DOL starter, 380 V 400 V 415 V: 7.5 kW, Ir= 10 - 16 A, 230 V 50 Hz, 240 V 60 Hz, AC voltageDOL starter, Basic device: MSC, Notes: Not suitable for motors with efficiency class IE3., Motor ratings Motor rating AC-3 380 V 400 V 415 V: P= 7.5 kW, Setting range of overload releases: Ir= 10 - 16 A, Coordination: Type of coordination “1”, Actuating voltage: 230 V 50 Hz, 240 V 60 Hz, AC voltage, Standards: UL 508 (on request), CSA C 22.2 No. 14 (on request)

DOL starter, 380 V 400 V 415 V: 7.5 kW, Ir= 10 - 16 A, 230 V 50 Hz, 240 V 60 Hz, AC voltage
DOL starter, Basic device: MSC, Notes: Not suitable for motors with efficiency class IE3., Motor ratings Motor rating AC-3 380 V 400 V 415 V: P= 7.5 kW, Setting range of overload releases: Ir= 10 - 16 A, Coordination: Type of coordination “1”, Actuating voltage: 230 V 50 Hz, 240 V 60 Hz, AC voltage, Standards: UL 508 (on request), CSA C 22.2 No. 14 (on request)

Basic function DOL starters (complete devices)
Basic device MSC
Notes Not suitable for motors with efficiency class IE3.
Connection to SmartWire-DT no
Motor rating [P]
>AC-3
>380 V 400 V 415 V [P]
7.5 kW
Rated operational current
>AC-3
>380 V 400 V 415 V [Ie]
15.2 A
Rated short-circuit current 380 - 415 V [Iq ] 50 kA
Setting range of overload releases [Ir] 10 - 16 A
Coordination Type of coordination “1”
Contact sequence 1210SWI-16
Actuating voltage 230 V 50 Hz, 240 V 60 Hz
Motor-protective circuit-breakers AC voltage
Contactor PKZM0-16 Type
DOL starter wiring set

Mechanical connection element and electrical electric contact module
DILM15-10(…) Part no.
Notes PKZM0-XDM12 Type
Standards

The DOL starters (complete units) consist of a PKZM0 motor protective circuit breaker and a DILM contactor. These combinations are mounted on the busbar adapters.

The connection of the main circuit between the motor protective circuit breaker and the contactor is established with an electrical contact module.

Cannot be combined with NHI-E-…-PKZ0-C standard auxiliary contact with spring-cage terminal.

