Product range |
Contactors |
Application |
Contactors for Motors |
Subrange |
Standard devices greater than 170 A |
Utilization category |
AC-1: Non-inductive or slightly inductive loads, resistance furnaces NAC-3: Normal AC induction motors: starting, switch off during running AC-4: Normal AC induction motors: starting, plugging, reversing, inching |
Connection technique |
Screw connection |
AC-3 >380 V 400 V [Ie] |
|
AC-1 >Conventional free air thermal current, 3 pole, 50 - 60 Hz >Open >at 40 °C [Ith =Ie] |
400 A |
AC-1 >Conventional free air thermal current, 3 pole, 50 - 60 Hz >enclosed [Ith
] |
612 A |
AC-1 >Conventional free air thermal current, 1 pole >open [Ith
] |
450 A |
AC-1 >Conventional free air thermal current, 1 pole >enclosed [Ith
] |
1250 A |
AC-3 >220 V 230 V [P] |
1125 A |
AC-3 >380 V 400 V [P] |
|
AC-3 >660 V 690 V [P] |
125 kW |
AC-3 >1000 V [P] |
212 kW |
AC-4 >220 V 230 V [P] |
300 kW |
AC-4 >380 V 400 V [P] |
132 kW |
AC-4 >660 V 690 V [P] |
92 kW |
AC-4 >1000 V [P] |
160 kW |
Contact sequence |
240 kW |
Can be combined with auxiliary contact |
132 kW |
Actuating voltage |
|
Voltage AC/DC |
DILM820-XHI… |
N/O = Normally open |
220 - 240 V 50/60 Hz |
N/C = Normally closed |
AC operation |
possible variants at auxiliary contact module fitting options |
|
Side mounting auxiliary contacts |
2 N/O |
Instructions |
2 NC |
Instructions |
|
Notes |
on the side: 2 x DILM820-XHI11(V)-SI; 2 x DILM820-XHI11-SA |
Standards |
|
Lifespan, mechanical >AC operated [Operations] |
Interlocked opposing contacts according to IEC/EN 60947-5-1 Appendix L, inside the auxiliary contact module Auxiliary contacts used as mirror contacts according to IEC/EN 60947-4-1 Appendix F (not N/C late open) |
Operating frequency, mechanical >AC operated [Operations/h] |
integrated suppressor circuit in actuating electronics 660 V, 690 V or 1000 V: not directly reversing |
Climatic proofing |
DILM…-S power contactors are actuated traditionally |
| ① Stopping in the event of an emergency (emergency switching off) |
|
Ambient temperature >Open |
|
Ambient temperature >Enclosed |
IEC/EN 60947, VDE 0660, UL, CSA |
Ambient temperature >Storage |
7 x 106
|
Mounting position |
2000 |
Mechanical shock resistance (IEC/EN 60068-2-27) >Half-sinusoidal shock, 10 ms >Main contacts >N/O contact |
Damp heat, constant, to IEC 60068-2-78 Damp heat, cyclic, to IEC 60068-2-30 |
Mechanical shock resistance (IEC/EN 60068-2-27) >Half-sinusoidal shock, 10 ms >Auxiliary contacts >N/O contact |
-40 - +60 °C |
Mechanical shock resistance (IEC/EN 60068-2-27) >Half-sinusoidal shock, 10 ms >Auxiliary contacts >N/C contact |
- 40 - + 40 °C |
Degree of Protection |
- 40 - + 80 °C |
Protection against direct contact when actuated from front (EN 50274) |
|
Altitude |
10 g |
Weight >AC operated |
10 g |
Weight >DC operated |
8 g |
Weight >Weight |
IP00 |
Terminal capacity main cable >Flexible with cable lug |
Finger and back-of-hand proof with terminal shroud or terminal block |
Terminal capacity main cable >Stranded with cable lug |
Max. 2000 m |
Terminal capacity main cable >Solid or stranded |
8.42 kg |
Terminal capacity main cable >Flat conductor [Lamellenzahl x Breite x Dicke ] |
8.42 kg |
Terminal capacity main cable >Busbar [Width] |
8.42 kg |
Main cable connection screw/bolt |
50 - 240 mm2
|
Tightening torque |
70 - 240 mm2
|
Terminal capacity control circuit cables >Solid |
2/0 - 500 MCM AWG |
Terminal capacity control circuit cables >Flexible with ferrule |
