alt
alt

NZM3-XKS
260039 NZM3-XKS
260039

Screw connection, 3p, standard, size 3Optional accessories for the circuit-breaker series NZM offers a comprehensive portfolio of application options for use world wide. The mounting is always flexible and easy thanks to the modular function groups. Notes: part no. contains parts for a terminal located at top or bottom for 3 or 4 pole switches. Standard connection with all NZM3, PN3 and N3 circuit-breakers. Conversion kit for circuit-breaker with box terminal. Use special cable lug narrow version. fitted within the switch housing. If a busbar is used, insulation (400mm) heat-shrink tubing and a cover NZM3(-4)-XKSA are required. U e ≧ 525 VAC. For all other connection types use cover NZM3(-4)-XKSA. Can be used for: NZM3(-4), PN3(-4), N(N/O)3(-4)

Screw connection, 3p, standard, size 3
Optional accessories for the circuit-breaker series NZM offers a comprehensive portfolio of application options for use world wide. The mounting is always flexible and easy thanks to the modular function groups. Notes: part no. contains parts for a terminal located at top or bottom for 3 or 4 pole switches. Standard connection with all NZM3, PN3 and N3 circuit-breakers. Conversion kit for circuit-breaker with box terminal. Use special cable lug narrow version. fitted within the switch housing. If a busbar is used, insulation (400mm) heat-shrink tubing and a cover NZM3(-4)-XKSA are required. U e ≧ 525 VAC. For all other connection types use cover NZM3(-4)-XKSA. Can be used for: NZM3(-4), PN3(-4), N(N/O)3(-4)

Number of conductors 3 pole
Accessories Screw connection
Rated current [In] 630 A
For use with NZM3, PN3, N(S)3
Type of conductor
>Cu/Al cable
Copper cable lugs
Aluminium cable lug
Terminal capacities
>flexible
1 x 16 - 300
2 x 16 - 240 mm2
AWG/kcmil 1 x 4 - 350
2 x 350 mm2
Cu strip (number of segments x width x segment thickness) 10 x 32 x 1.0
+ 5 x 32 x 1.0 mm2
Copper busbar width x thickness [Width] 30 x 10
+ 30 x 5 mm
Notes

Type contains parts for a terminal located at top or bottom for 3 or 4‐pole circuit‐breakers.

Standard connection with all NZM3, PN3 and N3 circuit‐breakers.

Conversion kit for circuit‐breaker with box terminal.

Use special cable lugs narrow version, → 059775

Fitted within the switch housing

When a busbar is used insulation is required (400 mm) e.g. using heat shrink and a shroud NZM3(‐4)‐XKSA.

Ue ≧ 525 V AC:

A shroud NZM3(‐4)‐XKSA must be used with all other connection types.

10.2 Strength of materials and parts
>10.2.2 Corrosion resistance
Meets the product standard´s requirements.
10.2 Strength of materials and parts
>10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard´s requirements.
10.2 Strength of materials and parts
>10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard´s requirements.
10.2 Strength of materials and parts
>10.2.3.3 Verification of resistance of insulating materials to abnormal heat and fire due to internal electric effects
Meets the product standard´s requirements.
10.2 Strength of materials and parts
>10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard´s requirements.
10.2 Strength of materials and parts
>10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
10.2 Strength of materials and parts
>10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2 Strength of materials and parts
>10.2.7 Inscriptions
Meets the product standard´s requirements.
10.3 Degree of protection of ASSEMBLIES Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances Meets the product standard´s requirements.
10.5 Protection against electric shock Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections Is the panel builder´s responsibility.
10.8 Connections for external conductors Is the panel builder´s responsibility.
10.9 Insulation properties
>10.9.2 Power-frequency electric strength
Is the panel builder´s responsibility.
10.9 Insulation properties
>10.9.3 Impulse withstand voltage
Is the panel builder´s responsibility.
10.9 Insulation properties
>10.9.4 Testing of enclosures made of insulating material
Is the panel builder´s responsibility.
10.10 Temperature rise The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating Is the panel builder´s responsibility. The specifications for the switchgear must be observed.
10.12 Electromagnetic compatibility Is the panel builder´s responsibility. The specifications for the switchgear must be observed.
10.13 Mechanical function The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
Suitable for number of poles 3
Model Other
Product Standards UL489; CSA-C22.2 No. 5-09; IEC60947, CE marking
UL File No. E31593
UL Category Control No. DIHS
CSA File No. 022086
CSA Class No. 1437-01
North America Certification UL listed, CSA certified
Suitable for Refer to main component information

As Mnelko, we are a reliable partner in industrial automation solutions, offering high-quality and innovative products with a wide product range to meet all the needs of your business. Our product portfolio consists of solutions designed based on the principles of high performance, durability, and efficiency to support modern industrial processes.
All of our products ensure maximum reliability even in challenging working conditions and help your business operations run smoothly. The products we offer in industrial automation, energy management, cabling solutions, and many other areas adapt flexibly to the needs of different sectors.
Additionally, our products are manufactured using only high-quality materials and comply with international standards. Through the solutions we provide, we enable our customers to increase operational efficiency and optimize costs. Our company closely follows technological advancements and continuously offers innovative products to help our customers gain a competitive advantage.
On each of our product pages, you can find comprehensive information about technical details, areas of use, and product features. You can explore all the products you need to strengthen your industrial processes on our website and enjoy a seamless purchasing experience.

Similar Products

NZMH2-4-VX250/VAR
Eaton
NZMH2-VX250-SVE
Eaton
NZMS2-4-VX250/VAR
Eaton
NZMS2-4-VX160
Eaton
NZMS2-MX220-SVE
Eaton
NZMS2-VX250-SVE
Eaton
NZMN2-4-VX160/VAR
Eaton
NZMN2-VX100-BT
Eaton