Product range |
Contactors |
Application |
DC contactor |
Subrange |
Comfort devices greater than 170 A |
Instructions |
DILDC contactors feature an electronic arc suppression system. Because of this, it is important not to exceed any technical data limits in general – especially the making and breaking capacity limits. Opening the device will immediately void the warranty. integrated suppressor circuit in actuating electronics |
Connection technique |
Screw connection |
DC-1 >Notes |
|
DC-1 >1000 V [Ie] |
Ie at 60 °C |
Can be combined with auxiliary contact |
600 A |
Actuating voltage |
DILM820-XHI… |
Voltage AC/DC |
RDS 250: 110 - 250 V 40 - 60 Hz/110 - 350 V DC |
N/O = Normally open |
AC and DC operation |
N/C = Normally closed |
|
possible variants at auxiliary contact module fitting options |
2 N/O |
Side mounting auxiliary contacts |
2 NC |
Standards |
|
Lifespan, mechanical >AC operated [Operations] |
on the side: 2 x DILM820-XHI11(V)-SI; 2 x DILM820-XHI11-SA |
Lifespan, mechanical >DC operated [Operations] |
|
Operating frequency, mechanical >AC operated [Operations/h] |
|
Operating frequency, mechanical >DC operated [Operations/h] |
EN60947-4-1, EN60947-5-1 |
Maximum operating frequency >electrical (Contactors without overload relay) [Operations/h] |
1 x 106
|
Climatic proofing |
1 x 106
|
Ambient temperature >Open |
1000 |
Ambient temperature >Enclosed |
1000 |
Ambient temperature >Storage |
100 |
Mounting position |
Damp heat, constant, to IEC 60068-2-78 Damp heat, cyclic, to IEC 60068-2-30 |
Mechanical shock resistance (IEC/EN 60068-2-27) >Half-sinusoidal shock, 10 ms >Main contacts >N/O contact |
-40 - +70 °C |
Mechanical shock resistance (IEC/EN 60068-2-27) >Half-sinusoidal shock, 10 ms >Auxiliary contacts >N/O contact |
- 40 - + 40 °C |
Mechanical shock resistance (IEC/EN 60068-2-27) >Half-sinusoidal shock, 10 ms >Auxiliary contacts >N/C contact |
- 40 - + 80 °C |
Degree of Protection |
|
Protection against direct contact when actuated from front (EN 50274) |
10 g |
Altitude |
10 g |
Weight >Weight |
8 g |
Terminal capacity main cable >Flexible with cable lug |
IP00 |
Terminal capacity main cable >Stranded with cable lug |
Covers on main terminals safeguarded against accidental contact with fingers or back of hand |
Terminal capacity main cable >Solid or stranded |
Max. 2000 m |
Terminal capacity main cable >Busbar [Width] |
7.5 kg |
Main cable connection screw/bolt |
50 - 240 mm2
|
Tightening torque |
50 - 240 mm2
|
Terminal capacity control circuit cables >Solid |
1/0 - 500 MCM AWG |
Terminal capacity control circuit cables >Flexible with ferrule |
40 mm |
Terminal capacity control circuit cables >Solid or stranded |
M10 |
Control circuit cable connection screw/bolt |
24 Nm |
Tightening torque |
1 x (0.75 - 2.5) 2 x (0.75 - 2.5) mm2 |
Tool >Main cable >Width across flats |
1 x (0.75 - 2.5) 2 x (0.75 - 2.5) mm2 |
Tool >Control circuit cables >Pozidriv screwdriver |
2 x (18 - 12) AWG |
Tool >Control circuit cables >Standard screwdriver |
M3.5 |
Rated impulse withstand voltage [Uimp] |
1.2 Nm |
Overvoltage category/pollution degree |
16 mm |
Rated insulation voltage [Ui] |
2 Size |
Rated operational voltage [Ue] |
0.8 x 5.5 1 x 6 mm |
Safe isolation to EN 61140 >Between control inputs and main contacts |
|
Safe isolation to EN 61140 >Between auxiliary contacts and main contacts |
8000 V |
Safe isolation to EN 61140 >between the contacts |
III/3 |
Making capacity |
1000 V DC |
Breaking capacity >220 V 230 V |
1000 V DC |
