alt
alt

N4-4-1200-S15-PV-NA
179330 N4-4-1200-S15-PV-NA
179330

Molded Case Switch 4p 1200A 1500VDC ULMolded Case Switch N..DC in the special version for up to 1500 VDC can be used on 1 or 2 poles. The comply with the isolation properties even for earthed IT networks. Accessories as e.g. bridge kits, connection terminals and door coupling rotary handles enable individual installation in the most varied of distribution systems. Auxiliary contacts, voltage releases and remote operators facilitate signaling and automation. Notes: main switch characteristics including positive drive according to IEC/EN 60204 und VDE 0113. Isolating characteristics according to IEC/EN 60947-3 and VDE 0660. Approved according to UL489B. Terminal type: a series connection is required for 2 pole switching according to the specified connection options. See accessories bridge kits. Switch can not be combined with plug-in / withdrawable units and / or connection on rear.

Molded Case Switch 4p 1200A 1500VDC UL
Molded Case Switch N..DC in the special version for up to 1500 VDC can be used on 1 or 2 poles. The comply with the isolation properties even for earthed IT networks. Accessories as e.g. bridge kits, connection terminals and door coupling rotary handles enable individual installation in the most varied of distribution systems. Auxiliary contacts, voltage releases and remote operators facilitate signaling and automation. Notes: main switch characteristics including positive drive according to IEC/EN 60204 und VDE 0113. Isolating characteristics according to IEC/EN 60947-3 and VDE 0660. Approved according to UL489B. Terminal type: a series connection is required for 2 pole switching according to the specified connection options. See accessories bridge kits. Switch can not be combined with plug-in / withdrawable units and / or connection on rear.