Fixing with flat cable terminal or cable terminal blocks See terminal capacity for cable terminal blocks mm |
Terminal capacity control circuit cables >Solid or stranded |
25 mm |
Control circuit cable connection screw/bolt |
M10 |
Tightening torque |
24 Nm |
Tool >Main cable >Width across flats |
1 x (0.75 - 2.5) 2 x (0.75 - 2.5) mm2 |
Tool >Control circuit cables >Pozidriv screwdriver |
1 x (0.75 - 2.5) 2 x (0.75 - 2.5) mm2 |
Rated impulse withstand voltage [Uimp] |
18 - 14 AWG |
Overvoltage category/pollution degree |
M3.5 |
Rated insulation voltage [Ui] |
1.2 Nm |
Rated operational voltage [Ue] |
16 mm |
Safe isolation to EN 61140 >between coil and contacts |
2 Size |
Safe isolation to EN 61140 >between the contacts |
|
Making capacity (p.f. to IEC/EN 60947) |
8000 V AC |
Breaking capacity >220 V 230 V |
III/3 |
Breaking capacity >380 V 400 V |
1000 V AC |
Breaking capacity >500 V |
1000 V AC |
Breaking capacity >660 V 690 V |
500 V AC |
Breaking capacity >1000 V |
500 V AC |
Component lifespan |
5500 A |
Short-circuit rating >Short-circuit protection maximum fuse >Type “2” coordination >400 V [gG/gL 500 V] |
5000 A |
Short-circuit rating >Short-circuit protection maximum fuse >Type “2” coordination >690 V [gG/gL 690 V] |
5000 A |
Short-circuit rating >Short-circuit protection maximum fuse >Type “2” coordination >1000 V [gG/gL 1000 V] |
5000 A |
Short-circuit rating >Short-circuit protection maximum fuse >Type “1” coordination >400 V [gG/gL 500 V] |
5000 A |
Short-circuit rating >Short-circuit protection maximum fuse >Type “1” coordination >690 V [gG/gL 690 V] |
950 A |
Short-circuit rating >Short-circuit protection maximum fuse >Type “1” coordination >1000 V [gG/gL 1000 V] |
AC1: See → Engineering, characteristic curves AC3: See → Engineering, characteristic curves AC4: See → Engineering, characteristic curves |
AC-1 >Rated operational current >Conventional free air thermal current, 3 pole, 50 - 60 Hz >Open >at 40 °C [Ith =Ie] |
500 A |
AC-1 >Rated operational current >Conventional free air thermal current, 3 pole, 50 - 60 Hz >Open >at 50 °C [Ith =Ie] |
500 A |
AC-1 >Rated operational current >Conventional free air thermal current, 3 pole, 50 - 60 Hz >Open >at 55 °C [Ith =Ie] |
200 A |
AC-1 >Rated operational current >Conventional free air thermal current, 3 pole, 50 - 60 Hz >Open >at 60 °C [Ith =Ie] |
630 A |
AC-1 >Rated operational current >Conventional free air thermal current, 3 pole, 50 - 60 Hz >enclosed [Ith
] |
630 A |
AC-1 >Rated operational current >Conventional free air thermal current, 3 pole, 50 - 60 Hz >Notes |
250 A |
AC-1 >Rated operational current >Conventional free air thermal current, 1 pole >Note |
|
AC-1 >Rated operational current >Conventional free air thermal current, 1 pole >open [Ith
] |
612 A |
AC-1 >Rated operational current >Conventional free air thermal current, 1 pole >enclosed [Ith
] |
548 A |
AC-3 >Rated operational current >Open, 3-pole: 50 – 60 Hz >Notes |
522 A |
AC-3 >Rated operational current >Open, 3-pole: 50 – 60 Hz >220 V 230 V [Ie] |
500 A |
AC-3 >Rated operational current >Open, 3-pole: 50 – 60 Hz >240 V [Ie] |
450 A |
AC-3 >Rated operational current >Open, 3-pole: 50 – 60 Hz >380 V 400 V [Ie] |
At maximum permissible ambient air temperature. |
AC-3 >Rated operational current >Open, 3-pole: 50 – 60 Hz >415 V [Ie] |
at maximum permissible ambient air temperature |
AC-3 >Rated operational current >Open, 3-pole: 50 – 60 Hz >440V [Ie] |
1250 A |
AC-3 >Rated operational current >Open, 3-pole: 50 – 60 Hz >500 V [Ie] |