Breaking capacity >380 V 400 V |
1000 V |
Breaking capacity >500 V |
1000 V |
Breaking capacity >660 V 690 V |
1000 V |
Breaking capacity >1000 V |
900 A |
Short-circuit rating >Short-circuit protection maximum fuse >Type “2” coordination >400 V DC [gR 1000 VDC] |
900 A |
Short-circuit rating >Short-circuit protection maximum fuse >Type “2” coordination >690 V DC [gR 1000 VDC] |
900 A |
Short-circuit rating >Short-circuit protection maximum fuse >Type “2” coordination >1000 V DC [gR 1000 VDC] |
900 A |
Short-circuit rating >Short-circuit protection maximum fuse >Type “1” coordination >400 V DC [gR 1000 VDC] |
900 A |
Short-circuit rating >Short-circuit protection maximum fuse >Type “1” coordination >690 V DC [gR 1000 VDC] |
900 A |
Short-circuit rating >Short-circuit protection maximum fuse >Type “1” coordination >1000 V DC [gR 1000 VDC] |
900 (max. short-circuit current 6 kA) A |
Rated operational current, open >DC-1 >Notes |
900 (max. short-circuit current 6 kA) A |
Rated operational current, open >DC-1 >1000 V [Ie] |
900 (max. short-circuit current 6 kA) A |
1 pole, at Ith |
900 (max. short-circuit current 30 kA) A |
Voltage tolerance >US |
900 (max. short-circuit current 30 kA) A |
Voltage tolerance >AC operated [Pick-up] |
900 (max. short-circuit current 30 kA) A |
Voltage tolerance >DC operated [Pick-up] |
|
Voltage tolerance >AC operated [Drop-out] |
Ie at 60 °C |
Voltage tolerance >DC operated [Drop-out] |
600 A |
Voltage tolerance >Actuation directly from PLC >UC |
|
Voltage tolerance >Actuation directly from PLC >UC min - max |
72 W |
Power consumption of the coil in a cold state and 1.0 x US >Note on power consumption |
|
Power consumption of the coil in a cold state and 1.0 x US >Pull-in power [Pick-up] |
110 - 250 V 40-60 Hz 110 - 350 V DC |
Power consumption of the coil in a cold state and 1.0 x US >Pull-in power [Pick-up] |
0.7 x US min - 1.15 x US max |
Power consumption of the coil in a cold state and 1.0 x US >Sealing power [Sealing] |
0.7 x US min - 1.15 x US max |
Power consumption of the coil in a cold state and 1.0 x US >Sealing power [Sealing] |
0.2 x US max - 0.6 x US min |
Duty factor |
0.2 x US max - 0.6 x US min |
Changeover time at 100 % US (recommended value) >Main contacts >Closing delay |
24 V DC |
Changeover time at 100 % US (recommended value) >Main contacts >Opening delay |
15 - 31,2 V DC |
PLC signal level (A3 - A4) to IEC/EN 61131-2 (type 2) >High |
Control transformer with uk ≦ 6% |
PLC signal level (A3 - A4) to IEC/EN 61131-2 (type 2) >Low |
600 VA |
Electromagnetic compatibility |
550 W |
Switching capacity >Maximum motor rating >Single-phase >General use |
18 VA |
Auxiliary contacts >Pilot Duty >AC operated |
9.5 W |
Auxiliary contacts >Pilot Duty >DC operated |
100 % DF |
Auxiliary contacts >General Use >AC |
80 ms |
Auxiliary contacts >General Use >AC |
40 ms |
Auxiliary contacts >General Use >DC |
15 V |
Auxiliary contacts >General Use >DC |
5 V |
Rated operational current for specified heat dissipation [In] |
|
Heat dissipation per pole, current-dependent [Pvid] |
This product is designed for operation in industrial environments (environment A). Its use in residential environments (environment B) may cause radio-frequency interference, requiring additional noise suppression measures. |
Equipment heat dissipation, current-dependent [Pvid] |
|
Static heat dissipation, non-current-dependent [Pvs] |
600 A |
Heat dissipation capacity [Pdiss] |
A600 |
Operating ambient temperature min. |
P300 |
