alt
alt

NZM1-XUHIVL110-130DC
259579 NZM1-XUHIVL110-130DC
259579

Undervoltage release, 110-130VDC, +2early N/OOptional accessories for the circuit-breaker series NZM offers a comprehensive portfolio of application options for use world wide. The mounting is always flexible and easy thanks to the modular function groups. Notes: for interlocking and load-shedding circuits, as well as for early-make of the undervoltage release in main-switch applications. For use with Emergency-Stop devices in conjunction with emergency-stop button. when the shunt release is energized, accidental contact with the main contacts of the switch during attempts to switch on is safely prevented. Early make of auxiliary contacts on switching on and off (manual operation): approx. 20ms. Undervoltage releases cannot be installed simultaneously with NZM..-XHIV.. early-make auxiliary contact or NZM..-XA.. shunt release. Can be used for: NZM1(-4), N(N/O)1(-4)

Undervoltage release, 110-130VDC, +2early N/O
Optional accessories for the circuit-breaker series NZM offers a comprehensive portfolio of application options for use world wide. The mounting is always flexible and easy thanks to the modular function groups. Notes: for interlocking and load-shedding circuits, as well as for early-make of the undervoltage release in main-switch applications. For use with Emergency-Stop devices in conjunction with emergency-stop button. when the shunt release is energized, accidental contact with the main contacts of the switch during attempts to switch on is safely prevented. Early make of auxiliary contacts on switching on and off (manual operation): approx. 20ms. Undervoltage releases cannot be installed simultaneously with NZM..-XHIV.. early-make auxiliary contact or NZM..-XA.. shunt release. Can be used for: NZM1(-4), N(N/O)1(-4)

Product range Accessories
Accessories Undervoltage release
Accessories Undervoltage release with early-make auxiliary contact
Standard/Approval UL/CSA, IEC
Construction size NZM1
Description Undervoltage release with 2 early-make auxiliary contacts, e.g., for early-make connection of undervoltage release in main switch applications, as well as for interlock and load shedding circuits.
For use with emergency-stop devices in connection with an emergency-stop button.
When the under-voltage trip is switched off, accidental contact with the circuit breaker’s primary contacts is prevented when switched on.
Early make of auxiliary contacts on switching on and off (manual operation): approx. 20 ms
Undervoltage releases cannot be installed simultaneously with NZM...-XHIV... early-make auxiliary contact or NZM...-XA... shunt release.
Connection type with 3 m connection cable instead of screw termination
Auxiliary contacts with 2 early-make auxiliary contacts
Rated control voltage [Us] 110 - 130 V DC V
For use with NZM1(-4), N(S)1(-4)
Rated control voltage [Us ]
>DC [Us ]
110-130 V DC
Rated control voltage [Us ]
>Rated control voltage [Us]
110 - 130 V DC V
Operating range
>Drop-out voltage
0.35 - 0.7 x Us
Operating range
>Pick-up voltage [x Uc]
0.85 - 1.1
Power consumption
>AC
>Pick-up AC
1.5 VA
Power consumption
>AC
>Sealing AC
1.5 VA
Power consumption
>DC
>Pick-up DC
0.8 W
Power consumption
>DC
>Sealing DC
0.8 W
Maximum opening delay (response time until opening of the main contacts) 19 ms
Minimum command time 10 - 15 ms
Solid or flexible conductor, with ferrule 1 x (0,75 - 2,5)
2 x (0,75 - 2,5) mm2
10.2 Strength of materials and parts
>10.2.2 Corrosion resistance
1 x (18 … 14)
2 x (18 … 14) AWG
10.2 Strength of materials and parts
>10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard´s requirements.
10.2 Strength of materials and parts
>10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard´s requirements.
10.2 Strength of materials and parts
>10.2.3.3 Verification of resistance of insulating materials to abnormal heat and fire due to internal electric effects
Meets the product standard´s requirements.
10.2 Strength of materials and parts
>10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard´s requirements.
10.2 Strength of materials and parts
>10.2.5 Lifting
Meets the product standard´s requirements.
10.2 Strength of materials and parts
>10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2 Strength of materials and parts
>10.2.7 Inscriptions
Does not apply, since the entire switchgear needs to be evaluated.
10.3 Degree of protection of ASSEMBLIES Meets the product standard´s requirements.
10.4 Clearances and creepage distances Does not apply, since the entire switchgear needs to be evaluated.
10.5 Protection against electric shock Meets the product standard´s requirements.
10.6 Incorporation of switching devices and components Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections Does not apply, since the entire switchgear needs to be evaluated.
10.8 Connections for external conductors Is the panel builder´s responsibility.
10.9 Insulation properties
>10.9.2 Power-frequency electric strength
Is the panel builder´s responsibility.
10.9 Insulation properties
>10.9.3 Impulse withstand voltage
Is the panel builder´s responsibility.
10.9 Insulation properties
>10.9.4 Testing of enclosures made of insulating material
Is the panel builder´s responsibility.
10.10 Temperature rise Is the panel builder´s responsibility.
10.11 Short-circuit rating The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.12 Electromagnetic compatibility Is the panel builder´s responsibility. The specifications for the switchgear must be observed.
10.13 Mechanical function Is the panel builder´s responsibility. The specifications for the switchgear must be observed.
Rated control supply voltage Us at AC 50HZ The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
Rated control supply voltage Us at AC 60HZ 0 - 0 V
Rated control supply voltage Us at DC 0 - 0 V
Voltage type for actuating 110 - 130 V
Type of electric connection DC
Number of contacts as normally open contact Screw connection
Number of contacts as normally closed contact 2
Number of contacts as change-over contact 0
Delayed 0
Suitable for power circuit breaker Yes
Suitable for off-load switch Yes
Suitable for motor safety switch Yes
Suitable for overload relay No
Product Standards No
UL File No. UL489; CSA-C22.2 No. 5-09; IEC60947, CE marking
UL Category Control No. E140305
CSA File No. DIHS
CSA Class No. 022086
North America Certification 1437-01

As Mnelko, we are a reliable partner in industrial automation solutions, offering high-quality and innovative products with a wide product range to meet all the needs of your business. Our product portfolio consists of solutions designed based on the principles of high performance, durability, and efficiency to support modern industrial processes.
All of our products ensure maximum reliability even in challenging working conditions and help your business operations run smoothly. The products we offer in industrial automation, energy management, cabling solutions, and many other areas adapt flexibly to the needs of different sectors.
Additionally, our products are manufactured using only high-quality materials and comply with international standards. Through the solutions we provide, we enable our customers to increase operational efficiency and optimize costs. Our company closely follows technological advancements and continuously offers innovative products to help our customers gain a competitive advantage.
On each of our product pages, you can find comprehensive information about technical details, areas of use, and product features. You can explore all the products you need to strengthen your industrial processes on our website and enjoy a seamless purchasing experience.

Similar Products

NZMH2-4-VX250/VAR
Eaton
NZMH2-VX250-SVE
Eaton
NZMS2-4-VX250/VAR
Eaton
NZMS2-4-VX160
Eaton
NZMS2-MX220-SVE
Eaton
NZMS2-VX250-SVE
Eaton
NZMN2-4-VX160/VAR
Eaton
NZMN2-VX100-BT
Eaton