Low-voltage h.b.c fuse switch strip, 160A, 500V/160A, 690V/160A, size 00H.b.c fuse switch strip, rated operational current 160A, max. fuse-link 500V/160A, max. fuse-link 690V/160A, size 00, with safety monitoring
Low-voltage h.b.c fuse switch strip, 160A, 500V/160A, 690V/160A, size 00
H.b.c fuse switch strip, rated operational current 160A, max. fuse-link 500V/160A, max. fuse-link 690V/160A, size 00, with safety monitoring
Product range | 60 mm system |
Basic function | Busbar fuse material |
Subrange | Low-voltage h.b.c. switch-fuse units |
Description | With fuse monitoring With connection area cover Mounting with snap-on mechanism |
Information about equipment supplied | With clamp/screw connection set |
Interval between busbar centres | 60 mm |
Rated operational current [Ie] | 160 A |
400 V | 160 A |
Frame size | 00 |
For use with | 12 x 5/10 15 x 5/10 20 x 5/10 25 x 5/10 30 x 5/10 |
For use with | Double T profile Triple T profile |
Connection | top or bottom |
Notes | NH-fuse-links →#289998 |
Standards | IEC/EN 60255, VDE 0435 part 303 |
Climatic proofing | Damp heat, constant, to IEC 60068-2-78 Damp heat, cyclic, to IEC 60068-2-30 |
Ambient temperature | -5 - +40 |
Altitude | max. 2000 m m |
Interval between busbar centres | 60 mm |
Number of poles/phases | 3 n |
Mounting position | Vertical, horizontal |
Overvoltage category/pollution degree | III/3 |
Protection type | IP30 (Operating state) IP10 (Front cover open) |
Degree of Protection | IP30 |
Direction of incoming supply | as required |
Lifespan, mechanical [Operations] | 100000000 |
Weight | 1.25 kg |
Rated operational voltage [Ue ] | 3 x 400 AC V |
Voltage range | Ue x 0.8 -1.1 V AC |
Rated frequency [f] | 50 - 60 Hz |
Own power consumption per phase (rung) | ≦ 2 (L2/L3) VA |
Rated insulation voltage [Ui ] | 400 V |
Rated operating mode | continuous operation |
Rated impulse withstand voltage [Uimp] | 4 kV |
Rated voltage [Ue] | 250 V AC |
Interval between busbar centres | 60 mm |
Overvoltage category/pollution degree | III/3 |
Rated operational current [Ie] | 160 A |
Rated conditional short-circuit current AC [Iq] | 50 kAeff |
Utilization category AC22B >Rated operating voltage [Ue] |
690 V AC |
Utilization category AC22B >Rated operating current [Ie] |
160 A |
Utilization category AC-23B >Rated operating voltage [Ue] |
500/400 V AC |
Utilization category AC-23B >Rated operating current [Ie] |
125/160 A |
Utilization category AC-21B >Rated operating voltage [Ue] |
690 V AC |
Utilization category AC-21B >Rated operating current [Ie] |
160 A |
Electrical | ≧ 150000 Operations |
Heat dissipation at Ith AC, without NH-SE | 20 W |
Number of poles | 3 pole |
Number of poles | 3 |
Rated operational voltage [Ue] >Rated operating voltage [Ue] |
400 V AC |
Rated frequency [f] | 50 - 60 Hz |
Rated operational current [Ie] | 160 A |
Conventional thermal current [Ith ] | 160 A |
Control mode | Uninterrupted operation |
Overvoltage category | III |
Utilization category | AC 15 |
Rated impulse withstand voltage [Uimp] | 4 kV |
Power loss >Fuse |
20 W at 160 A W |
Standards | EN 60947-5-1 |
Rated voltage [Ue ] | 250 V AC |
Conventional thermal current [Ith ] | 4 A |
AC-15 >Rated operational voltage [Ue ] |
230 V AC |
AC-15 >Rated operational current >AC-15 with 230 V [Ie] |
1 A |
Electrical | ≧ 150000 Operations |
Lifespan, mechanical [Operations] | 100000000 |
Max. admissible back-up fuse | 4 A gL |
Frame size | 00 |
Max. rated operational current gL/gG | 160 A |
Max. admissible heat dissipation NH-SE [Pv] | 12 W |
Box terminal >Solid |
2 x 2.5 mm2 |
Flange connection >Diameter [d] |
M8 mm |
Flange connection >Stranded with cable lug |
1 x 70 mm2 |
Flange connection >Flat busbar [max.] |
20 x 8 mm |
Box terminal >Stranded |
1.5 - 70 mm2 |
Box terminal >Flat conductor [Lamellenzahl x Breite x Dicke ] |
6 x 9 x 0.8 mm |
Pick-up/drop-out time | < 500 ms |
Mounting on busbars >Combi-base for busbars |
direct on 12 - 30 x 5/10 Double T profile Triple T profile |
Terminals | Lift terminals |
Tightening torque of terminal screws | 3 Nm |
Lifespan, mechanical [Operations] | 100000000 |
Overvoltage category/pollution degree | III/3 |
Operating ambient temperature min. | -5 °C |
Operating ambient temperature max. | +40 °C |
Model | Fuse switch disconnector |
Double interrupting | No |
Rated permanent current Iu | 160 A |
Distance between rail centre, 40 mm | No |
Distance between rail centre, 50 mm | No |
Distance between rail centre, 60 mm | Yes |
Distance between rail centre, 100 mm | No |
Distance between rail centre, 185 mm | No |
Max. rated operation voltage Ue AC | 690 V |
Conditioned rated short-circuit current Iq | 50 kA |
Type of electrical connection of main circuit | Rail connection |
Number of poles | 3 |
Construction size fuse insert | NH00 |
Release indication | Mechanical top-plate indicator |
As Mnelko, we are a reliable partner in industrial automation solutions, offering high-quality and innovative products with a wide product range to meet all the needs of your business. Our product portfolio consists of solutions designed based on the principles of high performance, durability, and efficiency to support modern industrial processes.
All of our products ensure maximum reliability even in challenging working conditions and help your business operations run smoothly. The products we offer in industrial automation, energy management, cabling solutions, and many other areas adapt flexibly to the needs of different sectors.
Additionally, our products are manufactured using only high-quality materials and comply with international standards. Through the solutions we provide, we enable our customers to increase operational efficiency and optimize costs. Our company closely follows technological advancements and continuously offers innovative products to help our customers gain a competitive advantage.
On each of our product pages, you can find comprehensive information about technical details, areas of use, and product features. You can explore all the products you need to strengthen your industrial processes on our website and enjoy a seamless purchasing experience.