Operating ambient temperature max. |
600 V |
10.2 Strength of materials and parts >10.2.2 Corrosion resistance |
15 A |
10.2 Strength of materials and parts >10.2.3.1 Verification of thermal stability of enclosures |
250 V |
10.2 Strength of materials and parts >10.2.3.2 Verification of resistance of insulating materials to normal heat |
1 A |
10.2 Strength of materials and parts >10.2.3.3 Verification of resistance of insulating materials to abnormal heat and fire due to internal electric effects |
|
10.2 Strength of materials and parts >10.2.4 Resistance to ultra-violet (UV) radiation |
600 A |
10.2 Strength of materials and parts >10.2.5 Lifting |
72 W |
10.2 Strength of materials and parts >10.2.6 Mechanical impact |
0 W |
10.2 Strength of materials and parts >10.2.7 Inscriptions |
9 W |
10.3 Degree of protection of ASSEMBLIES |
0 W |
10.4 Clearances and creepage distances |
-40 °C |
10.5 Protection against electric shock |
+70 °C |
10.6 Incorporation of switching devices and components |
|
10.7 Internal electrical circuits and connections |
Meets the product standard´s requirements. |
10.8 Connections for external conductors |
Meets the product standard´s requirements. |
10.9 Insulation properties >10.9.2 Power-frequency electric strength |
Meets the product standard´s requirements. |
10.9 Insulation properties >10.9.3 Impulse withstand voltage |
Meets the product standard´s requirements. |
10.9 Insulation properties >10.9.4 Testing of enclosures made of insulating material |
Meets the product standard´s requirements. |
10.10 Temperature rise |
Does not apply, since the entire switchgear needs to be evaluated. |
10.11 Short-circuit rating |
Does not apply, since the entire switchgear needs to be evaluated. |
10.12 Electromagnetic compatibility |
Meets the product standard´s requirements. |
10.13 Mechanical function |
Does not apply, since the entire switchgear needs to be evaluated. |
Rated control supply voltage Us at AC 50HZ |
Meets the product standard´s requirements. |
Rated control supply voltage Us at AC 60HZ |
Does not apply, since the entire switchgear needs to be evaluated. |
Rated control supply voltage Us at DC |
Does not apply, since the entire switchgear needs to be evaluated. |
Voltage type for actuating |
Is the panel builder´s responsibility. |
Rated operation power at DC-3 / DC-5 at 440 V |
Is the panel builder´s responsibility. |
Rated operation current Ie at DC-3 / DC-5 at 440 V |
Is the panel builder´s responsibility. |
Modular version |
Is the panel builder´s responsibility. |
Number of auxiliary contacts as normally open contact |
Is the panel builder´s responsibility. |
Number of auxiliary contacts as normally closed contact |
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices. |
Type of electrical connection of main circuit |
Is the panel builder´s responsibility. The specifications for the switchgear must be observed. |
Number of normally closed contacts as main contact |
Is the panel builder´s responsibility. The specifications for the switchgear must be observed. |
Number of main contacts as normally open contact |
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed. |
Product Standards |
|
UL File No. |
|
UL Category Control No. |
110 - 250 V |
CSA File No. |
110 - 250 V |
CSA Class No. |
110 - 350 V |
North America Certification |
AC/DC |
Specially designed for North America |
0 kW |
Side mounting auxiliary contacts |
0 A |
possible variants at auxiliary contact module fitting options |
No |