Basic function accessories |
Contact elements |
Connection technique |
Screw terminals |
Fixing |
Front fixing |
Degree of Protection |
IP20 |
Connection to SmartWire-DT |
no |
Approval |
|
N/C = Normally closed |
1 NC |
Notes |
= safety function, by positive opening to IEC/EN 60947-5-1 |
[mm] |
4.8 |
Maximum travel [mm] |
5.7 |
Minimum force for positive opening [ N] |
15 |
Contact sequence |
|
Contact diagram |
|
Configuration |
|
Connection type |
Single contact |
Connection technique |
Screw terminals |
Standards |
IEC 60947-5-1 |
Lifespan, mechanical [Operations] |
> 5 x 106 |
Operating frequency [Operations/h] |
≦ 3600 |
Actuating force |
≦ 5 n |
Operating torque (screw terminals) |
≦ 0.8 Nm |
Degree of Protection |
IP20 |
Climatic proofing |
Damp heat, constant, to IEC 60068-2-78 Damp heat, cyclic, to IEC 60068-2-30 |
Ambient temperature >Open |
-25 - +70 °C |
Mechanical shock resistance to IEC 60068-2-27 Shock duration 11 ms, half-sinusoidal |
> 30 g |
Terminal capacities >Solid |
0.75 - 2.5 mm2 |
Terminal capacities >Stranded |
0.5 - 2.5 mm2
|
Terminal capacities >Flexible with ferrule |
0.5 - 1.5 mm2 |
Rated impulse withstand voltage [Uimp] |
6000 V AC |
Rated insulation voltage [Ui
] |
500 V |
Overvoltage category/pollution degree |
III/3 |
Control circuit reliability >at 24 V DC/5 mA [HF
] |
< 10-7 (i.e. 1 failure to 107 operations) Fault probability |
Control circuit reliability >at 5 V DC/1 mA [HF
] |
< 5 x 10-6 (i.e. 1 failure in 5 x 106 operations) Fault probability |
Max. short-circuit protective device >Fuseless |
PKZM0-10/FAZ-B6/1 Type |
Max. short-circuit protective device >Fuse [gG/gL] |
10 A |
Rated operational current [Ie
] >AC-15 >115 V [Ie
] |
6 A |
Rated operational current [Ie
] >AC-15 >220 V 230 V 240 V [Ie] |
6 A |
Rated operational current [Ie
] >AC-15 >380 V 400 V 415 V [Ie] |
4 A |
Rated operational current [Ie
] >AC-15 >500 V [Ie] |
2 A |
Rated operational current [Ie
] >DC-13 >24 V [Ie
] |
3 A |
Rated operational current [Ie
] >DC-13 >42 V [Ie
] |
1.7 A |
Rated operational current [Ie
] >DC-13 >60 V [Ie
] |
1.2 A |
Rated operational current [Ie
] >DC-13 >110 V [Ie
] |
0.6 A |
Rated operational current [Ie
] >DC-13 >220 V [Ie
] |
0.3 A |
Lifespan, electrical >AC-15 >230 V/0.5 A [Operations] |
1.6 x 106 |
Lifespan, electrical >AC-15 >230 V/1.0 A [Operations] |
1 x 106 |
Lifespan, electrical >AC-15 >230 V/3.0 A [Operations] |
0.7 x 106 |
Lifespan, electrical >DV-13 >12 V/2.8 A [Operations] |
1.2 x 106 |
Rated conditional short-circuit current [Iq] |
1 kA |
Rated operational current for specified heat dissipation [In] |
6 A |
Heat dissipation per pole, current-dependent [Pvid] |
0.11 W |
Equipment heat dissipation, current-dependent [Pvid] |
0 W |
Static heat dissipation, non-current-dependent [Pvs] |
0 W |
Heat dissipation capacity [Pdiss] |
0 W |
Operating ambient temperature min. |
-25 °C |
Operating ambient temperature max. |
+70 °C |
10.2 Strength of materials and parts >10.2.2 Corrosion resistance |
Meets the product standard´s requirements. |
10.2 Strength of materials and parts >10.2.3.1 Verification of thermal stability of enclosures |
Meets the product standard´s requirements. |
10.2 Strength of materials and parts >10.2.3.2 Verification of resistance of insulating materials to normal heat |
Meets the product standard´s requirements. |
10.2 Strength of materials and parts >10.2.3.3 Verification of resistance of insulating materials to abnormal heat and fire due to internal electric effects |
Meets the product standard´s requirements. |
10.2 Strength of materials and parts >10.2.4 Resistance to ultra-violet (UV) radiation |
Meets the product standard´s requirements. |
10.2 Strength of materials and parts >10.2.5 Lifting |
Does not apply, since the entire switchgear needs to be evaluated. |
10.2 Strength of materials and parts >10.2.6 Mechanical impact |
Does not apply, since the entire switchgear needs to be evaluated. |
10.2 Strength of materials and parts >10.2.7 Inscriptions |
Meets the product standard´s requirements. |
10.3 Degree of protection of ASSEMBLIES |
Does not apply, since the entire switchgear needs to be evaluated. |
10.4 Clearances and creepage distances |
Meets the product standard´s requirements. |
10.5 Protection against electric shock |
Does not apply, since the entire switchgear needs to be evaluated. |
10.6 Incorporation of switching devices and components |
Does not apply, since the entire switchgear needs to be evaluated. |
10.7 Internal electrical circuits and connections |
Is the panel builder´s responsibility. |
10.8 Connections for external conductors |
Is the panel builder´s responsibility. |
10.9 Insulation properties >10.9.2 Power-frequency electric strength |
Is the panel builder´s responsibility. |
10.9 Insulation properties >10.9.3 Impulse withstand voltage |
Is the panel builder´s responsibility. |
10.9 Insulation properties >10.9.4 Testing of enclosures made of insulating material |
Is the panel builder´s responsibility. |
10.10 Temperature rise |
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices. |
10.11 Short-circuit rating |
Is the panel builder´s responsibility. The specifications for the switchgear must be observed. |
10.12 Electromagnetic compatibility |
Is the panel builder´s responsibility. The specifications for the switchgear must be observed. |
10.13 Mechanical function |
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed. |
Number of contacts as change-over contact |
0 |
Number of contacts as normally open contact |
0 |
Number of contacts as normally closed contact |
1 |
Number of fault-signal switches |
0 |
Rated operation current Ie at AC-15, 230 V |
6 A |
Type of electric connection |
Screw connection |
Model |
Top mounting |
Mounting method |
Front fastening |
Lamp holder |
None |
Product Standards |
IEC/EN 60947-5; UL 508; CSA-C22.2 No. 14-05; CSA-C22.2 No. 94-91; CE marking |
UL File No. |
E29184 |
UL Category Control No. |
NKCR |
CSA File No. |
012528 |
CSA Class No. |
3211-03 |
North America Certification |
UL listed, CSA certified |
Degree of Protection |
UL/CSA Type: - |