Product range |
Accessories |
Single unit/Complete unit |
Single unit |
Basic function accessories |
Contact elements |
Connection technique |
Blade terminal |
Description |
admissible operating voltage: 5 – 250 V |
N/C = Normally closed |
1 NC |
Notes |
= safety function, by positive opening to IEC/EN 60947-5-1 |
Contact sequence |
|
Contact travel diagram, stroke in connection with front element |
|
Degree of Protection |
IP20 with ISH2,8 |
Connection to SmartWire-DT |
no |
Standards |
IEC/EN 60947 |
Lifespan, mechanical [Operations] |
> 100 x 106 |
Operating frequency [Operations/h] |
≦ 3600 |
Actuating force |
≦ 3 n |
Degree of protection, IEC/EN 60529 |
IP20 with ISH2,8 |
Climatic proofing |
Damp heat, constant, to IEC 60068-2-78 Damp heat, cyclic, to IEC 60068-2-30 |
Ambient temperature >Open |
-25 - +60 °C |
Ambient temperature >Enclosed |
- 25 - 40 °C |
Mounting position |
As required |
Mechanical shock resistance |
> 40 according to IEC 60068-2-27 Shock duration 11 ms Sinusoidal g |
Terminal capacities |
0.5 - 1.0 mm2
|
Blade terminal |
2.8 x 0.8 mm to DIN 46244 |
Fast-on connectors |
2.8 x 0.8 mm to DIN 46247 and IEC 60760 |
Rated impulse withstand voltage [Uimp] |
4000 V AC |
Rated insulation voltage [Ui
] |
250 V |
Overvoltage category/pollution degree |
III/3 |
Rated operational voltage [Ue] |
250 V AC |
Control circuit reliability >at 24 V DC/5 mA [HF
] |
< 10-7 (i.e. 1 failure to 107 operations) Fault probability |
Control circuit reliability >at 5 V DC/1 mA [HF
] |
< 5 x 10-6 (i.e. 1 failure in 5 x 106 operations) Fault probability |
Use of insulated ferrule ISH 2,8 |
>24 V AC/DC recommended >50 V AC or 120 V DC is mandatory, even on unused blade terminals |
Max. short-circuit protective device >Fuseless |
FAZ-B6/1 Type |
Max. short-circuit protective device >Fuse [gG/gL] |
10 A |
Rated operational current [Ie
] >AC-15 >24 V [Ie
] |
4 A |
Rated operational current [Ie
] >AC-15 >48 V [Ie
] |
4 A |
Rated operational current [Ie
] >AC-15 >110 V [Ie
] |
4 A |
Rated operational current [Ie
] >AC-15 >220 V 230 V 240 V [Ie] |
4 A |
Rated operational current [Ie
] >DC-13 >24 V [Ie
] |
1.5 A |
Rated operational current [Ie
] >DC-13 >42 V [Ie
] |
1 A |
Rated operational current [Ie
] >DC-13 >60 V [Ie
] |
0.8 A |
Rated operational current [Ie
] >DC-13 >110 V [Ie
] |
0.5 A |
Rated operational current [Ie
] >DC-13 >220 V [Ie
] |
0.2 A |
Lifespan, electrical AC-15 to IEC/EN 60947-5-1 at 230 V; Ie = rated operational current |
|
Rated operational current for specified heat dissipation [In] |
4 A |
Heat dissipation per pole, current-dependent [Pvid] |
0.1 W |
Equipment heat dissipation, current-dependent [Pvid] |
0 W |
Static heat dissipation, non-current-dependent [Pvs] |
0 W |
Heat dissipation capacity [Pdiss] |
0 W |
Operating ambient temperature min. |
-25 °C |
Operating ambient temperature max. |
+60 °C |
10.2 Strength of materials and parts >10.2.2 Corrosion resistance |
Meets the product standard´s requirements. |
10.2 Strength of materials and parts >10.2.3.1 Verification of thermal stability of enclosures |
Meets the product standard´s requirements. |
10.2 Strength of materials and parts >10.2.3.2 Verification of resistance of insulating materials to normal heat |
Meets the product standard´s requirements. |
10.2 Strength of materials and parts >10.2.3.3 Verification of resistance of insulating materials to abnormal heat and fire due to internal electric effects |
Meets the product standard´s requirements. |
10.2 Strength of materials and parts >10.2.4 Resistance to ultra-violet (UV) radiation |
Meets the product standard´s requirements. |
10.2 Strength of materials and parts >10.2.5 Lifting |
Does not apply, since the entire switchgear needs to be evaluated. |
10.2 Strength of materials and parts >10.2.6 Mechanical impact |
Does not apply, since the entire switchgear needs to be evaluated. |
10.2 Strength of materials and parts >10.2.7 Inscriptions |
Meets the product standard´s requirements. |
10.3 Degree of protection of ASSEMBLIES |
Does not apply, since the entire switchgear needs to be evaluated. |
10.4 Clearances and creepage distances |
Meets the product standard´s requirements. |
10.5 Protection against electric shock |
Does not apply, since the entire switchgear needs to be evaluated. |
10.6 Incorporation of switching devices and components |
Does not apply, since the entire switchgear needs to be evaluated. |
10.7 Internal electrical circuits and connections |
Is the panel builder´s responsibility. |
10.8 Connections for external conductors |
Is the panel builder´s responsibility. |
10.9 Insulation properties >10.9.2 Power-frequency electric strength |
Is the panel builder´s responsibility. |
10.9 Insulation properties >10.9.3 Impulse withstand voltage |
Is the panel builder´s responsibility. |
10.9 Insulation properties >10.9.4 Testing of enclosures made of insulating material |
Is the panel builder´s responsibility. |
10.10 Temperature rise |
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices. |
10.11 Short-circuit rating |
Is the panel builder´s responsibility. The specifications for the switchgear must be observed. |
10.12 Electromagnetic compatibility |
Is the panel builder´s responsibility. The specifications for the switchgear must be observed. |
10.13 Mechanical function |
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed. |
Number of contacts as change-over contact |
0 |
Number of contacts as normally open contact |
0 |
Number of contacts as normally closed contact |
1 |
Number of fault-signal switches |
0 |
Rated operation current Ie at AC-15, 230 V |
6 A |
Type of electric connection |
Screw connection |
Model |
Top mounting |
Mounting method |
Front fastening |
Lamp holder |
None |
Product Standards |
IEC/EN 60947-5; UL 508; CSA-C22.2 No. 14-05; CE marking |
UL File No. |
E29184 |
UL Category Control No. |
NKCR |
CSA File No. |
46552 |
CSA Class No. |
3211-03 |
North America Certification |
UL listed, CSA certified |