Product range Switch-disconnectors
Protective function Disconnectors/main switches
Photovoltaic applications
Product range DC switch-disconnectors
Application field Utility buildings
Open areas
Part no. N…PV-NA
Standard/Approval UL489B
IEC 60947-3
CE
CCC
Rated operational voltage 1500
Installation type Fixed
Construction size N4
Description Main switch characteristics including positive drive to IEC/EN 60204 and VDE 0113.
Isolating characteristics to IEC/EN 60947-3 and VDE 0660.
N switch-disconnectors can, in addition, be combined with NZM...-XU, NZM...-XA shunt releases and auxiliary contacts as well as with NZM...-XR... remote operator.
For DC switching, all 4 contacts must be connected in series. Refer to the information on jumper kit accessories.
When working with ungrounded systems (e.g., IT), the installation must ensure that a double ground fault will be impossible.
Switch can not be combined with plug-in/withdrawable units and/or connection on rear.
Within the scope of application for UL489B, the switch cannot be combined with connection width extensions, module plates, or band terminals either.
N4-4-...-S15-DC feeder unit and outgoer from the bottom only.
Suitable for 100%-rated application together with an enclosure with minimum dimensions of 1200 x 600 x 275 mm (WxHxD).
Does not provide any overcurrent protection.
Connection options 1230DRW-12061230DRW-13351230DRW-1369
Number of poles 4-pole basic device, usable in a 1-pole or 2-pole configuration depending on the type of connection
Standard equipment Screw connection
Switch positions I, +, 0
Rated current = rated uninterrupted current [In = Iu] 1200 A
Remotely control / trip Optionally with XR remote operator/Can be optionally controlled remotely with XU/XA shunt release
Rated operating frequency DC
Rated operational voltage, max. [Ue] 1500 V DC
Rated uninterrupted current with terminal jumpers
>at 40°
1200
Rated uninterrupted current with terminal jumpers
>at 65°
1200
Rated uninterrupted current with terminal jumpers Values for rated uninterrupted current at 65 °C include jumpers.
Utilization category DC21A
Rated operational current [Ie ]
>DC-21B [Ie]
1200 CSA
Overvoltage category/pollution degree III/3
Rated insulation voltage [Ui ] 1500 V
Ambient temperature
>Ambient temperature, storage
- 40 - + 70 °C
Ambient temperature
>Operation
-25 - +70 °C
t = 0.1 s [Icw] 34 kA
Max. operating frequency 60 Ops/h
Lifespan, mechanical [Operations] 10000
Electrical [Operations] Lifespan, mechanical: of which max. 50 % trip by shunt/undervoltage release
Standard equipment 500
Round copper conductor
>Tunnel terminal
>Stranded
>4-hole
Screw connection
Round copper conductor
>Bolt terminals
>Direct on the switch
>Stranded
4 x (50 - 240) mm2
Round copper conductor
>Bolt terminals
>Module plate
>Single hole [min.]
1 x (120 - 185)
4 x (50 - 185) mm2
Round copper conductor
>Bolt terminals
>Module plate
>Single hole [max.]
1 x (120 - 300) mm2
Round copper conductor
>Bolt terminals
>Module plate
>Double hole [min.]
2 x (95 - 300) mm2
Round copper conductor
>Bolt terminals
>Module plate
>Double hole [max.]
2 x (95 - 185) mm2
Round copper conductor
>Bolt terminals
>Connection width extension
>Connection width extension
4 x (35 - 185) mm2
Al conductors, Cu cable
>Tunnel terminal
>Stranded
>4-hole
4 x 300
6 x (95 - 240) mm2
Al conductors, Cu cable
>Bolt terminal and rear-side connection
>Flat copper strip, with holes [min.]
4 x (50 - 240) mm2
Al conductors, Cu cable
>Bolt terminal and rear-side connection
>Flat copper strip, with holes [max.]
(2 x) 10 x 50 x 1.0 mm
Al conductors, Cu cable
>Bolt terminal and rear-side connection
>Connection width extension
(2 x) 10 x 50 x 1.0 mm
Cu strip (number of segments x width x segment thickness)
>Flat conductor terminal [min.]
(2 x) 10 x 80 x 1,0 mm
Cu strip (number of segments x width x segment thickness)
>Flat conductor terminal [max.]
6 x 16 x 0.8 mm
Cu strip (number of segments x width x segment thickness)
>Module plate
>Single hole
(2 x) 10 x 32 x 1.0 mm
Cu strip (number of segments x width x segment thickness)
>Bolt terminal and rear-side connection
>Flat copper strip, with holes [min.]
(2 x) 10 x 50 x 1,0 mm
Cu strip (number of segments x width x segment thickness)
>Bolt terminal and rear-side connection
>Flat copper strip, with holes [max.]
(2 x) 10 x 50 x 1.0 mm
Cu strip (number of segments x width x segment thickness)
>Bolt terminal and rear-side connection
>Connection width extension
(2 x) 10 x 50 x 1.0 mm
Copper busbar (width x thickness) [mm]
>Bolt terminal and rear-side connection
>Screw connection
(2 x) 10 x 80 x 1,0 mm
Copper busbar (width x thickness) [mm]
>Bolt terminal and rear-side connection
>Direct on the switch [min.]
M10
Copper busbar (width x thickness) [mm]
>Bolt terminal and rear-side connection
>Direct on the switch [max.]
25 x 5 mm
Copper busbar (width x thickness) [mm]
>Bolt terminal and rear-side connection
>Module plate
>Single hole [min.]
2 x (50 x 10)
2 x (80 x 10) mm
Copper busbar (width x thickness) [mm]
>Bolt terminal and rear-side connection
>Module plate
>Single hole [max.]
25 x 5 mm
Copper busbar (width x thickness) [mm]
>Bolt terminal and rear-side connection
>Module plate
>Double hole
2 x (50 x 10) mm
Copper busbar (width x thickness) [mm]
>Bolt terminal and rear-side connection
>Connection width extension
>Connection width extension [min.]
2 x (50 x 10) mm
Copper busbar (width x thickness) [mm]
>Bolt terminal and rear-side connection
>Connection width extension
>Connection width extension [max.]
60 x 10 mm
Rated operational current for specified heat dissipation [In] 2 x (10 x 80) mm