1125 A |
AC-3 >Rated operational current >Open, 3-pole: 50 – 60 Hz >660 V 690 V [Ie] |
At maximum permissible ambient temperature (open.) |
AC-3 >Rated operational current >Open, 3-pole: 50 – 60 Hz >1000 V [Ie
] |
400 A |
AC-3 >Motor rating [P] >220 V 230 V [P] |
400 A |
AC-3 >Motor rating [P] >240V [P] |
400 A |
AC-3 >Motor rating [P] >380 V 400 V [P] |
400 A |
AC-3 >Motor rating [P] >415 V [P] |
400 A |
AC-3 >Motor rating [P] >440 V [P] |
400 A |
AC-3 >Motor rating [P] >500 V [P] |
325 A |
AC-3 >Motor rating [P] >660 V 690 V [P] |
95 A |
AC-3 >Motor rating [P] >1000 V [P] |
125 kW |
AC-4 >Rated operational current >Open, 3-pole: 50 – 60 Hz >220 V 230 V [Ie
] |
132 kW |
AC-4 >Rated operational current >Open, 3-pole: 50 – 60 Hz >240 V [Ie
] |
212 kW |
AC-4 >Rated operational current >Open, 3-pole: 50 – 60 Hz >380 V 400 V [Ie
] |
232 kW |
AC-4 >Rated operational current >Open, 3-pole: 50 – 60 Hz >415 V [Ie
] |
250 kW |
AC-4 >Rated operational current >Open, 3-pole: 50 – 60 Hz >440 V [Ie
] |
280 kW |
AC-4 >Rated operational current >Open, 3-pole: 50 – 60 Hz >500 V [Ie
] |
300 kW |
AC-4 >Rated operational current >Open, 3-pole: 50 – 60 Hz >660 V 690 V [Ie
] |
132 kW |
AC-4 >Rated operational current >Open, 3-pole: 50 – 60 Hz >1000 V [Ie
] |
296 A |
AC-4 >Motor rating [P] >220 V 230 V [P] |
296 A |
AC-4 >Motor rating [P] >240 V [P] |
296 A |
AC-4 >Motor rating [P] >380 V 400 V [P] |
296 A |
AC-4 >Motor rating [P] >415 V [P] |
296 A |
AC-4 >Motor rating [P] >440 V [P] |
296 A |
AC-4 >Motor rating [P] >500 V [P] |
260 A |
AC-4 >Motor rating [P] >660 V 690 V [P] |
95 A |
AC-4 >Motor rating [P] >1000 V [P] |
92 kW |
Individual compensation, rated operational current Ie of three-phase capacitors >Open >up to 525 V |
100 kW |
Individual compensation, rated operational current Ie of three-phase capacitors >Open >690 V |
160 kW |
Max. inrush current peak |
176 kW |
Component lifespan [Operations] |
186 kW |
Max. operating frequency |
210 kW |
Rated operational current, open >DC-1 >Notes |
240 kW |
3 pole, at Ith (60°) |
132 kW |
Current heat loss at Ie to AC-3/400 V |
|
Voltage tolerance >US |
307 A |
Voltage tolerance >AC operated [Pick-up] |
177 A |
Voltage tolerance >AC operated [Drop-out] |
30 x Ie |
Power consumption of the coil in a cold state and 1.0 x US >Note on power consumption |
0.1 x 106
|
Power consumption of the coil in a cold state and 1.0 x US >Pull-in power [Pick-up] |
200 Ops/h |
Power consumption of the coil in a cold state and 1.0 x US >Pull-in power [Pick-up] |
|
Power consumption of the coil in a cold state and 1.0 x US >Sealing power [Sealing] |
see DILDC300/DILDC600 or on request |
Power consumption of the coil in a cold state and 1.0 x US >Sealing power [Sealing] |
|
Duty factor |
58 W |
Changeover time at 100 % US (recommended value) >Main contacts >Closing delay |
37 W |
Changeover time at 100 % US (recommended value) >Main contacts >Opening delay |
|
Behaviour in marginal and transitional conditions >Sealing >Voltage interruptions >(0 … 0.2 x Uc min) ≦ 10 ms |
220 - 240 V 50/60 Hz |
Behaviour in marginal and transitional conditions >Sealing >Voltage interruptions >(0 … 0.2 x Uc min) > 10 ms |
0.85 x US min - 1.1 x US max |
Behaviour in marginal and transitional conditions >Sealing >Voltage drops >(0.2 … 0.6 x Uc min) ≦ 12 ms |
0.2 x US min - 0.4 x US max |
Behaviour in marginal and transitional conditions >Sealing >Voltage drops >(0.2 … 0.6 x Uc min) > 12 ms |
Control transformer with uk ≦ 10% |
