alt
alt

LS-XB-ZB
106872 LS-XB-ZB
106872

Actuator, form XBIEC EN 60947-5-1, IP66_x, approval of employers´ liability insurance Association GS-ET-15, device for world markets, accessories for safety position switches for protection of personnel with separated actuator for protective shrouds, necessary actuation, and positive-opening contacts

Actuator, form XB
IEC EN 60947-5-1, IP66_x, approval of employers´ liability insurance Association GS-ET-15, device for world markets, accessories for safety position switches for protection of personnel with separated actuator for protective shrouds, necessary actuation, and positive-opening contacts

Basic function actuators
Part group reference LS(4)…ZB
Function Flat actuator
Description With the actuator inserted, the N/O contact is open and the NC contact is closed.
For use with LS…ZB
Standards IEC/EN 60947
Climatic proofing Damp heat, constant, to IEC 60068-2-78; damp heat, cyclical, to IEC 60068-2-30
Mounting position As required
Terminal capacities
>Solid
1 x (0.75 - 2.5)
2 x (0.75 - 1.5) mm2
Terminal capacities
>Flexible with ferrule
1 x (0.5 - 1.5)
2 x (0.5 - 1.5) mm2
Repetition accuracy 0.02 mm
Rated impulse withstand voltage [Uimp] 6000 V AC
Rated insulation voltage [Ui ] 500 V
Rated operational current [Ie ]
>AC-15
>24 V [Ie ]
10 A
Rated operational current [Ie ]
>AC-15
>220 V 230 V 240 V [Ie]
6 A
Rated operational current [Ie ]
>AC-15
>380 V 400 V 415 V [Ie]
4 A
Rated operational current [Ie ]
>DC-13
>24 V [Ie ]
3 A
Rated operational current [Ie ]
>DC-13
>110 V [Ie ]
0.8 A
Rated operational current [Ie ]
>DC-13
>220 V [Ie ]
0.3 A
Supply frequency max. 400 Hz
Short-circuit rating to IEC/EN 60947-5-1
>max. fuse
6 A gG/gL
Mechanical shock resistance (half-sinusoidal shock, 20 ms)
>Standard-action contact
25 g
Operating frequency [Operations/h] ≦ 1800
Rated operational current for specified heat dissipation [In] 0 A
Heat dissipation per pole, current-dependent [Pvid] 0 W
Equipment heat dissipation, current-dependent [Pvid] 0 W
Static heat dissipation, non-current-dependent [Pvs] 0 W
Heat dissipation capacity [Pdiss] 0 W
10.2 Strength of materials and parts
>10.2.2 Corrosion resistance
Meets the product standard´s requirements.
10.2 Strength of materials and parts
>10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard´s requirements.
10.2 Strength of materials and parts
>10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard´s requirements.
10.2 Strength of materials and parts
>10.2.3.3 Verification of resistance of insulating materials to abnormal heat and fire due to internal electric effects
Meets the product standard´s requirements.
10.2 Strength of materials and parts
>10.2.4 Resistance to ultra-violet (UV) radiation
Please enquire
10.2 Strength of materials and parts
>10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
10.2 Strength of materials and parts
>10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2 Strength of materials and parts
>10.2.7 Inscriptions
Meets the product standard´s requirements.
10.3 Degree of protection of ASSEMBLIES Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances Meets the product standard´s requirements.
10.5 Protection against electric shock Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections Is the panel builder´s responsibility.
10.8 Connections for external conductors Is the panel builder´s responsibility.
10.9 Insulation properties
>10.9.2 Power-frequency electric strength
Is the panel builder´s responsibility.
10.9 Insulation properties
>10.9.3 Impulse withstand voltage
Is the panel builder´s responsibility.
10.9 Insulation properties
>10.9.4 Testing of enclosures made of insulating material
Is the panel builder´s responsibility.
10.10 Temperature rise Not applicable.
10.11 Short-circuit rating Is the panel builder´s responsibility. The specifications for the switchgear must be observed.
10.12 Electromagnetic compatibility Is the panel builder´s responsibility. The specifications for the switchgear must be observed.
10.13 Mechanical function The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
Model Actuator with horizontal mounting

As Mnelko, we are a reliable partner in industrial automation solutions, offering high-quality and innovative products with a wide product range to meet all the needs of your business. Our product portfolio consists of solutions designed based on the principles of high performance, durability, and efficiency to support modern industrial processes.
All of our products ensure maximum reliability even in challenging working conditions and help your business operations run smoothly. The products we offer in industrial automation, energy management, cabling solutions, and many other areas adapt flexibly to the needs of different sectors.
Additionally, our products are manufactured using only high-quality materials and comply with international standards. Through the solutions we provide, we enable our customers to increase operational efficiency and optimize costs. Our company closely follows technological advancements and continuously offers innovative products to help our customers gain a competitive advantage.
On each of our product pages, you can find comprehensive information about technical details, areas of use, and product features. You can explore all the products you need to strengthen your industrial processes on our website and enjoy a seamless purchasing experience.