alt
alt

LS-02-CC/RL
156509 LS-02-CC/RL
156509

Position switch, Rotary lever, Complete device, 2 NC, Cage Clamp, Yellow, Insulated material, -40 - +70 °C, EN 50047 Form AIEC EN 60947-5-1, high degree of protection IP66, device for world markets, modular system, also for use in safety circuits, by positive operation and positive opening contacts. Easy mounting technology operating heads can be attached in any 4 directions and snapped on simple, quick and safely using the bayonet fitting. They are equipped with Cage Clamp or screw terminals and are available with metal or insulated enclosures., suitable for use with electronic devices to IEC/EN 61131-2

Position switch, Rotary lever, Complete device, 2 NC, Cage Clamp, Yellow, Insulated material, -40 - +70 °C, EN 50047 Form A
IEC EN 60947-5-1, high degree of protection IP66, device for world markets, modular system, also for use in safety circuits, by positive operation and positive opening contacts. Easy mounting technology operating heads can be attached in any 4 directions and snapped on simple, quick and safely using the bayonet fitting. They are equipped with Cage Clamp or screw terminals and are available with metal or insulated enclosures., suitable for use with electronic devices to IEC/EN 61131-2

Product range Rotary lever
Degree of Protection IP66, IP67
Features Complete device
Ambient temperature -40 - +70 °C
Design EN 50047 Form A
N/C = Normally closed 2 NC
Notes = safety function, by positive opening to IEC/EN 60947-5-1
Contact sequence 131S001
Contact travel■ = Contact closed□ = Contact open 1310DIA-5
Positive opening (ZW) yes
Enclosure covers Yellow
Enclosure covers 116C064
Housing Insulated material
Connection type Cage Clamp
Notes Cage-Clamp is a registered trademark of Wago Kontakttechnik, 32432 Minden, Germany.
Accessories for the Cage-Clamp terminals from Wago:power comb, gray, Wago Article No. 264-402
Notes The operating head can be rotated at 90° intervals to adapt to the specified approach direction.
Standards IEC/EN 60947
Climatic proofing Damp heat, constant, to IEC 60068-2-78; damp heat, cyclical, to IEC 60068-2-30
Ambient temperature -40 - +70 °C
Mounting position As required
Degree of Protection IP66, IP67
Terminal capacities
>Solid
1 x (0.5 - 2.5) mm2
Terminal capacities
>Flexible with ferrule
1 x (0.5 - 1.5) mm2
Repetition accuracy 0.15 mm
Rated impulse withstand voltage [Uimp] 4000 V AC
Rated insulation voltage [Ui ] 400 V
Overvoltage category/pollution degree III/3
Rated operational current [Ie ]
>AC-15
>24 V [Ie ]
6 A
Rated operational current [Ie ]
>AC-15
>220 V 230 V 240 V [Ie]
6 A
Rated operational current [Ie ]
>AC-15
>380 V 400 V 415 V [Ie]
4 A
Rated operational current [Ie ]
>DC-13
>24 V [Ie ]
3 A
Rated operational current [Ie ]
>DC-13
>110 V [Ie ]
0.6 A
Rated operational current [Ie ]
>DC-13
>220 V [Ie ]
0.3 A
Control circuit reliability
>at 24 V DC/5 mA [HF ]
< 10 -7, < 1 fault in 107 operations Fault probability
Control circuit reliability
>at 5 V DC/1 mA [HF ]
< 5 x 10-6, < 1 failure at 5 x 106 operations Fault probability
Supply frequency max. 400 Hz
Short-circuit rating to IEC/EN 60947-5-1
>max. fuse
6 A gG/gL
Lifespan, mechanical [Operations] 8 x 106
Mechanical shock resistance (half-sinusoidal shock, 20 ms)
>Standard-action contact
25 g
Operating frequency [Operations/h] ≦ 6000
Mechanical
>Actuating force at beginning/end of stroke
1.0/8.0 N
Mechanical
>Actuating torque of rotary drives
0.2 Nm
Mechanical
>Max. operating speed with DIN cam
1.5 m/s
Mechanical
>Notes
for angle of actuation α = 0°
Rated operational current for specified heat dissipation [In] 6 A
Heat dissipation per pole, current-dependent [Pvid] 0.17 W
Equipment heat dissipation, current-dependent [Pvid] 0 W
Static heat dissipation, non-current-dependent [Pvs] 0 W
Heat dissipation capacity [Pdiss] 0 W
Operating ambient temperature min. -40 °C
Operating ambient temperature max. +70 °C
10.2 Strength of materials and parts
>10.2.2 Corrosion resistance
Meets the product standard´s requirements.
10.2 Strength of materials and parts
>10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard´s requirements.
10.2 Strength of materials and parts
>10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard´s requirements.
10.2 Strength of materials and parts
>10.2.3.3 Verification of resistance of insulating materials to abnormal heat and fire due to internal electric effects
Meets the product standard´s requirements.
10.2 Strength of materials and parts
>10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard´s requirements.
10.2 Strength of materials and parts
>10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
10.2 Strength of materials and parts
>10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.2 Strength of materials and parts
>10.2.7 Inscriptions
Meets the product standard´s requirements.
10.3 Degree of protection of ASSEMBLIES Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances Meets the product standard´s requirements.
10.5 Protection against electric shock Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections Is the panel builder´s responsibility.
10.8 Connections for external conductors Is the panel builder´s responsibility.
10.9 Insulation properties
>10.9.2 Power-frequency electric strength
Is the panel builder´s responsibility.
10.9 Insulation properties
>10.9.3 Impulse withstand voltage
Is the panel builder´s responsibility.
10.9 Insulation properties
>10.9.4 Testing of enclosures made of insulating material
Is the panel builder´s responsibility.
10.10 Temperature rise The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
10.11 Short-circuit rating Is the panel builder´s responsibility. The specifications for the switchgear must be observed.
10.12 Electromagnetic compatibility Is the panel builder´s responsibility. The specifications for the switchgear must be observed.
10.13 Mechanical function The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
Type of control element Rotary lever
Product Standards IEC/EN 60947-5; UL 508; CSA-C22.2 No. 14; CE marking
UL File No. E29184
UL Category Control No. NKCR
CSA File No. 12528
CSA Class No. 3211-03
North America Certification UL listed, CSA certified
Degree of Protection IEC: IP66, 67, UL/CSA Type 3R, 4X (indoor use only), 12, 13

As Mnelko, we are a reliable partner in industrial automation solutions, offering high-quality and innovative products with a wide product range to meet all the needs of your business. Our product portfolio consists of solutions designed based on the principles of high performance, durability, and efficiency to support modern industrial processes.
All of our products ensure maximum reliability even in challenging working conditions and help your business operations run smoothly. The products we offer in industrial automation, energy management, cabling solutions, and many other areas adapt flexibly to the needs of different sectors.
Additionally, our products are manufactured using only high-quality materials and comply with international standards. Through the solutions we provide, we enable our customers to increase operational efficiency and optimize costs. Our company closely follows technological advancements and continuously offers innovative products to help our customers gain a competitive advantage.
On each of our product pages, you can find comprehensive information about technical details, areas of use, and product features. You can explore all the products you need to strengthen your industrial processes on our website and enjoy a seamless purchasing experience.