alt
alt

NZM2-4-XFIA30
292345 NZM2-4-XFIA30
292345

Earth-fault release 30mA, AC/DC sensitive, 4pOptional accessories for the circuit-breaker series NZM offers a comprehensive portfolio of application options for use world wide. The mounting is always flexible and easy thanks to the modular function groups. Notes: AC/DC current sensitivity according to the core-balance principle (in range 0 … 100 kHz). Observe response threshold dependence on frequency! See “Frequency response” characteristic curve. Adjusting buttons can be sealed. Can be used for NZM2-4, N2-4

Earth-fault release 30mA, AC/DC sensitive, 4p
Optional accessories for the circuit-breaker series NZM offers a comprehensive portfolio of application options for use world wide. The mounting is always flexible and easy thanks to the modular function groups. Notes: AC/DC current sensitivity according to the core-balance principle (in range 0 … 100 kHz). Observe response threshold dependence on frequency! See “Frequency response” characteristic curve. Adjusting buttons can be sealed. Can be used for NZM2-4, N2-4

Description Core-balance principle with AC/DC sensitivity (in range 0 - 100 kHz)
For 4 pole NZM2-4 circuit-breakers and N2-4 switch-disconnectors
Internal power supply Us = 50 - 400 V
Contact sequence 123N012
Contact sequence 000Z244
For use with NZM2-4
N2-4
Pole 4 pole
Notes

Observe response threshold dependence on frequency!

See “Frequency response” characteristic curve

Auxiliary contacts (1 N/O, 1N/C integrated) are reset via the reset button.

Not in combination with plug-in units, insulated enclosure or main switch assembly kit for side panel mounting with mounting bracket.

Rated ultimate short-circuit breaking capacity is determined by the fitted NZM2.

If a switch-disconnector N2 is applied by the back-up fuse to be used → Technical data.

Standards IEC/EN 60947-2
IEC/EN 60947-2 annex B
Sensitivity Sensitive to AC/DC (type B)
Min. operating voltage [Ue]
>or detection of fault currents type A/AC
0 V independent of mains voltage
Min. operating voltage [Ue]
>or detection of fault currents type B
50 V (dependent on mains power)
Suitability for the application In three- and single-phase systems
Rated operational voltage [Ue] 50…400 (3~) V AC
Rated frequency [f] 50 Hz
Number of poles 4-pole
Rated current range [In ] 15…250 A
Rated fault currents [ I Δn ] 0.03 A
Detection range of the fault current with AC voltage: 0 - 100 kHz
with pulsed DC voltage: 50 Hz
Rated ultimate short-circuit making capacity and rated ultimate short-circuit breaking capacity [IΔm ] = ICU A
Mechanical shock resistance (IEC 60068-2-27) 20 (half-sinusoidal shock 20 ms)
Lifespan, mechanical (50 % with fault current) [Operations] ≧ 2 000
Standard front dimension 96 mm
Mounting Bottom
Mounting position Vertical and 90° in all directions
Supply Bottom
Degree of protection IP20 in the operating component area
Ambient temperature -25 - +70
Terminal capacity
>Flexible without ferrule
wie NZM2 Standardanschluss mm2
Terminal capacity
>flexible with ferrules
With NZM2 standard connection mm2
Operating ambient temperature min. -25 °C
Operating ambient temperature max. +70 °C
10.2 Strength of materials and parts
>10.2.2 Corrosion resistance
Meets the product standard´s requirements.
10.2 Strength of materials and parts
>10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard´s requirements.
10.2 Strength of materials and parts
>10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard´s requirements.
10.2 Strength of materials and parts
>10.2.3.3 Verification of resistance of insulating materials to abnormal heat and fire due to internal electric effects
Meets the product standard´s requirements.
10.2 Strength of materials and parts
>10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard´s requirements.
10.2 Strength of materials and parts
>10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
10.2 Strength of materials and parts
>10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2 Strength of materials and parts
>10.2.7 Inscriptions
Meets the product standard´s requirements.
10.3 Degree of protection of ASSEMBLIES Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances Meets the product standard´s requirements.
10.5 Protection against electric shock Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections Is the panel builder´s responsibility.
10.8 Connections for external conductors Is the panel builder´s responsibility.
10.9 Insulation properties
>10.9.2 Power-frequency electric strength
Is the panel builder´s responsibility.
10.9 Insulation properties
>10.9.3 Impulse withstand voltage
Is the panel builder´s responsibility.
10.9 Insulation properties
>10.9.4 Testing of enclosures made of insulating material
Is the panel builder´s responsibility.
10.10 Temperature rise The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating Is the panel builder´s responsibility. The specifications for the switchgear must be observed.
10.12 Electromagnetic compatibility Is the panel builder´s responsibility. The specifications for the switchgear must be observed.
10.13 Mechanical function The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
Rated control supply voltage Us at AC 50HZ 50 - 400 V
Rated control supply voltage Us at AC 60HZ 50 - 400 V
Rated control supply voltage Us at DC 0 - 0 V
Rated fault current 0.03 - 0.03 A
Max. power on-delay time 30 ms
Delay adjustable No
Max. rated operation voltage Ue 400 V
Characteristic curve 1230DIA-164

As Mnelko, we are a reliable partner in industrial automation solutions, offering high-quality and innovative products with a wide product range to meet all the needs of your business. Our product portfolio consists of solutions designed based on the principles of high performance, durability, and efficiency to support modern industrial processes.
All of our products ensure maximum reliability even in challenging working conditions and help your business operations run smoothly. The products we offer in industrial automation, energy management, cabling solutions, and many other areas adapt flexibly to the needs of different sectors.
Additionally, our products are manufactured using only high-quality materials and comply with international standards. Through the solutions we provide, we enable our customers to increase operational efficiency and optimize costs. Our company closely follows technological advancements and continuously offers innovative products to help our customers gain a competitive advantage.
On each of our product pages, you can find comprehensive information about technical details, areas of use, and product features. You can explore all the products you need to strengthen your industrial processes on our website and enjoy a seamless purchasing experience.

Similar Products

NZMH2-4-VX250/VAR
Eaton
NZMH2-VX250-SVE
Eaton
NZMS2-4-VX250/VAR
Eaton
NZMS2-4-VX160
Eaton
NZMS2-MX220-SVE
Eaton
NZMS2-VX250-SVE
Eaton
NZMN2-4-VX160/VAR
Eaton
NZMN2-VX100-BT
Eaton