alt
alt

NZM-XDMI-DPV1
270333 NZM-XDMI-DPV1
270333

Fieldbus connection, profibus-DPV1-SlaveOptional accessories for the circuit-breaker series NZM offers a comprehensive portfolio of application options for use world wide. The mounting is always flexible and easy thanks to the modular function groups. Notes: connection to the DMI module. Transfer of phase currents, parameter data, status data and diagnostics data. Transfer of circuit-breaker position (wiring of auxiliary contacts to DMI inputs). Actuation of the DMI motor starter functions and the NZM remote operator. detection of digital inputs and actuation via field Bus. PROFIBUS-DPV1 slave fieldbus connection. Can be operated with class 1 and class 2 masters. Addressable 1 to 126. Can be used for: NZM2, NZM2-4, NZM3, NZM3-4, NZM4, NZM4-4

Fieldbus connection, profibus-DPV1-Slave
Optional accessories for the circuit-breaker series NZM offers a comprehensive portfolio of application options for use world wide. The mounting is always flexible and easy thanks to the modular function groups. Notes: connection to the DMI module. Transfer of phase currents, parameter data, status data and diagnostics data. Transfer of circuit-breaker position (wiring of auxiliary contacts to DMI inputs). Actuation of the DMI motor starter functions and the NZM remote operator. detection of digital inputs and actuation via field Bus. PROFIBUS-DPV1 slave fieldbus connection. Can be operated with class 1 and class 2 masters. Addressable 1 to 126. Can be used for: NZM2, NZM2-4, NZM3, NZM3-4, NZM4, NZM4-4

Product range Accessories
Accessories Diagnostics, communication
Description

Connection to the DMI module

  • Transfer of phase currents, parameter data, status data and diagnostics data.
  • Transfer of circuit-breaker position (wiring of auxiliary contacts to DMI inputs).
  • Actuation of the DMI motor starter functions and the NZM remote operator.
  • Detection of digital inputs and actuation via field Bus.
  • PROFIBUS-DPV1-Slave fieldbus interface. Can be operated with class 1 and class 2 masters. Addresses available: 1 to 126.
Bus protocol PROFIBUS-DP
Notes

Connected to the DMI module and has the same contour appearance.

Standards EN 55011, EN 55022, IEC/EN 61000-4, IEC 60068-2-6, IEC 60068-2-27
Dimensions (W x H x D) 35.5 x 90 x 58 (2 PE) mm
Weight 0.15 kg
Mounting Top-hat rail IEC/EN 60715, 35 mm or screw fixing using fixing brackets ZB4-101-GF1 (accessories)
Solid 0.2 … 4 (AWG 22 … 12) mm2
Flexible with ferrule 0.2 … 2.5 (AWG 22 … 12) mm2
Standard screwdriver 0.8 x 3.5 mm
Max. tightening torque 0.6 Nm
Operating ambient temperature -25 to 55, cold as per IEC 60068-2-1, heat as per IEC 60068-2-2 °C
Condensation Take appropriate measures to prevent condensation
Storage - 40 - 70 °C
Relative humidity, non-condensing (IEC/EN 60068-2-30) 5 - 95 %
Air pressure (operation) 795 - 1080 hPa
Corrosion resistance
>IEC/EN 60068-2-42 [4 days SO2]
10 cm3/m3
Corrosion resistance
>IEC/EN 60068-2-43 [4 days H2S]
1 cm3/m3
Pollution degree 2
Protection type (IEC/EN 60529, EN50178, VBG 4) IP20
Vibrations (IEC/EN 60068-2-6)
>Constant amplitude 0.15 mm
10 - 57 Hz
Vibrations (IEC/EN 60068-2-6)
>Constant acceleration 2 g
57 - 150 Hz
Mechanical shock resistance (IEC/EN 60068-2-27) semi-sinusoidal 15 g/11 ms 18 Impacts
Drop to IEC/EN 60068-2-31 [Drop height] 50 mm
Free fall, packaged (IEC/EN 60068-2-32) 1 m
Mounting position Vertical or horizontal
Electrostatic discharge (IEC/EN 61000-4-2, Level 3, ESD)
>Air discharge
8 kV
Electrostatic discharge (IEC/EN 61000-4-2, Level 3, ESD)
>Contact discharge
6 kV
Electromagnetic fields (RFI) to IEC EN 61000-4-3 10 V/m
Radio interference suppression EN 55011 Class B, EN 55022 Class B
Burst Impulse (IEC/EN 61000-4-4, Level 3)
>Supply cable
2 kV
Burst Impulse (IEC/EN 61000-4-4, Level 3)
>Signal lines
2 kV
power pulses (surge) (IEC/EN 61000-4-5, level 2) 0.5 (supply cables, symmetrical) kV
Immunity to line-conducted interference to (IEC/EN 61000-4-6) 10 V
Clearance in air and creepage distances EN 50178, UL 508, CSA C22.2, No. 142
Insulation resistance EN 50178
Rated operational voltage [Ue] 24 (-15/+20 %) V
Admissible range 20.4 - 28.8 V DC
Residual ripple < 5 %
at 24 V DC Normally 200 mA
Voltage dips ≤ 10 ms
Heat dissipation at 24 V DC 4.8 W
AS-I power supply Yes
Supply Power LED (POW): green
LED display PROFIBUS-DP LED (BUS): red
Connection technique SUB-D 9 pole, socket
Potential isolation Between bus and power supply (simple), between bus and power supply and NZM-XDMI612 (safe isolation)
Function PROFIBUS-DP slave
Interface RS485
Bus protocol PROFIBUS-DP
Baud rates Automatic search up to 12 MBit⁄s
Bus terminating resistors Separate external bus termination required
Bus addresses 1 … 126 via DMI
Services
>Cyclic
Status ON/OFF/tripped (detailed),