Equipment heat dissipation, current-dependent [Pvid] 1200 A
Operating ambient temperature min. 231 W
Operating ambient temperature max. -25 °C
10.2 Strength of materials and parts
>10.2.2 Corrosion resistance
+70 °C
10.2 Strength of materials and parts
>10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard´s requirements.
10.2 Strength of materials and parts
>10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard´s requirements.
10.2 Strength of materials and parts
>10.2.3.3 Verification of resistance of insulating materials to abnormal heat and fire due to internal electric effects
Meets the product standard´s requirements.
10.2 Strength of materials and parts
>10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard´s requirements.
10.2 Strength of materials and parts
>10.2.5 Lifting
Meets the product standard´s requirements.
10.2 Strength of materials and parts
>10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2 Strength of materials and parts
>10.2.7 Inscriptions
Does not apply, since the entire switchgear needs to be evaluated.
10.3 Degree of protection of ASSEMBLIES Meets the product standard´s requirements.
10.4 Clearances and creepage distances Does not apply, since the entire switchgear needs to be evaluated.
10.5 Protection against electric shock Meets the product standard´s requirements.
10.6 Incorporation of switching devices and components Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections Does not apply, since the entire switchgear needs to be evaluated.
10.8 Connections for external conductors Is the panel builder´s responsibility.
10.9 Insulation properties
>10.9.2 Power-frequency electric strength
Is the panel builder´s responsibility.
10.9 Insulation properties
>10.9.3 Impulse withstand voltage
Is the panel builder´s responsibility.
10.9 Insulation properties
>10.9.4 Testing of enclosures made of insulating material
Is the panel builder´s responsibility.
10.10 Temperature rise Is the panel builder´s responsibility.
10.11 Short-circuit rating The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.12 Electromagnetic compatibility Is the panel builder´s responsibility. The specifications for the switchgear must be observed.
10.13 Mechanical function Is the panel builder´s responsibility. The specifications for the switchgear must be observed.
Version as main switch The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
Version as maintenance-/service switch Yes
Version as safety switch Yes
Version as emergency stop installation No
Version as reversing switch Yes
Number of switches No
Max. rated operation voltage Ue AC 1
Rated operating voltage 0 V
Rated permanent current Iu 1500 - 1500 V
Rated permanent current at AC-23, 400 V 1200 A
Rated permanent current at AC-21, 400 V 0 A
Rated operation power at AC-3, 400 V 0 A
Rated short-time withstand current lcw 0 kW
Rated operation power at AC-23, 400 V 34 kA
Switching power at 400 V 0 kW
Conditioned rated short-circuit current Iq 0 kW
Number of poles 0 kA
Number of auxiliary contacts as normally closed contact 4
Number of auxiliary contacts as normally open contact 0
Number of auxiliary contacts as change-over contact 0
Motor drive optional 0
Motor drive integrated Yes
Voltage release optional No
Device construction Yes
Suitable for ground mounting Built-in device fixed built-in technique
Suitable for front mounting 4-hole Yes
Suitable for front mounting centre No
Suitable for distribution board installation No
Suitable for intermediate mounting Yes
Colour control element Yes
Type of control element Black
Interlockable Rocker lever
Type of electrical connection of main circuit Yes
Degree of protection (IP), front side Screw connection
Degree of protection (NEMA) IP20
Product Standards
UL File No. UL 489B; IEC 60947-3; CE marking; CCC
CSA File No. E471671
CSA Class No. -
North America Certification ---
Specially designed for North America UL listed
Suitable for No
Current Limiting Circuit-Breaker Feeder circuits, branch circuits
Max. Voltage Rating No
Degree of Protection 1500 VDC

As Mnelko, we are a reliable partner in industrial automation solutions, offering high-quality and innovative products with a wide product range to meet all the needs of your business. Our product portfolio consists of solutions designed based on the principles of high performance, durability, and efficiency to support modern industrial processes.
All of our products ensure maximum reliability even in challenging working conditions and help your business operations run smoothly. The products we offer in industrial automation, energy management, cabling solutions, and many other areas adapt flexibly to the needs of different sectors.
Additionally, our products are manufactured using only high-quality materials and comply with international standards. Through the solutions we provide, we enable our customers to increase operational efficiency and optimize costs. Our company closely follows technological advancements and continuously offers innovative products to help our customers gain a competitive advantage.
On each of our product pages, you can find comprehensive information about technical details, areas of use, and product features. You can explore all the products you need to strengthen your industrial processes on our website and enjoy a seamless purchasing experience.

Similar Products

NZMH2-4-VX250/VAR
Eaton
NZMH2-VX250-SVE
Eaton
NZMS2-4-VX250/VAR
Eaton
NZMS2-4-VX160
Eaton
NZMS2-MX220-SVE
Eaton
NZMS2-VX250-SVE
Eaton
NZMN2-4-VX160/VAR
Eaton
NZMN2-VX100-BT
Eaton