connection to Vn voltage tap-off.

Product range Accessories
Accessories Interface module
Standard/Approval UL/CSA, IEC
Construction size NZM4
Description For universal connection of optional circuit breaker functions.
Required for communication
The connection types depend on the design of the interface module.
Circuit breaker status detection (I, +, 0) for the electronic trip unit.
The switch´s status can be communicated.
24 V DC auxiliary power connection.
Connection for Communications Adapter Module (CAM).
Optional CAM available for various Fieldbus communication systems (Profibus DP, SmartWire-DT, Ethernet-based Fieldbus).
Connection to optional, internal Modbus RTU module.
Connection to neutral voltage Vn.
Mechanical pass-through of the switch´s status (I, O) for use by the remote operator.
Connection type with push in terminal
With bolt connection
For use with NZM4-PX(PMX)…
Rated control voltage [Us ]
>DC [Us ]
24-24 V DC
Rated control voltage [Us ]
>Tolerance
+/- 20%
Rated control voltage [Us ]
>max. current consumption
100
Rated control voltage [Us ]
>Connection
>Connection type
Screw terminal
Rated control voltage [Us ]
>Connection
>Stripping length
5 mm
Rated control voltage [Us ]
>Connection
>Terminal capacity
>Solid
1 x (0.2 - 1.5) mm2
Rated control voltage [Us ]
>Connection
>Terminal capacity
>Stranded
1 x (0.2 - 1.5) mm2
Rated control voltage [Us ]
>Connection
>Terminal capacity
1 x AWG 24 - AWG 16 AWG
Rated control voltage [Us ]
>Connection
>Terminal capacity
>with uninsulated end sleeve in accordance with DIN46228 / 1
1 x (0,25 - 0,75) mm2
Rated control voltage [Us ]
>Connection
>Terminal capacity
>with insulated end sleeve in accordance with DIN46224 / 4
1 x (0,25 - 0,75) mm2
Rated control voltage [Us ]
>Connection
>Terminal capacity
>Min. tightening torque
0.22 Nm
Rated control voltage [Us ]
>Connection
>Terminal capacity
>Maximum tightening torque
0.25 Nm
Connection technique 5-pin plug connector
Connection type assembled CAM cable
Connection technique 10-pin plug connector
Connection type pre-wired cable to the Modbus module
10.2 Strength of materials and parts
>10.2.2 Corrosion resistance
Meets the product standard´s requirements.
10.2 Strength of materials and parts
>10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard´s requirements.
10.2 Strength of materials and parts
>10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard´s requirements.
10.2 Strength of materials and parts
>10.2.3.3 Verification of resistance of insulating materials to abnormal heat and fire due to internal electric effects
Meets the product standard´s requirements.
10.2 Strength of materials and parts
>10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard´s requirements.
10.2 Strength of materials and parts
>10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
10.2 Strength of materials and parts
>10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2 Strength of materials and parts
>10.2.7 Inscriptions
Meets the product standard´s requirements.
10.3 Degree of protection of ASSEMBLIES Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances Meets the product standard´s requirements.
10.5 Protection against electric shock Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections Is the panel builder´s responsibility.
10.8 Connections for external conductors Is the panel builder´s responsibility.
10.9 Insulation properties
>10.9.2 Power-frequency electric strength
Is the panel builder´s responsibility.
10.9 Insulation properties
>10.9.3 Impulse withstand voltage
Is the panel builder´s responsibility.
10.9 Insulation properties
>10.9.4 Testing of enclosures made of insulating material
Is the panel builder´s responsibility.
10.10 Temperature rise The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating Is the panel builder´s responsibility. The specifications for the switchgear must be observed.
10.12 Electromagnetic compatibility Is the panel builder´s responsibility. The specifications for the switchgear must be observed.
10.13 Mechanical function The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
Type of accessory Communication and measuring function
Product Standards In preparation
Degree of Protection Installation in the switch

As Mnelko, we are a reliable partner in industrial automation solutions, offering high-quality and innovative products with a wide product range to meet all the needs of your business. Our product portfolio consists of solutions designed based on the principles of high performance, durability, and efficiency to support modern industrial processes.
All of our products ensure maximum reliability even in challenging working conditions and help your business operations run smoothly. The products we offer in industrial automation, energy management, cabling solutions, and many other areas adapt flexibly to the needs of different sectors.
Additionally, our products are manufactured using only high-quality materials and comply with international standards. Through the solutions we provide, we enable our customers to increase operational efficiency and optimize costs. Our company closely follows technological advancements and continuously offers innovative products to help our customers gain a competitive advantage.
On each of our product pages, you can find comprehensive information about technical details, areas of use, and product features. You can explore all the products you need to strengthen your industrial processes on our website and enjoy a seamless purchasing experience.

Similar Products

NZMH2-4-VX250/VAR
Eaton
NZMH2-VX250-SVE
Eaton
NZMS2-4-VX250/VAR
Eaton
NZMS2-4-VX160
Eaton
NZMS2-MX220-SVE
Eaton
NZMS2-VX250-SVE
Eaton
NZMN2-4-VX160/VAR
Eaton
NZMN2-VX100-BT
Eaton