load early warnings,

phase currents I1/I2/I3 [A],

remote operator actuation,

display/operation NZM-XDMI612 inputs/outputs,

motor starter functions
Services
>Acyclic
Display/match protection settings,

event list,

identification,

hours of operation,

switching operations,

time
10.2 Strength of materials and parts
>10.2.2 Corrosion resistance
Meets the product standard´s requirements.
10.2 Strength of materials and parts
>10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard´s requirements.
10.2 Strength of materials and parts
>10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard´s requirements.
10.2 Strength of materials and parts
>10.2.3.3 Verification of resistance of insulating materials to abnormal heat and fire due to internal electric effects
Meets the product standard´s requirements.
10.2 Strength of materials and parts
>10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard´s requirements.
10.2 Strength of materials and parts
>10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
10.2 Strength of materials and parts
>10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2 Strength of materials and parts
>10.2.7 Inscriptions
Meets the product standard´s requirements.
10.3 Degree of protection of ASSEMBLIES Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances Meets the product standard´s requirements.
10.5 Protection against electric shock Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections Is the panel builder´s responsibility.
10.8 Connections for external conductors Is the panel builder´s responsibility.
10.9 Insulation properties
>10.9.2 Power-frequency electric strength
Is the panel builder´s responsibility.
10.9 Insulation properties
>10.9.3 Impulse withstand voltage
Is the panel builder´s responsibility.
10.9 Insulation properties
>10.9.4 Testing of enclosures made of insulating material
Is the panel builder´s responsibility.
10.10 Temperature rise The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating Is the panel builder´s responsibility. The specifications for the switchgear must be observed.
10.12 Electromagnetic compatibility Is the panel builder´s responsibility. The specifications for the switchgear must be observed.
10.13 Mechanical function The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
Supply voltage AC 50 Hz 0 - 0 V
Supply voltage AC 60 Hz 0 - 0 V
Supply voltage DC 0 - 0 V
Voltage type of supply voltage DC
Supporting protocol for TCP/IP No
Supporting protocol for PROFIBUS Yes
Supporting protocol for CAN No
Supporting protocol for INTERBUS No
Supporting protocol for ASI No
Supporting protocol for KNX No
Supporting protocol for MODBUS No
Supporting protocol for Data-Highway No
Supporting protocol for DeviceNet No
Supporting protocol for SUCONET No
Supporting protocol for LON No
Supporting protocol for SERCOS No
Supporting protocol for PROFINET IO No
Supporting protocol for PROFINET CBA No
Supporting protocol for Foundation Fieldbus No
Supporting protocol for EtherNet/IP No
Supporting protocol for AS-Interface Safety at Work No
Supporting protocol for DeviceNet Safety No
Supporting protocol for INTERBUS-Safety No
Supporting protocol for PROFIsafe No
Supporting protocol for SafetyBUS p No
Supporting protocol for other bus systems No
Radio standard Bluetooth No
Radio standard WLAN 802.11 No
Radio standard GPRS No
Radio standard GSM No
Radio standard UMTS No
IO link master No
System accessory Yes
Degree of protection (IP) IP20
With potential separation No
Fieldbus connection over separate bus coupler possible No
Rail mounting possible Yes
Wall mounting/direct mounting No
Front build in possible Yes
Rack-assembly possible No
Suitable for safety functions No
Category according to EN 954-1
SIL according to IEC 61508 None
Performance level acc. EN ISO 13849-1 None
Appendant operation agent (Ex ia) No
Appendant operation agent (Ex ib) No
Explosion safety category for gas None
Explosion safety category for dust Other
Width 36 mm
Height 90 mm
Depth 60 mm

As Mnelko, we are a reliable partner in industrial automation solutions, offering high-quality and innovative products with a wide product range to meet all the needs of your business. Our product portfolio consists of solutions designed based on the principles of high performance, durability, and efficiency to support modern industrial processes.
All of our products ensure maximum reliability even in challenging working conditions and help your business operations run smoothly. The products we offer in industrial automation, energy management, cabling solutions, and many other areas adapt flexibly to the needs of different sectors.
Additionally, our products are manufactured using only high-quality materials and comply with international standards. Through the solutions we provide, we enable our customers to increase operational efficiency and optimize costs. Our company closely follows technological advancements and continuously offers innovative products to help our customers gain a competitive advantage.
On each of our product pages, you can find comprehensive information about technical details, areas of use, and product features. You can explore all the products you need to strengthen your industrial processes on our website and enjoy a seamless purchasing experience.

Similar Products

NZMH2-4-VX250/VAR
Eaton
NZMH2-VX250-SVE
Eaton
NZMS2-4-VX250/VAR
Eaton
NZMS2-4-VX160
Eaton
NZMS2-MX220-SVE
Eaton
NZMS2-VX250-SVE
Eaton
NZMN2-4-VX160/VAR
Eaton
NZMN2-VX100-BT
Eaton