Behaviour in marginal and transitional conditions >Sealing >Voltage drops >(0.6 … 0.7 x Uc min) |
715 VA |
Behaviour in marginal and transitional conditions >Sealing >Excess voltage >(1.15 … 1.3 x Uc max) |
645 W |
Behaviour in marginal and transitional conditions >Sealing >Pick-up phase >(0 … 0.7 x Uc min) |
6.8 VA |
Behaviour in marginal and transitional conditions >Sealing >Pick-up phase >(0.7 x Uc min … 1.15 x Uc max) |
4 W |
Admissible transitional contact resistance
(of the external control circuit device when actuating A11) |
100 % DF |
Electromagnetic compatibility |
55 ms |
Switching capacity >Maximum motor rating >Three-phase >200 V 208 V |
50 ms |
Switching capacity >Maximum motor rating >Three-phase >230 V 240 V |
Time is bridged successfully |
Switching capacity >Maximum motor rating >Three-phase >460 V 480 V |
Drop-out of the contactor |
Switching capacity >Maximum motor rating >Three-phase >575 V 600 V |
Time is bridged successfully |
Switching capacity >General use |
Drop-out of the contactor |
Auxiliary contacts >Pilot Duty >AC operated |
Contactor remains switched on |
Auxiliary contacts >Pilot Duty >DC operated |
Contactor remains switched on |
Auxiliary contacts >General Use >AC |
Contactor does not switch on |
Auxiliary contacts >General Use >AC |
Contactor switches on with certainty |
Auxiliary contacts >General Use >DC |
≦ 500 mΩ |
Auxiliary contacts >General Use >DC |
|
Short Circuit Current Rating >Basic Rating >SCCR |
This product is designed for operation in industrial environments (environment A). Its use in residential environments (environment B) may cause radio-frequency interference, requiring additional noise suppression measures. |
Short Circuit Current Rating >Basic Rating >max. Fuse |
|
Short Circuit Current Rating >Basic Rating >max. CB |
125 HP |
Short Circuit Current Rating >480 V High Fault >SCCR (fuse) |
150 HP |
Short Circuit Current Rating >480 V High Fault >max. Fuse |
300 HP |
Short Circuit Current Rating >480 V High Fault >SCCR (CB) |
400 HP |
Short Circuit Current Rating >480 V High Fault >max. CB |
450 A |
Short Circuit Current Rating >600 V High Fault >SCCR (fuse) |
A600 |
Short Circuit Current Rating >600 V High Fault >max. Fuse |
P300 |
Short Circuit Current Rating >600 V High Fault >SCCR (CB) |
600 V |
Short Circuit Current Rating >600 V High Fault >max. CB |
15 A |
Special Purpose Ratings >Definite Purpose Ratings (100,000 cycles acc. to UL 1995) >LRA 480V 60Hz 3phase |
250 V |
Special Purpose Ratings >Definite Purpose Ratings (100,000 cycles acc. to UL 1995) >FLA 480V 60Hz 3phase |
1 A |
Special Purpose Ratings >Definite Purpose Ratings (100,000 cycles acc. to UL 1995) >LRA 600V 60Hz 3phase |
30 kA |
Special Purpose Ratings >Definite Purpose Ratings (100,000 cycles acc. to UL 1995) >FLA 600V 60Hz 3phase |
800 A |
Rated operational current for specified heat dissipation [In] |
600 A |
Heat dissipation per pole, current-dependent [Pvid] |
30/100 kA |
Equipment heat dissipation, current-dependent [Pvid] |
800/600 Class J A |
Static heat dissipation, non-current-dependent [Pvs] |
100 kA |
Heat dissipation capacity [Pdiss] |
600 A |
Operating ambient temperature min. |
30/100 kA |
Operating ambient temperature max. |
800/600 Class J A |
10.2 Strength of materials and parts >10.2.2 Corrosion resistance |
30 kA |
10.2 Strength of materials and parts >10.2.3.1 Verification of thermal stability of enclosures |
600 A |
10.2 Strength of materials and parts >10.2.3.2 Verification of resistance of insulating materials to normal heat |
