alt
alt

NH-SLS-00/160-60-SI
106216 NH-SLS-00/160-60-SI
106216

Low-voltage h.b.c fuse switch strip, 160A, 500V/160A, 690V/160A, size 00H.b.c fuse switch strip, rated operational current 160A, max. fuse-link 500V/160A, max. fuse-link 690V/160A, size 00, with safety monitoring

Low-voltage h.b.c fuse switch strip, 160A, 500V/160A, 690V/160A, size 00
H.b.c fuse switch strip, rated operational current 160A, max. fuse-link 500V/160A, max. fuse-link 690V/160A, size 00, with safety monitoring

Product range 60 mm system
Basic function Busbar fuse material
Subrange Low-voltage h.b.c. switch-fuse units
Description With fuse monitoring
With connection area cover
Mounting with snap-on mechanism
Information about equipment supplied With clamp/screw connection set
Interval between busbar centres 60 mm
Rated operational current [Ie] 160 A
400 V 160 A
Frame size 00
For use with 12 x 5/10
15 x 5/10
20 x 5/10
25 x 5/10
30 x 5/10
For use with Double T profile
Triple T profile
Connection top or bottom
Notes NH-fuse-links →#289998
Standards IEC/EN 60255,
VDE 0435 part 303
Climatic proofing Damp heat, constant, to IEC 60068-2-78
Damp heat, cyclic, to IEC 60068-2-30
Ambient temperature -5 - +40
Altitude max. 2000 m m
Interval between busbar centres 60 mm
Number of poles/phases 3 n
Mounting position Vertical, horizontal
Overvoltage category/pollution degree III/3
Protection type IP30 (Operating state)
IP10 (Front cover open)
Degree of Protection IP30
Direction of incoming supply as required
Lifespan, mechanical [Operations] 100000000
Weight 1.25 kg
Rated operational voltage [Ue ] 3 x 400 AC V
Voltage range Ue x 0.8 -1.1 V AC
Rated frequency [f] 50 - 60 Hz
Own power consumption per phase (rung) ≦ 2 (L2/L3) VA
Rated insulation voltage [Ui ] 400 V
Rated operating mode continuous operation
Rated impulse withstand voltage [Uimp] 4 kV
Rated voltage [Ue] 250 V AC
Interval between busbar centres 60 mm
Overvoltage category/pollution degree III/3
Rated operational current [Ie] 160 A
Rated conditional short-circuit current AC [Iq] 50 kAeff
Utilization category AC­22B
>Rated operating voltage [Ue]
690 V AC
Utilization category AC­22B
>Rated operating current [Ie]
160 A
Utilization category AC-23B
>Rated operating voltage [Ue]
500/400 V AC
Utilization category AC-23B
>Rated operating current [Ie]
125/160 A
Utilization category AC-21B
>Rated operating voltage [Ue]
690 V AC
Utilization category AC-21B
>Rated operating current [Ie]
160 A
Electrical ≧ 150000 Operations
Heat dissipation at Ith AC, without NH-SE 20 W
Number of poles 3 pole
Number of poles 3
Rated operational voltage [Ue]
>Rated operating voltage [Ue]
400 V AC
Rated frequency [f] 50 - 60 Hz
Rated operational current [Ie] 160 A
Conventional thermal current [Ith ] 160 A
Control mode Uninterrupted operation
Overvoltage category III
Utilization category AC 15
Rated impulse withstand voltage [Uimp] 4 kV
Power loss
>Fuse
20 W at 160 A W
Standards EN 60947-5-1
Rated voltage [Ue ] 250 V AC
Conventional thermal current [Ith ] 4 A
AC-15
>Rated operational voltage [Ue ]
230 V AC
AC-15
>Rated operational current
>AC-15 with 230 V [Ie]
1 A
Electrical ≧ 150000 Operations
Lifespan, mechanical [Operations] 100000000
Max. admissible back-up fuse 4 A gL
Frame size 00
Max. rated operational current gL/gG 160 A
Max. admissible heat dissipation NH-SE [Pv] 12 W
Box terminal
>Solid
2 x 2.5 mm2
Flange connection
>Diameter [d]
M8 mm
Flange connection
>Stranded with cable lug
1 x 70 mm2
Flange connection
>Flat busbar [max.]
20 x 8 mm
Box terminal
>Stranded
1.5 - 70 mm2
Box terminal
>Flat conductor [Lamellenzahl x Breite x Dicke ]
6 x 9 x 0.8 mm
Pick-up/drop-out time < 500 ms
Mounting on busbars
>Combi-base for busbars
direct on
12 - 30 x 5/10
Double T profile
Triple T profile
Terminals Lift terminals
Tightening torque of terminal screws 3 Nm
Lifespan, mechanical [Operations] 100000000
Overvoltage category/pollution degree III/3
Operating ambient temperature min. -5 °C
Operating ambient temperature max. +40 °C
Model Fuse switch disconnector
Double interrupting No
Rated permanent current Iu 160 A
Distance between rail centre, 40 mm No
Distance between rail centre, 50 mm No
Distance between rail centre, 60 mm Yes
Distance between rail centre, 100 mm No
Distance between rail centre, 185 mm No
Max. rated operation voltage Ue AC 690 V
Conditioned rated short-circuit current Iq 50 kA
Type of electrical connection of main circuit Rail connection
Number of poles 3
Construction size fuse insert NH00
Release indication Mechanical top-plate indicator

As Mnelko, we are a reliable partner in industrial automation solutions, offering high-quality and innovative products with a wide product range to meet all the needs of your business. Our product portfolio consists of solutions designed based on the principles of high performance, durability, and efficiency to support modern industrial processes.
All of our products ensure maximum reliability even in challenging working conditions and help your business operations run smoothly. The products we offer in industrial automation, energy management, cabling solutions, and many other areas adapt flexibly to the needs of different sectors.
Additionally, our products are manufactured using only high-quality materials and comply with international standards. Through the solutions we provide, we enable our customers to increase operational efficiency and optimize costs. Our company closely follows technological advancements and continuously offers innovative products to help our customers gain a competitive advantage.
On each of our product pages, you can find comprehensive information about technical details, areas of use, and product features. You can explore all the products you need to strengthen your industrial processes on our website and enjoy a seamless purchasing experience.

Similar Products

BBT-S60-30x10-CI
Eaton
BBT-S60-20x10-CI
Eaton
Z-SLS/NEOZ/3+PEN
Eaton