Further informationPage
Technical data PKZM0→ PKZM0
Accessories PKZ→ 072896
Technical data DILM→ DILM
Accessories DILM→ 281199
Rated impulse withstand voltage [Uimp]
UL 508 (on request)
CSA C 22.2 No. 14 (on request)
Overvoltage category/pollution degree 6000 V AC
Rated operational voltage [Ue] III/3
Rated operational current
>Open, 3-pole: 50 – 60 Hz
>380 V 400 V [Ie]
230 - 415 V
Motor protective circuit breaker PKZM0, PKE 15 A
DILM contactors
>Power consumption of the coil in a cold state and 1.0 x US
>Dual-voltage coil 50 Hz [Sealing]
PKZM0 motor-protective circuit-breakers, see motor-protective circuit-breakers/PKZM0 product group
DILM contactors, see contactor product group
DILET timing relay, ETR, see contactors, electronic timing relays product group
Auxiliary contacts
>Pilot Duty
>AC operated
1.2 W
Auxiliary contacts
>Pilot Duty
>DC operated
A600
Auxiliary contacts
>General Use
>AC
P300
Auxiliary contacts
>General Use
>AC
600 V
Auxiliary contacts
>General Use
>DC
15 A
Auxiliary contacts
>General Use
>DC
250 V
Rated operational current for specified heat dissipation [In] 1 A
Heat dissipation per pole, current-dependent [Pvid] 15.5 A
Equipment heat dissipation, current-dependent [Pvid] 3.7 W
Static heat dissipation, non-current-dependent [Pvs] 11.1 W
Heat dissipation capacity [Pdiss] 1.4 W
Operating ambient temperature min. 0 W
Operating ambient temperature max. -25 °C
10.2 Strength of materials and parts
>10.2.2 Corrosion resistance
+55 °C
10.2 Strength of materials and parts
>10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard´s requirements.
10.2 Strength of materials and parts
>10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard´s requirements.
10.2 Strength of materials and parts
>10.2.3.3 Verification of resistance of insulating materials to abnormal heat and fire due to internal electric effects
Meets the product standard´s requirements.
10.2 Strength of materials and parts
>10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard´s requirements.
10.2 Strength of materials and parts
>10.2.5 Lifting
Meets the product standard´s requirements.
10.2 Strength of materials and parts
>10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2 Strength of materials and parts
>10.2.7 Inscriptions
Does not apply, since the entire switchgear needs to be evaluated.
10.3 Degree of protection of ASSEMBLIES Meets the product standard´s requirements.
10.4 Clearances and creepage distances Does not apply, since the entire switchgear needs to be evaluated.
10.5 Protection against electric shock Meets the product standard´s requirements.
10.6 Incorporation of switching devices and components Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections Does not apply, since the entire switchgear needs to be evaluated.
10.8 Connections for external conductors Is the panel builder´s responsibility.
10.9 Insulation properties
>10.9.2 Power-frequency electric strength
Is the panel builder´s responsibility.
10.9 Insulation properties
>10.9.3 Impulse withstand voltage
Is the panel builder´s responsibility.
10.9 Insulation properties
>10.9.4 Testing of enclosures made of insulating material
Is the panel builder´s responsibility.
10.10 Temperature rise Is the panel builder´s responsibility.
10.11 Short-circuit rating The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.12 Electromagnetic compatibility Is the panel builder´s responsibility. The specifications for the switchgear must be observed.
10.13 Mechanical function Is the panel builder´s responsibility. The specifications for the switchgear must be observed.
Kind of motor starter The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
With short-circuit release Direct starter
Rated control supply voltage Us at AC 50HZ Yes
Rated control supply voltage Us at AC 60HZ 230 - 230 V
Rated control supply voltage Us at DC 0 - 0 V
Voltage type for actuating 0 - 0 V
Rated operation power at AC-3, 230 V, 3-phase AC
Rated operation power at AC-3, 400 V 4 kW
Rated power, 460 V, 60 Hz, 3-phase 7.5 kW
Rated power, 575 V, 60 Hz, 3-phase 0 kW
Rated operation current Ie 0 kW
Rated operation current at AC-3, 400 V 15.2 A
Overload release current setting 15 A
Rated conditional short-circuit current, type 1, 480 Y/277 V 10 - 16 A
Rated conditional short-circuit current, type 1, 600 Y/347 V 0 A
Rated conditional short-circuit current, type 2, 230 V 0 A
Rated conditional short-circuit current, type 2, 400 V 0 A
Number of auxiliary contacts as normally open contact 0 A
Number of auxiliary contacts as normally closed contact 1
Ambient temperature, upper operating limit 0
Temperature compensated overload protection 60 °C
Release class Yes
Type of electrical connection of main circuit CLASS 10
Type of electrical connection for auxiliary- and control current circuit Screw connection
Rail mounting possible Screw connection
With transformer Yes
Number of command positions No
Suitable for emergency stop 0
Coordination class according to IEC 60947-4-3 No
Number of indicator lights Class 1
External reset possible 0
With fuse No
Degree of protection (IP) No
Degree of protection (NEMA) IP20
Supporting protocol for TCP/IP Other
Supporting protocol for PROFIBUS No
Supporting protocol for CAN No
Supporting protocol for INTERBUS No
Supporting protocol for ASI No
Supporting protocol for MODBUS No
Supporting protocol for Data-Highway No
Supporting protocol for DeviceNet No
Supporting protocol for SUCONET No
Supporting protocol for LON No
Supporting protocol for PROFINET IO No
Supporting protocol for PROFINET CBA No
Supporting protocol for SERCOS No
Supporting protocol for Foundation Fieldbus No
Supporting protocol for EtherNet/IP No
Supporting protocol for AS-Interface Safety at Work No
Supporting protocol for DeviceNet Safety No
Supporting protocol for INTERBUS-Safety No
Supporting protocol for PROFIsafe No
Supporting protocol for SafetyBUS p No
Supporting protocol for other bus systems No
Width No
Height 45 mm
Depth 200 mm
Product Standards 154 mm
UL File No. UL60947-4-1A; CSA-C22.2 No. 14-10; IEC60947-4-1; CE marking
UL Category Control No. E123500
CSA File No. NKJH
CSA Class No. 12528
North America Certification 3211-04
Specially designed for North America UL listed, CSA certified

As Mnelko, we are a reliable partner in industrial automation solutions, offering high-quality and innovative products with a wide product range to meet all the needs of your business. Our product portfolio consists of solutions designed based on the principles of high performance, durability, and efficiency to support modern industrial processes.
All of our products ensure maximum reliability even in challenging working conditions and help your business operations run smoothly. The products we offer in industrial automation, energy management, cabling solutions, and many other areas adapt flexibly to the needs of different sectors.
Additionally, our products are manufactured using only high-quality materials and comply with international standards. Through the solutions we provide, we enable our customers to increase operational efficiency and optimize costs. Our company closely follows technological advancements and continuously offers innovative products to help our customers gain a competitive advantage.
On each of our product pages, you can find comprehensive information about technical details, areas of use, and product features. You can explore all the products you need to strengthen your industrial processes on our website and enjoy a seamless purchasing experience.

Similar Products

MSC-D-0,4-M7(230V50HZ)/BBA
Eaton
MSC-D-0,25-M7(230V50HZ)/BBA
Eaton
MSC-D-0,63-M7(230V50HZ)/BBA
Eaton
Z-SS-60-ADD/6-54
Eaton
BBA2-80/2TS-S
Eaton
Z-D02/SIKA-HF
Eaton