3300 A |
10.2 Strength of materials and parts >10.2.3.3 Verification of resistance of insulating materials to abnormal heat and fire due to internal electric effects |
550 A |
10.2 Strength of materials and parts >10.2.4 Resistance to ultra-violet (UV) radiation |
3120 A |
10.2 Strength of materials and parts >10.2.5 Lifting |
420 A |
10.2 Strength of materials and parts >10.2.6 Mechanical impact |
|
10.2 Strength of materials and parts >10.2.7 Inscriptions |
400 A |
10.3 Degree of protection of ASSEMBLIES |
12.33 W |
10.4 Clearances and creepage distances |
0 W |
10.5 Protection against electric shock |
3.3 W |
10.6 Incorporation of switching devices and components |
0 W |
10.7 Internal electrical circuits and connections |
-40 °C |
10.8 Connections for external conductors |
+60 °C |
10.9 Insulation properties >10.9.2 Power-frequency electric strength |
|
10.9 Insulation properties >10.9.3 Impulse withstand voltage |
Meets the product standard´s requirements. |
10.9 Insulation properties >10.9.4 Testing of enclosures made of insulating material |
Meets the product standard´s requirements. |
10.10 Temperature rise |
Meets the product standard´s requirements. |
10.11 Short-circuit rating |
Meets the product standard´s requirements. |
10.12 Electromagnetic compatibility |
Meets the product standard´s requirements. |
10.13 Mechanical function |
Does not apply, since the entire switchgear needs to be evaluated. |
Rated control supply voltage Us at AC 50HZ |
Does not apply, since the entire switchgear needs to be evaluated. |
Rated control supply voltage Us at AC 60HZ |
Meets the product standard´s requirements. |
Rated control supply voltage Us at DC |
Does not apply, since the entire switchgear needs to be evaluated. |
Voltage type for actuating |
Meets the product standard´s requirements. |
Rated operation current Ie at AC-1, 400 V |
Does not apply, since the entire switchgear needs to be evaluated. |
Rated operation current Ie at AC-3, 400 V |
Does not apply, since the entire switchgear needs to be evaluated. |
Rated operation power at AC-3, 400 V |
Is the panel builder´s responsibility. |
Rated operation current Ie at AC-4, 400 V |
Is the panel builder´s responsibility. |
Rated operation power at AC-4, 400 V |
Is the panel builder´s responsibility. |
Rated operation power NEMA |
Is the panel builder´s responsibility. |
Modular version |
Is the panel builder´s responsibility. |
Number of auxiliary contacts as normally open contact |
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices. |
Number of auxiliary contacts as normally closed contact |
Is the panel builder´s responsibility. The specifications for the switchgear must be observed. |
Type of electrical connection of main circuit |
Is the panel builder´s responsibility. The specifications for the switchgear must be observed. |
Number of normally closed contacts as main contact |
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed. |
Number of main contacts as normally open contact |
|
Product Standards |
|
UL File No. |
220 - 240 V |
UL Category Control No. |
220 - 240 V |
CSA File No. |
0 - 0 V |
CSA Class No. |
AC |
North America Certification |
612 A |
Specially designed for North America |
400 A |
Side mounting auxiliary contacts |
200 kW |
possible variants at auxiliary contact module fitting options |
296 A |
Characteristic curve |
160 kW |
Characteristic curve |
223 kW |
Characteristic curve |
No |
Characteristic curve |
2 |